A panelboard must have a rating (busbar ampacity) not less than:
a.The minimum feeder capacity required for the load served, as computed per Article 220
b.50% of the service rating
c.The largest single branch circuit only
d.Twice the neutral load
Giải thích
Per 408.30, a panelboard must have a rating not less than the minimum feeder or service capacity required for the load computed under Article 220. Sizing only to a single branch circuit or an arbitrary fraction of the service would leave the busbar under-rated for the actual load.
Trích dẫn luật: 2023 NEC §408.30Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.