Where multiple service disconnects are installed under the 2023 NEC, the general requirement (compared to older editions) is that they be:

a.Operable by a maximum of six movements of the hand in one enclosure
b.Installed in separate enclosures, or in a listed assembly, rather than up to six switches in a single common enclosure
c.Interlocked so only one can open at a time
d.Located outdoors only

Giải thích

The 2023 NEC changed the multiple-disconnect rule so that up to six service disconnects must be in separate enclosures (or part of a listed switchboard, switchgear, or metering-disconnect assembly), rather than as several breakers in one common enclosure. The old six-hand-movement allowance in a single cabinet is no longer the general rule.

Trích dẫn luật: 2023 NEC §230.71