When installing a surge-protective device (SPD), the best practice for the connecting conductors is to:
a.Make them as long as possible for flexibility
b.Coil extra length behind the panel
c.Keep them as short and straight as practicable
d.Route them alongside the grounding electrode conductor for the full length
Giải thích
SPD performance depends on low conductor impedance, so the leads should be kept as short and straight as practicable to minimize added voltage from lead inductance during a surge. Long or coiled leads raise the let-through voltage and reduce protection, defeating the purpose of the device.
Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A detached garage is supplied by a feeder from the main dwelling. At the garage, the code generally requires:
- On a 4-wire delta system where the midpoint of one phase is grounded, the conductor with the higher voltage to ground (the high leg) must be durably and permanently marked, typically colored:
- A service raceway enters a building from an underground distribution system. To prevent moisture and gases from entering, the raceway must be:
- Where multiple service disconnects are installed under the 2023 NEC, the general requirement (compared to older editions) is that they be:
- In a standard dwelling load calculation, the general lighting and receptacle load demand factor applies 100% to:
- A series-rated combination of overcurrent devices is permitted to protect equipment where the available fault current exceeds the interrupting rating of a downstream device, provided the combination is:
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra