Per 334.30, Type NM cable must be secured and supported at intervals not exceeding what distance along the run?
a.3 ft (900 mm)
b.6 ft (1.8 m)
c.4-1/2 ft (1.4 m)
d.10 ft (3.0 m)
Giải thích
Section 334.30 requires NM cable to be secured at intervals not exceeding 4-1/2 ft, and within 12 in of every box or fitting. 6 ft is the MC interval, while 3 ft and 10 ft are not NM support values.
Trích dẫn luật: 2023 NEC §334.30Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.