Mạch nhánh & Đi dâyCâu 221 / 521
Per 330.30, Type MC cable must be supported and secured at intervals not exceeding what distance?
a.6 ft (1.8 m)
b.4-1/2 ft (1.4 m)
c.3 ft (900 mm)
d.10 ft (3.0 m)
Giải thích
Section 330.30 requires MC cable to be secured at intervals not exceeding 6 ft, and within 12 in of a box where practicable. 4-1/2 ft is the NM/AC interval; 3 ft and 10 ft are not MC support values.
Trích dẫn luật: 2023 NEC §330.30Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.