For the same 5 HP, 230 V motor (FLC 15.2 A), what is the maximum instantaneous-trip circuit breaker setting permitted by Table 430.52?
a.45.6 A
b.38 A
c.76 A
d.121.6 A
Giải thích
Table 430.52 permits an instantaneous-trip breaker up to 800% of FLC for most motors: 15.2 x 8 = 121.6 A. 45.6 A is 300%, 38 A is 250%, and 76 A is 500%.
Trích dẫn luật: 2023 NEC §430.52Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.