Which motor current rating is used to select the running overload (overcurrent) protection device?
a.The Table 430.250 full-load current
b.The motor nameplate full-load amperes
c.The locked-rotor current from Table 430.251
d.250% of the full-load current
Giải thích
NEC 430.6(A)(2) and 430.32 base overload protection on the motor's nameplate full-load amperes, because overloads protect the actual motor. The table FLC is used for conductors and short-circuit protection, not overload sizing.
Trích dẫn luật: 2023 NEC §430.32Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A 5 HP, 230 V, three-phase motor has an FLC of 15.2 A. What is the maximum nontime-delay fuse permitted by Table 430.52 for branch-circuit protection?
- For the same 5 HP, 230 V motor (FLC 15.2 A), what is the maximum instantaneous-trip circuit breaker setting permitted by Table 430.52?
- When sizing branch-circuit conductors and short-circuit/ground-fault protection for a standard motor, which current value does the NEC require you to use?
- A motor nameplate reads 28 A full-load, service factor 1.0, temperature rise not marked. What is the maximum overload rating under NEC 430.32(A)(1)?
- A feeder supplies two three-phase, 460 V motors: 20 HP (FLC 27 A) and 10 HP (FLC 14 A). Per NEC 430.24, what minimum feeder conductor ampacity is required?
- A motor disconnecting means must have an ampere rating at least 115% of the motor FLC. For a 15 HP, 460 V, three-phase motor (FLC 21 A), what is the minimum disconnect ampere rating?