A rooftop A/C unit has one compressor at 30 A rated-load and a condenser fan at 1.5 A. What is the minimum circuit ampacity (MCA), using 125% of the largest motor plus other loads?
a.37.5 A
b.31.5 A
c.39 A
d.40.5 A
Giải thích
MCA = (30 x 1.25) + 1.5 = 37.5 + 1.5 = 39 A. 37.5 A forgets the fan, 31.5 A applies 125% to a wrong base, and 40.5 A applies 125% to both loads.
Trích dẫn luật: 2023 NEC §440.33Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- For the 100 HP, 460 V motor (FLC 124 A), what is the maximum dual-element (time-delay) fuse per Table 430.52 (175%)?
- In a typical motor branch circuit, which sequence correctly lists the components from the supply toward the motor?
- An HVAC nameplate lists MCA = 27.5 A and MOCP = 45 A. What is the minimum ampacity the branch-circuit conductors must have?
- An HVAC nameplate specifies 'Maximum Fuse or HACR Breaker.' What does HACR indicate?
- What is the rated secondary current of a 75 kVA, three-phase transformer with a 208 V secondary?
- For the 75 kVA transformer with a 208 A secondary, what is the maximum secondary overcurrent protective device using the 125% value of Table 450.3(B)?