For the 100 HP, 460 V motor (FLC 124 A), what is the maximum dual-element (time-delay) fuse per Table 430.52 (175%)?
a.310 A
b.372 A
c.155 A
d.217 A
Giải thích
Dual-element time-delay fuse: 175% of FLC = 124 x 1.75 = 217 A. 310 A is 250% (inverse-time breaker), 372 A is 300% (nontime-delay fuse), and 155 A is 125% (conductor factor).
Trích dẫn luật: 2023 NEC §430.52Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Per NEC Table 430.248, what is the full-load current of a 2 HP, single-phase, 230 V motor?
- Using NEC Table 430.250, what is the full-load current of a 100 HP, 460 V, three-phase motor?
- For a 100 HP, 460 V motor (FLC 124 A), what minimum branch-circuit conductor ampacity does NEC 430.22 require?
- In a typical motor branch circuit, which sequence correctly lists the components from the supply toward the motor?
- An HVAC nameplate lists MCA = 27.5 A and MOCP = 45 A. What is the minimum ampacity the branch-circuit conductors must have?
- A rooftop A/C unit has one compressor at 30 A rated-load and a condenser fan at 1.5 A. What is the minimum circuit ampacity (MCA), using 125% of the largest motor plus other loads?