Thiết bị & Hệ thốngCâu 277 / 521
Per NEC Table 430.248, what is the full-load current of a 2 HP, single-phase, 230 V motor?
a.12 A
b.24 A
c.10 A
d.17 A
Giải thích
Table 430.248 lists 12 A for a 2 HP, 230 V single-phase motor. 24 A is the same HP at 115 V, 10 A is a 1.5 HP 230 V motor, and 17 A is a 3 HP 230 V motor.
Trích dẫn luật: 2023 NEC Table 430.248Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- For a continuous-duty three-phase motor rated more than 1 HP without integral overload protection, how many overload units are generally required?
- A continuous-duty motor has a nameplate FLA of 62 A and a service factor of 1.15. What is the maximum overload device rating at 125% under NEC 430.32(A)(1)?
- If the 125% overload device will not allow a 62 A (SF 1.15) motor to start, NEC 430.32(C) permits increasing the overload trip setting to a maximum of what value?
- Using NEC Table 430.250, what is the full-load current of a 100 HP, 460 V, three-phase motor?
- For a 100 HP, 460 V motor (FLC 124 A), what minimum branch-circuit conductor ampacity does NEC 430.22 require?
- For the 100 HP, 460 V motor (FLC 124 A), what is the maximum dual-element (time-delay) fuse per Table 430.52 (175%)?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra