For a 100 HP, 460 V motor (FLC 124 A), what minimum branch-circuit conductor ampacity does NEC 430.22 require?
a.124 A
b.136.4 A
c.155 A
d.174.6 A
Giải thích
430.22 requires 125% of FLC: 124 x 1.25 = 155 A. 124 A omits the factor, 136.4 A is 110%, and 174.6 A is about 141%.
Trích dẫn luật: 2023 NEC §430.22Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- If the 125% overload device will not allow a 62 A (SF 1.15) motor to start, NEC 430.32(C) permits increasing the overload trip setting to a maximum of what value?
- Per NEC Table 430.248, what is the full-load current of a 2 HP, single-phase, 230 V motor?
- Using NEC Table 430.250, what is the full-load current of a 100 HP, 460 V, three-phase motor?
- For the 100 HP, 460 V motor (FLC 124 A), what is the maximum dual-element (time-delay) fuse per Table 430.52 (175%)?
- In a typical motor branch circuit, which sequence correctly lists the components from the supply toward the motor?
- An HVAC nameplate lists MCA = 27.5 A and MOCP = 45 A. What is the minimum ampacity the branch-circuit conductors must have?