A small single-phase motor has a nameplate FLA of 14 A, service factor 1.0, no marked temperature rise. What is the maximum overload device rating under NEC 430.32(A)(1)?
a.14 A
b.17.5 A
c.15.4 A
d.16.1 A
Giải thích
Without a 1.15+ SF or <=40C rise marking, overload is limited to 115% of nameplate: 14 x 1.15 = 16.1 A. 125% (17.5 A) applies only to qualifying motors, 15.4 A is 110%, and 14 A applies no factor.
Trích dẫn luật: 2023 NEC §430.32Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- For the 7.5 HP, 230 V motor (FLC 22 A), what is the maximum nontime-delay fuse per Table 430.52 (300%)?
- When the Table 430.52 percentage produces a value that does not correspond to a standard fuse or breaker size, NEC 430.52(C)(1) Exception No. 1 permits you to:
- Per NEC Table 430.248, what is the full-load current of a 1 HP, single-phase, 115 V motor?
- NEC 430.75 requires that motor control circuits be arranged so that:
- A 15 kVA, single-phase transformer has a 480 V primary. What is the rated primary current?
- For the 15 kVA, 480 V single-phase transformer (primary current 31.25 A), what is the maximum primary-only overcurrent device using the 125% factor of Table 450.3(B)?