For the 15 kVA, 480 V single-phase transformer (primary current 31.25 A), what is the maximum primary-only overcurrent device using the 125% factor of Table 450.3(B)?
a.31.25 A
b.46.9 A
c.39.1 A
d.62.5 A
Giải thích
Primary current >=9 A limits primary-only protection to 125%: 31.25 x 1.25 = 39.1 A (next standard size up permitted where needed). 31.25 A omits the factor, 46.9 A is 150%, and 62.5 A is 200%.
Trích dẫn luật: 2023 NEC §450.3Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.