Which of the following is NOT required to be marked on a motor nameplate by NEC 430.7?
a.Rated full-load amperes
b.Rated voltage and horsepower (or kW)
c.Rated frequency and number of phases
d.The branch-circuit conductor size to be installed
Giải thích
NEC 430.7 requires the manufacturer, voltage, HP/kW, FLA, frequency, phases, speed, and similar data on the nameplate, but not the field branch-circuit conductor size - that is the installer's design calculation. All other listed items are required nameplate markings.
Trích dẫn luật: 2023 NEC §430.7Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- NEC 430.75 requires that motor control circuits be arranged so that:
- A 15 kVA, single-phase transformer has a 480 V primary. What is the rated primary current?
- For the 15 kVA, 480 V single-phase transformer (primary current 31.25 A), what is the maximum primary-only overcurrent device using the 125% factor of Table 450.3(B)?
- For a permanently installed swimming pool, what conductor is required for the equipotential bonding grid?
- A non-Type IC recessed luminaire must be spaced at least how far from combustible material, except at the points of support?
- Thermal insulation must be kept at least how far from a non-Type IC recessed luminaire enclosure?