A branch circuit carries a continuous load of 80 A. What minimum OCPD rating is required?
a.80 A
b.100 A
c.90 A
d.64 A
Giải thích
Per 210.20(A), the OCPD must be at least 125% of the continuous load: 80 A x 1.25 = 100 A. 80 A ignores the 125% factor, 90 A is insufficient, and 64 A wrongly reduces the load.
Trích dẫn luật: 2023 NEC §210.20(A)Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.