A dwelling has two required small-appliance branch circuits and one laundry circuit. What is the total calculated load for these before demand factors?
a.4,500 VA
b.3,000 VA
c.1,500 VA
d.6,000 VA
Giải thích
Per 220.52, each small-appliance and laundry circuit is figured at 1,500 VA: (2 x 1,500) + 1,500 = 4,500 VA. 3,000 VA omits the laundry circuit and 1,500 VA counts only one.
Trích dẫn luật: 2023 NEC §220.52Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Why is a service disconnect required to be readily accessible and located near the point of entrance of the service conductors?
- A branch circuit carries a continuous load of 80 A. What minimum OCPD rating is required?
- Using the standard 3 VA/sq ft general lighting unit load, what is the general lighting load for a 2,000 sq ft dwelling (before demand factors)?
- A dwelling has one 12 kW electric range. Using Table 220.55 Column C, what is the demand load?
- Two 12 kW electric ranges are in a two-unit dwelling. Using Table 220.55 Column C, what is the total demand?
- A single household electric clothes dryer is rated 4 kW. What value is used for the service/feeder demand calculation?