Before performing a continuity test on a cable with an ohmmeter, what condition must exist?
a.The circuit must be de-energized (no voltage present)
b.The circuit must be energized at full load
c.The conductor must be under 120 V
d.The neutral must be bonded to a driven ground rod
Giải thích
An ohmmeter/continuity function supplies its own small test voltage; applying it to a live circuit gives false readings and can damage the meter or injure you. The conductor must be de-energized and isolated. Energizing (b, c) defeats the test, and grounding a rod (d) is unrelated.
Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A heating element rated at 24 ohms is connected across a 120 V supply. Using Ohm's law, what current flows through it?
- You will take voltage measurements at the line terminals of a 240 V main service panel. What minimum measurement category (CAT) rating should your meter and leads carry for this location?
- A 120 V branch circuit supplies a load drawing 1,500 W. What current does the load draw?
- A plug-in receptacle tester shows its 'hot/neutral reversed' indication at a 120 V outlet. What does this mean and what is the fix?
- On a 120/240 V multiwire branch circuit, the shared neutral becomes open. What symptom is most characteristic?
- You test a 480 V motor with a 500 V megohmmeter and read 0.4 megohms. Using the common one-megohm-per-kilovolt-plus-one-megohm minimum guideline, is the insulation acceptable?