Kiểm tra & Khắc phục sự cốCâu 486 / 521
On a 120/240 V multiwire branch circuit, the shared neutral becomes open. What symptom is most characteristic?
a.Both 120 V loads simply stop working with 0 V at each
b.The two 120 V loads see unequal, shifting voltages, one above 120 V and one below, as their series combination divides the 240 V
c.The breaker trips immediately every time
d.Voltage to ground doubles equally on both lines to 240 V each
Giải thích
With the neutral open, the two line-to-neutral loads are placed in series across 240 V; the voltage divides inversely to their resistances, so the lighter-loaded side rises (often damaging equipment) and the heavier side drops. They do not both read 0 V (a). An open neutral does not by itself trip the breaker (c) or raise each line to 240 V to ground (d).
Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A 120 V branch circuit supplies a load drawing 1,500 W. What current does the load draw?
- Before performing a continuity test on a cable with an ohmmeter, what condition must exist?
- A plug-in receptacle tester shows its 'hot/neutral reversed' indication at a 120 V outlet. What does this mean and what is the fix?
- You test a 480 V motor with a 500 V megohmmeter and read 0.4 megohms. Using the common one-megohm-per-kilovolt-plus-one-megohm minimum guideline, is the insulation acceptable?
- Which instrument lets you measure the current in a single energized conductor without disconnecting or breaking into the circuit?
- A DMM reads 12 V across a resistor and a clamp meter reads 3 A through it. What is the resistor's value?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra