For a 200 A single-phase dwelling service, the minimum aluminum service-entrance conductor permitted by the dwelling service conductor provisions is:
a.1/0 AWG copper
b.3/0 AWG aluminum
c.4/0 AWG aluminum
d.250 kcmil copper
Giải thích
Section 310.12 (dwelling services and feeders) permits 4/0 AWG aluminum for a 200 A single-phase dwelling service. 3/0 aluminum is undersized for 200 A, while the copper options are permitted but are not the minimum aluminum answer asked for.