Ground-fault protection of equipment is generally required for solidly grounded wye services of more than 150 V to ground but not exceeding 1000 V phase-to-phase, where the service disconnect is rated:
a.1000 A or more
b.400 A or more
c.100 A or more
d.2000 A or more
Giải thích
Per 230.95, ground-fault protection of equipment is required on such services where the service disconnecting means is rated 1000 A or more. The other ampere thresholds do not match the code trigger for this GFP requirement.
Trích dẫn luật: 2023 NEC §230.95Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.