Load & DesignCâu 17 / 110
A branch duct must deliver 200 CFM at a velocity of about 600 feet per minute. Approximately what free area is required?
a.0.10 square feet
b.0.20 square feet
c.0.33 square feet
d.0.66 square feet
Giải thích
Area equals CFM divided by velocity: 200 / 600 = 0.33 square feet. This corresponds to roughly a 8-inch round duct. Selecting the right size keeps velocity and noise within acceptable limits.
Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- If a home has a calculated cooling load of 30,000 BTU/hr, what nominal equipment size is the closest match?
- Friction rate in duct design is typically expressed in which units?
- Air velocity in a duct is calculated by dividing airflow (CFM) by what?
- Under California energy standards, duct leakage in many new and altered systems must be verified by which method?
- Which condition would a technician correct by performing an accurate load calculation instead of using a rule of thumb like square footage per ton?
- Latent load in a cooling calculation refers to the energy required to do what?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-20 Warm-Air HVAC Trade Exam · Quy trình kiểm tra