Cấp nước & Phân phốiCâu 19 / 360
A water service run has a developed length of 120 feet with an available pressure of 60 psi and a required residual of 15 psi at the highest fixture, which is 25 feet above the meter. Roughly how much pressure remains for friction loss in the piping (ignoring meter and fitting losses)?
a.60 psi
b.45 psi
c.34.2 psi is close; about 34 psi
d.0 psi
Giải thích
Elevation loss is 25 ft x 0.433 psi/ft = about 10.8 psi. Starting at 60 psi, subtract 15 psi residual and about 10.8 psi elevation, leaving roughly 60 - 15 - 10.8 = 34.2 psi available for friction. The 60 psi and 0 psi answers ignore the required residual and elevation deductions.
Trích dẫn luật: 2022 California Plumbing Code (CPC) §610.0Luyện miễn phí toàn bộ 360 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- What is the fundamental purpose of cross-connection control in a potable water system?
- When sizing water piping using the fixture unit method, why is the total demand in gpm always less than the simple sum of every fixture's peak flow?
- A flushometer (flush valve) water closet is being served. Compared with a flush-tank water closet, what does the flushometer require from the water distribution design?
- A janitor's service sink has a hose thread faucet used with cleaning chemicals. What is the simplest code-recognized protection against back-siphonage at that outlet?
- You are supporting horizontal CPVC hot water pipe, 1 inch and smaller. What is the maximum horizontal support spacing typically required?
- A reduced pressure principle assembly (RP) discharges water from its relief port during a fouling event. Where must the relief port discharge terminate?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-36 Plumbing Trade Examination · Quy trình kiểm tra