A reduced pressure principle assembly (RP) discharges water from its relief port during a fouling event. Where must the relief port discharge terminate?
a.Directly into the sanitary sewer with a solid connection
b.To atmosphere through an air gap so it cannot be submerged
c.Into a sealed pit under the assembly
d.Back into the potable line downstream
Giải thích
The RP relief port must discharge to atmosphere through an air gap so a backflow or fouling event cannot cause submergence and re-contamination. A solid sewer connection, a sealed pit that could flood, or routing back into the potable line would defeat the protection.
Trích dẫn luật: 2022 California Plumbing Code (CPC) §603.0Luyện miễn phí toàn bộ 360 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A water service run has a developed length of 120 feet with an available pressure of 60 psi and a required residual of 15 psi at the highest fixture, which is 25 feet above the meter. Roughly how much pressure remains for friction loss in the piping (ignoring meter and fitting losses)?
- A janitor's service sink has a hose thread faucet used with cleaning chemicals. What is the simplest code-recognized protection against back-siphonage at that outlet?
- You are supporting horizontal CPVC hot water pipe, 1 inch and smaller. What is the maximum horizontal support spacing typically required?
- A hot water recirculation loop is added so users get hot water quickly at a remote fixture. What is the main plumbing purpose of the recirculation return line?
- Which standard applies to cross-linked polyethylene (PEX) tubing used in potable water distribution?
- A residential water heater is 55 feet of developed pipe run from the farthest bathroom. Using standard practice, which change would most directly reduce the long wait for hot water without adding a recirculation pump?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-36 Plumbing Trade Examination · Quy trình kiểm tra