A commercial irrigation system injects fertilizer chemicals into the line and operates under continuous pressure with potential backpressure. Which backflow assembly is required for this high-hazard cross-connection?
a.Atmospheric vacuum breaker (AVB)
b.Pressure vacuum breaker (PVB)
c.Dual check valve
d.Reduced pressure principle backflow assembly (RP)
Giải thích
Chemical injection creates a high (health) hazard, and continuous pressure with possible backpressure rules out siphon-only devices. An RP assembly (or an air gap) is the required protection. An AVB and PVB protect only against back-siphonage, not backpressure, and a simple dual check is not rated for a health hazard.
Trích dẫn luật: 2022 California Plumbing Code (CPC) §603.0Luyện miễn phí toàn bộ 360 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A single-family dwelling has a total demand of 22 water supply fixture units (WSFU). Using the code sizing tables, which is the smallest nominal water service pipe size that is generally acceptable for a building water service?
- You measure a static street pressure of 95 psi at a new residence. According to the code, what is required on the water supply?
- An air gap is used to protect a potable water outlet discharging into a fixture. What is the minimum required vertical air gap relative to the effective opening of the supply?
- An atmospheric vacuum breaker (AVB) is installed to protect a hose connection. What installation condition must be satisfied for an AVB to be used correctly?
- A plumber connects PEX tubing to a residential water heater. What does the code require at the hot-water outlet connection?
- You are supporting horizontal 1-inch copper water tube. Per the code hanger and support spacing table, what is the maximum horizontal spacing between supports for copper tube 1-1/2 inch and smaller?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-36 Plumbing Trade Examination · Quy trình kiểm tra