Cấp nước & Phân phốiCâu 56 / 360
A dental office has vacuum and treatment equipment connected to the potable supply, presenting a health hazard with possible backpressure. Which premise-isolation assembly is appropriate?
a.Atmospheric vacuum breaker
b.Hose bibb vacuum breaker
c.Double check valve
d.Reduced pressure principle assembly (RP)
Giải thích
A health hazard with possible backpressure requires a reduced pressure principle assembly (RP) for premise isolation. An AVB and hose bibb vacuum breaker protect only against back-siphonage, and a double check is limited to low hazards, so none of those suffice for a health hazard with backpressure.
Trích dẫn luật: 2022 California Plumbing Code (CPC) §603.0Luyện miễn phí toàn bộ 360 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Where must a readily accessible full-open shutoff valve be provided on the building water supply?
- To allow individual maintenance, where does good practice and code generally require shutoff (angle stop) valves in a dwelling?
- A two-story home has the main run in the crawlspace and risers to the second floor. To minimize pressure loss to upstairs fixtures during simultaneous use, which strategy is best?
- After installing a new RP assembly on a high-hazard connection, what ongoing requirement typically applies?
- Threaded steel (galvanized) water pipe is run horizontally. What is the typical maximum horizontal support spacing?
- A single check valve is proposed as backflow protection for a high-hazard chemical connection. Why is this not acceptable?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-36 Plumbing Trade Examination · Quy trình kiểm tra