Duyệt tất cả câu hỏi

Mọi câu hỏi kèm đáp án và giải thích — học theo chủ đề hoặc tất cả cùng lúc.

Core (Universal)

40 câu hỏi
1. Why is the stratospheric ozone layer important to life on Earth?
a.It traps heat and keeps the planet warm
b.It absorbs harmful ultraviolet (UV) radiation from the sun
c.It produces the oxygen that people breathe
d.It reflects radio signals back to the surface

The ozone layer in the stratosphere absorbs most of the sun's harmful ultraviolet (UV) radiation, which protects humans, animals, and plants. It does not warm the planet like greenhouse gases do, produce breathable oxygen, or reflect radio signals. Protecting this layer is the main reason Section 608 limits the release of ozone-depleting refrigerants.

2. Which element released from CFC and HCFC refrigerants is chiefly responsible for destroying stratospheric ozone?
a.Nitrogen
b.Carbon
c.Chlorine
d.Hydrogen

Chlorine atoms released from CFCs and HCFCs act as a catalyst, and a single chlorine atom can destroy thousands of ozone molecules before it is removed from the stratosphere. Carbon and hydrogen are part of the molecule but are not the ozone-destroying agent, and nitrogen is not the driver of this reaction. This is why chlorine-containing refrigerants have been phased out.

3. What is the Montreal Protocol?
a.An international treaty to phase out the production of ozone-depleting substances
b.A U.S. law that sets minimum wages for HVAC technicians
c.A manufacturer standard for compressor efficiency
d.A voluntary industry pledge to recycle scrap metal

The Montreal Protocol, adopted in 1987, is the international treaty under which nations agreed to phase out the production and consumption of ozone-depleting substances such as CFCs and HCFCs. It is not a wage law, a compressor efficiency standard, or a metal recycling pledge. U.S. obligations under this treaty are carried out through the Clean Air Act.

4. Section 608 of the Clean Air Act primarily regulates which activity?
a.The design of home thermostats
b.The price technicians may charge customers
c.The electrical wiring of condensing units
d.The handling of refrigerants during service, maintenance, and disposal of appliances

Section 608 of the Clean Air Act establishes the national program for managing ozone-depleting and substitute refrigerants during the service, maintenance, repair, and disposal of appliances. It does not set thermostat designs, service prices, or wiring rules. The regulations that carry out Section 608 are found in 40 CFR Part 82, Subpart F.

Clean Air Act §608
5. What does ODP stand for when comparing refrigerants?
a.Operating Discharge Pressure
b.Ozone Depletion Potential
c.Overall Design Performance
d.Oil Displacement Percentage

ODP means Ozone Depletion Potential, a value that compares a substance's ability to destroy stratospheric ozone relative to CFC-11, which is assigned an ODP of 1.0. It has nothing to do with discharge pressure, design performance, or oil displacement. HFCs have an ODP of zero because they contain no chlorine.

6. A supplier tells a technician that R-410A has an ODP of zero but a high GWP. What does GWP measure?
a.How much a gas contributes to global warming compared to carbon dioxide
b.How much the gas depletes stratospheric ozone
c.The working pressure of the refrigerant in a condenser
d.The percentage of water vapor in the refrigerant

GWP means Global Warming Potential, which compares how much heat a gas traps in the atmosphere relative to carbon dioxide (CO2 = 1). R-410A has zero ODP because it contains no chlorine, but its high GWP is why HFCs are now being phased down under the AIM Act. GWP is not a measure of ozone depletion, working pressure, or water content.

7. Which of the following refrigerants is a CFC that has already been phased out of production?
a.R-410A
b.R-134a
c.R-12
d.R-1234yf

R-12 is a chlorofluorocarbon (CFC) with a high ozone depletion potential and its production was banned in the United States. R-134a and R-410A are HFCs with zero ODP, and R-1234yf is a low-GWP HFO. CFCs were the first class of refrigerants eliminated under the Montreal Protocol.

8. R-22 is best classified as which type of refrigerant?
a.A hydrofluorocarbon (HFC) with zero ozone depletion
b.A hydrofluoroolefin (HFO) with very low GWP
c.A natural refrigerant
d.A hydrochlorofluorocarbon (HCFC) with some ozone-depleting potential

R-22 is a hydrochlorofluorocarbon (HCFC), which still contains chlorine and therefore has some ozone depletion potential, though less than a CFC. It is not an HFC, an HFO, or a natural refrigerant. Because HCFCs deplete ozone, R-22 was placed on a production and import phaseout schedule.

9. As of January 1, 2020, what happened to R-22 (HCFC-22) in the United States?
a.Its production and import were banned, so only recovered, recycled, or reclaimed supplies remain
b.It became legal to vent it freely to the atmosphere
c.It was reclassified as a natural refrigerant
d.It was required in all new residential air conditioners

Beginning January 1, 2020, it became illegal to produce or import R-22 in the United States, so servicing older R-22 equipment now depends on recovered, recycled, or reclaimed supplies. Venting R-22 remains illegal, it was never a natural refrigerant, and new systems use non-ozone-depleting refrigerants. The phaseout follows the Montreal Protocol schedule for HCFCs.

10. The AIM Act of 2020 directs EPA to phase down the production and consumption of which class of refrigerants?
a.CFCs
b.HFCs
c.Natural refrigerants such as CO2
d.Nitrogen used for pressure testing

The American Innovation and Manufacturing (AIM) Act directs EPA to phase down the production and consumption of hydrofluorocarbons (HFCs) by 85 percent over roughly 15 years because of their high global warming potential. CFCs were already addressed by the Montreal Protocol, and natural refrigerants and nitrogen are not targeted by the phasedown. This is a phasedown of quantity, not an immediate ban.

11. The 'three R's' of responsible refrigerant management are:
a.Refill, Resell, Reuse
b.Repair, Replace, Remove
c.Recover, Recycle, Reclaim
d.Reduce, Recharge, Report

The three R's are Recover, Recycle, and Reclaim, describing how refrigerant is removed, cleaned for on-site reuse, or reprocessed to a purity standard for resale. Repair, replace, refill, and report are legitimate service tasks but are not the recognized three R's. Understanding these three terms is central to Section 608 recovery requirements.

12. What is the difference between recycling and reclaiming refrigerant?
a.Recycling requires shipping to a refinery; reclaiming is done on the truck
b.There is no difference; the terms mean the same thing
c.Recycling reprocesses to new-product purity; reclaiming only removes oil
d.Recycling cleans refrigerant for on-site reuse; reclaiming reprocesses it to a purity standard so it can be resold

Recycling cleans refrigerant on-site with oil separation and filter-driers so it can be reused in the same or a related system, while reclaiming reprocesses the refrigerant to meet the AHRI 700 purity standard, allowing it to be resold. The two terms are not interchangeable, and the descriptions in the other options are reversed or inaccurate. Only reclaimed refrigerant may be sold to a new owner.

13. A technician is about to replace a compressor on a residential R-410A split system. Before opening the sealed system, the technician must:
a.Recover the refrigerant into an approved recovery cylinder using recovery equipment
b.Vent the refrigerant slowly so it disperses safely
c.Let the refrigerant leak out while purging with nitrogen
d.Discharge the refrigerant into a bucket of water

Section 608 requires that refrigerant be recovered into an approved recovery cylinder using recovery equipment before a sealed system is opened for service or disposal. Venting, purging to atmosphere, or discharging into water are all illegal releases. Knowingly venting refrigerant is prohibited and can lead to significant penalties.

40 CFR §82.156
14. Since November 15, 1995, it has been illegal to knowingly vent which refrigerants during service, maintenance, or disposal?
a.Only CFC refrigerants such as R-12
b.CFC and HCFC refrigerants and their non-exempt substitutes, including most HFCs
c.Only refrigerants used in automobiles
d.Only refrigerants in systems over 50 pounds

The venting prohibition originally covered CFCs and HCFCs, and effective November 15, 1995 it was extended to their non-exempt substitutes, which includes most HFCs such as R-410A and R-134a. It is not limited to CFCs, automotive systems, or large systems. Only a small number of substitutes that EPA has specifically exempted may be released, and even then good practice is to avoid venting.

40 CFR §82.154
15. A small household refrigerator contains less than 5 pounds of refrigerant. Which certification type covers recovering refrigerant from this small appliance?
a.Type II
b.Type III
c.Type I
d.No certification is required

Type I certification covers servicing and disposing of small appliances, defined as products manufactured, charged, and hermetically sealed in a factory with 5 pounds or less of refrigerant. Type II covers high-pressure systems and Type III covers low-pressure systems, and certification is always required to recover refrigerant. A Universal certification would also qualify because it includes Type I.

40 CFR §82.156
16. A technician who services rooftop package units charged with R-410A (a high-pressure refrigerant) needs which certification type at minimum?
a.Type I
b.Type III
c.No certification, because HFCs have zero ODP
d.Type II

Type II certification is required to service or dispose of high-pressure and very high-pressure appliances, which includes R-410A rooftop units. Type I covers only small appliances, Type III covers low-pressure systems, and certification is required for HFCs even though they have zero ODP. A Universal certification would also qualify because it includes Type II.

40 CFR §82.161
17. A technician services a large centrifugal chiller that uses R-123, a low-pressure refrigerant. Which certification type is required?
a.Type II
b.Type III
c.Type I
d.Any certification, because low-pressure systems are exempt

Type III certification is required to service or dispose of low-pressure appliances such as R-123 and R-11 centrifugal chillers, which operate below atmospheric pressure. Type I covers small appliances and Type II covers high-pressure systems, and low-pressure systems are not exempt. A Universal certification would also qualify because it includes Type III.

40 CFR §82.161
18. A technician wants a single certification that allows work on small appliances, high-pressure systems, and low-pressure systems. Which does the technician need?
a.Universal certification
b.Type I only
c.Type II only
d.A separate business license instead of a certification

Universal certification is earned by passing the Core section plus all three type-specific sections (Type I, II, and III), and it authorizes work on every category of stationary equipment. Holding only Type I or Type II limits the technician to that category. A business license is a different matter and does not replace technician certification.

40 CFR §82.161
19. How long does an EPA Section 608 technician certification remain valid?
a.One year, then it must be renewed
b.Five years, matching the cylinder test cycle
c.Ten years
d.It never expires once earned

A Section 608 technician certification does not expire; once earned it is valid for the life of the technician. There is no annual, five-year, or ten-year renewal requirement. The five-year figure in one option refers to cylinder hydrostatic testing, which is a separate rule.

40 CFR §82.161
20. A parts counter clerk is asked to sell a 25-pound cylinder of R-410A to a walk-in customer. Under Section 608 sales restrictions, the clerk may sell it only to someone who:
a.Pays in cash and shows a driver's license
b.Promises not to vent the refrigerant
c.Is an EPA Section 608 (or 609) certified technician, or a certified technician's employer
d.Owns the home where the system is installed

Since January 1, 2018, sales of HFC and other substitute refrigerants are restricted to EPA-certified technicians (or their employers or wholesalers), the same rule that already applied to ozone-depleting refrigerants. Paying cash, promising not to vent, or owning the home does not qualify a buyer. The clerk must verify the buyer's certification before completing the sale.

40 CFR §82.154
21. A technician is recovering R-134a from a high-pressure appliance manufactured after November 15, 1993, that normally holds less than 200 pounds. To what level must the system be evacuated using recovery equipment?
a.0 inches of mercury (Hg) vacuum
b.25 inches Hg vacuum
c.29.9 inches Hg vacuum
d.15 psig positive pressure

For a high-pressure appliance normally containing less than 200 pounds and manufactured on or after November 15, 1993, the required recovery level is 0 inches of mercury (Hg) vacuum, meaning down to atmospheric pressure. The deeper 25 inch Hg level applies to low-pressure appliances, and leaving positive pressure would leave refrigerant behind. Recovery levels depend on the appliance type, size, and manufacture date.

40 CFR §82.156
22. A technician is disposing of a low-pressure chiller manufactured after November 15, 1993. Which evacuation level generally applies to low-pressure appliances during recovery?
a.0 inches Hg vacuum
b.25 mm Hg absolute (approximately 29 inches Hg vacuum)
c.10 inches Hg vacuum
d.4 inches Hg vacuum

Low-pressure appliances must be evacuated to a deep vacuum, expressed as 25 mm Hg absolute, which is roughly 29 inches of mercury vacuum, because these refrigerants boil off only at very low pressures. The 0, 4, and 10 inch Hg figures apply to various high-pressure appliances, not low-pressure chillers. Deep evacuation is required to remove as much low-pressure refrigerant as practical.

40 CFR §82.156
23. A technician recovers refrigerant from a household window air conditioner (a small appliance) whose compressor still runs. Recovery equipment made after November 15, 1993 must remove at least what percentage of the charge?
a.70 percent
b.80 percent
c.90 percent
d.100 percent

For small appliances, recovery equipment manufactured on or after November 15, 1993 must recover 90 percent of the refrigerant when the appliance's compressor is operating, or the system must reach 4 inches Hg vacuum. If the compressor is not operating, the requirement is 80 percent. Reaching 100 percent is not physically required by the rule.

40 CFR §82.156
24. What is 'system-dependent' (passive) recovery?
a.Recovery that uses a large self-contained machine with its own compressor
b.Recovery performed only by the manufacturer
c.Recovery that vents part of the charge to speed up the process
d.Recovery that relies on the appliance's own compressor or internal pressure to move refrigerant into a recovery container

System-dependent or passive recovery uses the appliance's own compressor or its internal pressure to push refrigerant into a recovery container, and it is generally limited to small appliances. Self-contained (active) recovery uses a separate machine with its own compressor. Passive recovery must never involve venting any part of the charge.

25. The EPA program that reviews and lists acceptable substitute refrigerants for specific end uses is called:
a.The DOT Hazmat program
b.The SNAP (Significant New Alternatives Policy) program
c.The OSHA Refrigerant Registry
d.The ARI Reclamation program

The Significant New Alternatives Policy (SNAP) program reviews substitute refrigerants and lists them as acceptable or unacceptable for specific end uses based on overall risk to health and the environment. DOT regulates transport, OSHA regulates workplace safety, and AHRI (formerly ARI) sets the reclamation purity standard. A refrigerant may be listed as acceptable only for certain applications.

26. A wholesaler offers a technician a low-GWP refrigerant such as R-1234yf. This refrigerant is an example of:
a.A hydrofluoroolefin (HFO) with very low global warming potential
b.A chlorofluorocarbon (CFC)
c.A hydrochlorofluorocarbon (HCFC)
d.A refrigerant with high ozone depletion potential

R-1234yf is a hydrofluoroolefin (HFO), a newer class of refrigerant with zero ozone depletion potential and a very low global warming potential, which is why it is replacing higher-GWP HFCs. It is not a CFC or HCFC and does not deplete ozone. HFOs are mildly flammable (A2L), so technicians must follow the manufacturer's safety guidance.

27. A recovery cylinder is being filled with recovered R-404A. To leave room for liquid expansion, the cylinder must never be filled beyond what percent of its capacity?
a.50 percent
b.60 percent
c.95 percent
d.80 percent

Refrigerant recovery cylinders must never be filled beyond 80 percent of capacity by weight, leaving vapor space so the liquid can expand safely as temperature rises. Overfilling can cause the cylinder to become hydrostatically full and rupture. Filling to 95 percent is dangerous, while 50 or 60 percent is unnecessarily conservative and not the rule.

28. Cylinders used to store recovered refrigerant must be approved by which agency for transportation?
a.OSHA
b.EPA
c.DOT (Department of Transportation)
d.AHRI

Recovery cylinders must be Department of Transportation (DOT) approved for the transport of refrigerant under pressure, and they must be within their required inspection and test intervals. OSHA handles workplace safety, EPA handles refrigerant management rules, and AHRI publishes purity standards, but the cylinder approval itself is a DOT function. Using unapproved or expired cylinders is unsafe and illegal for transport.

29. A technician needs to identify a cylinder by its color. Which color has EPA and industry designated for refrigerant recovery cylinders?
a.Gray body with a yellow top (shoulder)
b.Solid green
c.Solid orange
d.Solid light blue

Refrigerant recovery cylinders are color-coded with a gray body and a yellow top or shoulder so they are easy to distinguish from virgin refrigerant cylinders. Solid colors such as green (older R-22), orange (R-404A), and light blue (R-134a) identify specific virgin refrigerants, not recovered mixtures. The gray and yellow scheme signals that the contents may be a mix that must be reclaimed or reused properly.

30. A technician pulls a light-green cylinder from the truck. Under the traditional color code, which refrigerant does light green identify?
a.R-410A
b.R-22
c.R-134a
d.R-404A

Under the traditional refrigerant color code, light green identifies R-22, while R-410A is rose (pink), R-134a is light blue, and R-404A is orange. Color codes help technicians grab the right cylinder, but the printed label must always be verified because colors can fade or be reused. Never rely on color alone to identify a refrigerant.

31. Under the traditional color code, which refrigerant cylinder is rose (pink)?
a.R-22
b.R-134a
c.R-410A
d.R-12

R-410A cylinders are traditionally colored rose (pink), which distinguishes them from light-green R-22, light-blue R-134a, and white R-12. Because R-410A operates at much higher pressures than R-22, using the correct refrigerant and gauges matters for safety. As always, the printed label is the authoritative identification, not the color.

32. A commercial supermarket rack system contains more than 50 pounds of refrigerant and develops a leak. Once the owner exceeds the applicable annual leak rate, the leak generally must be repaired within:
a.24 hours
b.7 days
c.90 days
d.30 days

For appliances containing 50 or more pounds of refrigerant, leaks that exceed the applicable annual leak rate threshold must generally be repaired within 30 days of discovery. A 24-hour or 7-day deadline is stricter than the rule requires, and 90 days is too long. If repairs cannot be completed in time, the owner may need a retrofit or retirement plan.

40 CFR §82.157
33. Under the leak repair rules, the leak rate thresholds apply to appliances that normally contain how much refrigerant?
a.5 pounds or more
b.50 pounds or more
c.200 pounds or more
d.Any amount, regardless of charge

The leak repair provisions apply to appliances that normally contain 50 or more pounds of refrigerant, such as commercial and industrial systems. Small appliances with 5 pounds or less are not subject to the leak rate thresholds, and 200 pounds is not the trigger. This is why leak inspections and repair recordkeeping focus on larger commercial equipment.

40 CFR §82.157
34. A service company disposes of a chiller that held 200 pounds of R-123. Records showing the refrigerant was recovered and the quantities involved generally must be kept for at least:
a.3 years
b.6 months
c.1 month
d.No records are required

Recordkeeping requirements under Section 608 generally call for records related to refrigerant recovery, service, and disposal to be retained for at least three years. Keeping records for only one month or six months would not satisfy the rule, and records are definitely required. Good records protect the technician and company if EPA requests documentation.

40 CFR §82.166
35. Before refrigerant that has been recovered from one owner's system can be sold to a different owner, it must be:
a.Simply filtered on the truck and relabeled
b.Recycled through a single-pass filter-drier
c.Reclaimed to the AHRI 700 purity standard by a certified reclaimer
d.Mixed with virgin refrigerant to dilute impurities

Used refrigerant can only be sold to a new owner after it has been reclaimed to the AHRI 700 purity standard, typically by an EPA-certified reclaimer. On-site recycling or simple filtering does not meet the standard for resale, and mixing with virgin refrigerant is not an acceptable substitute for reclamation. Reclaimed refrigerant must meet the same purity as new product.

36. A technician is scrapping an old refrigerator at a recycling yard. Who is responsible for ensuring the refrigerant is recovered before the appliance is shredded or disposed of?
a.Only the original manufacturer
b.No one, because scrap appliances are exempt
c.Only the homeowner who discarded it
d.The final person in the disposal chain must verify recovery, and technicians recovering it must be certified

Section 608 places responsibility on the disposal chain to ensure refrigerant is recovered before an appliance is shredded or scrapped, and the person who accepts the appliance for final disposal must verify that recovery occurred. Scrap appliances are not exempt, and responsibility is not limited to the manufacturer or homeowner alone. Anyone actually recovering the refrigerant must be certified and use proper equipment.

40 CFR §82.156
37. A technician finishes recovering R-410A but the recovery machine's low-loss fittings still hold a small amount of refrigerant. What is the correct practice?
a.Use self-sealing (low-loss) hoses and fittings to minimize refrigerant release when disconnecting
b.Crack the fittings open to atmosphere to relieve the pressure
c.Blow the hoses clear with compressed air
d.Let the trapped refrigerant leak out overnight

Low-loss fittings and self-sealing hoses are designed to trap the small amount of refrigerant left in hoses so it is not released to the atmosphere when connections are broken. Venting the fittings, blowing lines with air, or letting refrigerant leak out are all prohibited releases. Minimizing these small emissions is part of good recovery practice under Section 608.

40 CFR §82.156
38. Which of the following releases of refrigerant is NOT considered illegal venting under Section 608?
a.Opening a system to atmosphere before recovering the charge
b.A small release of nitrogen or CO2 used as a holding charge or for leak detection
c.Blowing R-22 out of a line set to clean it
d.Discharging R-134a to test a gauge manifold

Releasing a holding or trace gas such as nitrogen or CO2 that is not a regulated refrigerant is not considered illegal venting, which is why these gases are used for pressure testing and leak detection. Opening a system before recovery, blowing out refrigerant, or discharging R-134a are all prohibited releases of regulated refrigerant. The rule targets ozone-depleting and substitute refrigerants, not inert test gases.

40 CFR §82.154
39. A technician suspects a disposable (single-use) refrigerant cylinder is nearly empty. What is the correct handling under Section 608 practice?
a.Refill it with recovered refrigerant to reuse it
b.Vent the remaining vapor and toss it in the trash
c.Recover the remaining refrigerant (the 'heel') before the cylinder is discarded
d.Puncture it to make sure it is empty before recycling

The small amount of refrigerant left in a 'empty' disposable cylinder, called the heel, must be recovered before the cylinder is discarded, because venting it is illegal. Disposable DOT-39 cylinders must never be refilled, and puncturing a cylinder that still holds refrigerant would vent it. Only after the heel is recovered can the cylinder be safely rendered empty and recycled per local rules.

40. A homeowner asks a technician to just 'top off' a leaking R-22 system every summer instead of fixing the leak. Why is intentionally not repairing a significant leak a problem?
a.It voids the thermostat warranty
b.It has no downside as long as the system cools
c.It is only a concern for commercial systems
d.It wastes phased-out refrigerant and repeatedly emits ozone-depleting gas, which the regulations aim to prevent

Repeatedly recharging a leaking system wastes scarce, phased-out R-22 and allows an ozone-depleting refrigerant to escape into the atmosphere, exactly the outcome Section 608 is designed to reduce. It is not merely a warranty or commercial-only issue, and there is a real environmental and cost downside. Good practice is to find and repair leaks rather than continually add refrigerant.

Cập nhật gần nhất: · quy trình kiểm tra

Đội Ngũ Biên Tập PrepPass · Đối chiếu với Clean Air Act §608 / 40 CFR Part 82 · Quy trình kiểm tra

EPA Section 608 Technician Certification Exam (Core, Type I, Type II, Type III / Universal) thi những gì?

EPA Section 608 Technician Certification Exam (Core, Type I, Type II, Type III / Universal) do Administered by EPA-approved certifying organizations (e.g., ESCO Institute, Mainstream Engineering, HVAC Excellence) under U.S. EPA oversight tổ chức. Trọng số chủ đề dưới đây lấy từ đề cương thi chính thức — hãy ưu tiên học các chủ đề có trọng số cao nhất.

Số câu hỏi
Core plus each Type has 25 multiple-choice questions; Universal requires all four sections (100 questions total)
Điểm đậu
70%

Phân bố chủ đề

  • 25%
    Core (Universal)
  • 15%
    Regulations & Safety
  • 15%
    Type I — Small Appliances
  • 15%
    Type II — High-Pressure
  • 15%
    Type III — Low-Pressure
  • 15%
    Recovery & Recycling

Kỳ thi này khó cỡ nào?

Độ khó trung bình. EPA 608 thi theo từng phần — Core cộng Type I/II/III — mỗi phần 25 câu, đóng sách có giám sát, 70% (18/25) để đậu mỗi phần. Core thiên về lý thuyết; các phần Type là xử lý chất làm lạnh thực hành.

Số giờ học khuyến nghị
10-25 giờ; Universal (cả bốn phần) cần ôn nhiều nhất.
Tỷ lệ đậu lần đầu (ước tính)
Core và Type I đậu dễ; Type II bị trượt nhiều nhất. Dự kiến 1-2 lần cho phần khó.
Nên ưu tiên học đâu trước
Quy định Core (ozone, Clean Air Act, thu hồi) và thu hồi/hút chân không áp suất cao Type II.

Câu hỏi thường gặp

How many EPA 608 practice questions are here?+

240 original practice questions across all four sections — Core, Type I (small appliances), Type II (high-pressure), and Type III (low-pressure) — plus recovery/recycling, in English and Español, with a 40 CFR Part 82 or Clean Air Act §608 citation on most answers.

Is this EPA 608 practice test free?+

Yes — completely free, no signup. Unlimited rounds, a full timed mock exam, and explanations included. The official EPA 608 certification exam (about $20-$100) is taken separately through an EPA-approved organization.

Are these real EPA 608 exam questions?+

No. All 240 questions are original prose written from the public-domain Clean Air Act Section 608 and 40 CFR Part 82. We never copy from any prep provider or the real exam.

How is the EPA 608 exam structured and what's the passing score?+

It has four sections — Core plus Type I, II, and III — 25 questions each, and you need 70% (about 18 of 25) to pass each. Passing Core plus all three types earns Universal certification. Core and the Type sections are proctored.

Does the EPA 608 certification expire?+

No — EPA Section 608 technician certification is valid for life and never expires.

What languages is the EPA 608 exam available in?+

Many EPA-approved organizations offer it in English and Spanish. PrepPass practice is available in English and Español.

Báo lỗi