What is the maximum non-time-delay fuse permitted for branch-circuit short-circuit and ground-fault protection of a 34-ampere three-phase squirrel-cage motor, using the next standard size allowance?
a.110 amperes
b.100 amperes
c.90 amperes
d.125 amperes
Giải thích
Non-time-delay fuses are permitted at 300 percent of full-load current: 34 x 3.00 = 102 A, which is not a standard rating, so the next standard size of 110 amperes may be used. The 90-ampere answer belongs to the inverse-time breaker at 250 percent, and 125 amperes skips a standard size.
Trích dẫn luật: 2023 NEC Table 430.52(C)(1)Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A surface-mounted luminaire with a completely enclosed light source is installed in a clothes closet. What is the minimum clearance to the nearest point of the defined storage space?
- A recessed luminaire that is NOT identified for insulation contact must maintain what minimum clearance from thermal insulation?
- A generator nameplate current rating is 200 amperes. What minimum conductor ampacity is required from the generator terminals to the first overcurrent device?
- A photovoltaic source circuit uses modules with a rated short-circuit current of 10 amperes. What minimum conductor ampacity is required before any temperature or conduit-fill adjustments?
- A motor with a service factor of 1.16 will not start because the overload device trips, even though it is sized at 125 percent of nameplate current. To what maximum percentage may the overload device be increased?
- A 20-horsepower, 208-volt three-phase motor has a table full-load current of 59.4 amperes. What is the minimum copper branch-circuit conductor at 75 degrees C terminations?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Electrician Licensing Exam (NEC-based) · Quy trình kiểm tra