Motors & EquipmentCâu 105 / 120
A 20-horsepower, 208-volt three-phase motor has a table full-load current of 59.4 amperes. What is the minimum copper branch-circuit conductor at 75 degrees C terminations?
a.6 AWG
b.4 AWG
c.3 AWG
d.8 AWG
Giải thích
The conductor must carry 59.4 x 1.25 = 74.25 A. In the 75 degrees C column, 6 AWG copper is 65 A and falls short, while 4 AWG copper at 85 A is adequate. Choosing 3 AWG is oversized for the minimum, and 8 AWG at 50 A is well below the requirement.
Trích dẫn luật: 2023 NEC §430.22Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A surface-mounted luminaire with a completely enclosed light source is installed in a clothes closet. What is the minimum clearance to the nearest point of the defined storage space?
- A recessed luminaire that is NOT identified for insulation contact must maintain what minimum clearance from thermal insulation?
- A generator nameplate current rating is 200 amperes. What minimum conductor ampacity is required from the generator terminals to the first overcurrent device?
- A photovoltaic source circuit uses modules with a rated short-circuit current of 10 amperes. What minimum conductor ampacity is required before any temperature or conduit-fill adjustments?
- A motor with a service factor of 1.16 will not start because the overload device trips, even though it is sized at 125 percent of nameplate current. To what maximum percentage may the overload device be increased?
- What is the maximum non-time-delay fuse permitted for branch-circuit short-circuit and ground-fault protection of a 34-ampere three-phase squirrel-cage motor, using the next standard size allowance?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Electrician Licensing Exam (NEC-based) · Quy trình kiểm tra