Branch Circuits & FeedersCâu 29 / 120
What is the line current of a balanced 45 kVA, three-phase, 208-volt load?
a.216 amperes
b.125 amperes
c.72 amperes
d.144 amperes
Giải thích
For a three-phase load, I = VA / (1.732 x E) = 45,000 / (1.732 x 208) = 45,000 / 360.3, or about 125 A. The 216-ampere answer divides by the voltage alone as if the load were single-phase, 72 amperes divides by three times the voltage, and 144 amperes does not follow from the formula.
Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A 200-ampere feeder uses THHN copper conductors, but the equipment terminations are rated 75 degrees C. What is the minimum conductor size?
- Using the dwelling service and feeder conductor table, what is the minimum copper conductor size for a 200-ampere single-phase dwelling service?
- What is the allowable ampacity of 4/0 AWG copper THWN in the 75 degrees C column?
- Twelve current-carrying 12 AWG THHN copper conductors run in one raceway through a 38 degrees C ambient. What is the adjusted ampacity of each conductor?
- A 5,000-watt, 240-volt single-phase electric heater operates continuously. What is the minimum standard branch-circuit overcurrent device rating?
- On a 20-ampere branch circuit that supplies both lighting outlets and cord-and-plug-connected equipment not fastened in place, what is the maximum load the cord-and-plug equipment may impose?