Chương 2 / 523% của kỳ thi

Water Service, Distribution, and Backflow Protection

The water side of the exam tests whether you can deliver enough water at enough pressure to the highest and farthest fixture, while making sure nothing from the building can ever flow backward into the potable supply. That means sizing by water supply fixture units, doing pressure budget arithmetic in psi and feet of head, choosing the correct backflow device for the hazard, and knowing your approved materials and support spacing. The numbers in this chapter, especially 0.433 psi per foot and the 80 psi pressure-reducing valve threshold, appear on nearly every version of the test.

Sizing by Water Supply Fixture Units

A water supply fixture unit, or WSFU, is a demand value that accounts for both how much water a fixture uses and how often it is used. A private lavatory is about 1 WSFU, a bathtub about 4, a residential water closet with a flush tank about 2.2 to 3, a flushometer closet as much as 6 to 10, and a hose bibb about 2.5. Cold and hot demand for a fixture are each less than its total demand, which is why the tables list separate cold, hot, and total columns. Once you have the total WSFU on a section, you convert it to a probable demand in gallons per minute using the Hunter curve chart, then choose a pipe size that will carry that flow without exceeding the velocity limit or the pressure you have available. The relationship is not linear: fifty fixture units do not demand five times what ten fixture units demand, because the more fixtures on a system the less likely they are to run at once. Sizing is done section by section from the meter outward, and every section carries only the fixture units downstream of it. Water service, meaning the pipe from the main to the building, is sized on the same total but includes the meter loss, and no water service in most codes may be smaller than 3/4 in.

Total the WSFU downstream of each section, then convert to gpm
Fixture units are converted to probable demand with the Hunter curve. The conversion flattens out as the count grows, which is why large buildings do not need proportionally huge mains.
IPC Appendix E
Flush tanks and flushometers are not the same load
A flushometer water closet draws a large instantaneous flow and carries a much higher WSFU value than a tank-type closet, and it also needs about 20 psi residual instead of 8.
Water service is a minimum 3/4 in
Even a single small dwelling gets at least a 3/4 in service, and the building supply must be sized for the meter loss in addition to the piping loss.
IPC §603.1
Keep velocity within limits
Design for roughly 8 ft per second maximum in cold water copper and about 5 ft per second in hot water copper. Higher velocity causes erosion of the tube wall and noise.

The Pressure Budget

Every sizing problem is really a subtraction problem. Start with the static pressure available at the main, subtract the pressure lost to elevation, subtract the loss through the meter and through any backflow assembly, softener, or filter, subtract the friction loss in the pipe and fittings, and whatever is left must still meet the minimum residual pressure at the highest and farthest fixture. Elevation costs 0.433 psi for every foot of rise, or stated the other way, 1 psi lifts water 2.31 ft. A fixture 40 ft above the meter has already lost about 17.3 psi before any pipe friction is counted. Most fixtures need at least 8 psi residual, showers and some valves need 15 to 20, and flushometer valves need about 20 to 25. Friction loss is computed over the developed length, which is the measured pipe length plus an allowance for fittings, commonly taken as 50 percent of the measured length as a rule of thumb. On the high side, static pressure over 80 psi requires an approved pressure-reducing valve, because high pressure wastes water, stresses fixture connections, and causes leaks. When a pressure-reducing valve or a check valve or a backflow assembly closes the system, thermal expansion has nowhere to go and an expansion tank becomes necessary.

Elevation loss is 0.433 psi per foot of rise
Multiply the height from the source to the highest fixture by 0.433. A 25 ft rise costs about 10.8 psi. The inverse is 2.31 ft of head per psi.
Static pressure over 80 psi requires a pressure-reducing valve
Where the incoming pressure exceeds 80 psi, an approved pressure-reducing valve must be installed on the water service to protect fixtures and connections.
IPC §604.8
Leave the required residual pressure at the fixture
Plan for about 8 psi at most fixtures, 15 to 20 psi at showers and temperature-actuated valves, and about 20 to 25 psi at flushometer valves. If the budget does not leave that, the pipe is too small.
IPC §604.3
Size on developed length, not straight-line distance
Add an equivalent length for every elbow, tee, and valve. A common field allowance is to add 50 percent to the measured run when a detailed fitting count is not available.
A closed system needs thermal expansion control
Once a pressure-reducing valve, check valve, or backflow preventer is installed, install an expansion tank so heated water has somewhere to expand instead of lifting the relief valve.
IPC §607.3

Cross-Connection Control and Backflow Prevention

A cross-connection is any point where potable water can meet a non-potable substance. Backflow happens two ways: back-siphonage, caused by negative pressure in the supply such as a main break or heavy fire flow, and back-pressure, caused by a downstream system pushed above supply pressure by a pump, elevated tank, or boiler. The device you choose depends on the hazard level and on whether the connection is under continuous pressure. An air gap is the only absolute protection and must be at least twice the effective opening diameter and never less than 1 in. A reduced pressure principle assembly, or RP, is the highest-rated mechanical device and protects against both back-siphonage and back-pressure at a high hazard connection under continuous pressure. A double check valve assembly, or DC, is for low hazard connections under continuous pressure. A pressure vacuum breaker, or PVB, protects against back-siphonage only but may be under continuous pressure, and it is installed at least 12 in above the highest downstream outlet. An atmospheric vacuum breaker, or AVB, is the cheapest and most limited: back-siphonage only, never under continuous pressure, no valve downstream, and installed at least 6 in above the flood level rim of the fixture. Hose bibbs need a vacuum breaker because a hose in a bucket is a textbook cross-connection.

An air gap is twice the effective opening, minimum 1 in
A 3/4 in effective opening needs a 1-1/2 in air gap. Near a wall the requirement increases to three times the opening. An air gap cannot fail mechanically, which is why it outranks every device.
IPC §608.15.1
High hazard under continuous pressure requires an RP
Boiler feeds with chemicals, irrigation with injectors, and process water need a reduced pressure principle assembly, which relieves to atmosphere between two checks if either check fouls.
UPC §603.0
A double check is for low hazard only
A DC is acceptable for aesthetic or non-health hazards such as a fire sprinkler system without antifreeze. It must never be substituted where a health hazard exists.
AVBs and PVBs stop back-siphonage only
Neither protects against back-pressure. An AVB must not be under continuous pressure for more than 12 hours and must be at least 6 in above the flood level rim, with no shutoff downstream. A PVB may be under continuous pressure and sits at least 12 in above the highest outlet.
IPC §608.13
Backflow assemblies must be accessible and tested
Testable assemblies require annual testing by a certified tester and must be installed where they can be reached, serviced, and allowed to discharge without damage.

Approved Materials, Joints, and Support

Copper tube is classified by wall thickness: Type K is the heaviest and is used for underground and water service, Type L is the general interior standard and is required under slabs in many jurisdictions, and Type M is the thinnest and is limited or prohibited for some uses. CPVC and PEX are both approved for hot and cold distribution, with PEX requiring protection from ultraviolet light and from direct contact with certain materials, and neither being used for the direct connection to a water heater without an approved metallic transition where the manufacturer requires it. Any solder or flux used in potable water piping must be lead free, meaning no more than 0.2 percent lead, and wetted surfaces of pipe, fittings, and fixtures must not exceed a 0.25 percent weighted average lead content. Where copper meets steel, a dielectric union or approved fitting prevents galvanic corrosion. Support spacing is a memorization item: horizontal copper 1-1/2 in and smaller every 6 ft, copper 2 in and larger every 10 ft, CPVC every 3 ft, PEX every 32 in horizontally, and cast iron every 5 ft with additional support at joints. Vertical piping is supported at each floor level, and hangers must be of a material compatible with the pipe so they do not cause corrosion.

Copper Type K, L, and M differ by wall thickness
K is heaviest and used underground and for water service, L is the interior standard, and M is the thinnest with limited approval. Diameter is the same, only the wall changes.
Solder and flux in potable water must be lead free
Lead free means not more than 0.2 percent lead in solder and flux, and not more than a 0.25 percent weighted average lead content on wetted surfaces of pipe, fittings, and fixtures.
IPC §605.14.3
Support horizontal copper every 6 ft or 10 ft by size
Copper 1-1/2 in and smaller is supported at 6 ft intervals and 2 in and larger at 10 ft intervals. A 40 ft run of 3/4 in copper therefore needs supports about every 6 ft.
IPC Table 308.5
Plastic piping needs closer support
CPVC is supported roughly every 3 ft horizontally and PEX about every 32 in, because plastic sags under its own weight when hot water runs through it.
UPC §313.3
Isolate dissimilar metals
Use a dielectric union or approved dielectric fitting where copper joins galvanized steel so galvanic action does not eat the joint from the inside.

Water Hammer, Valves, and Shutoffs

Water hammer is the shock wave that travels back up a pipe when a fast-closing valve stops moving water. Solenoid valves on clothes washers and dishwashers, and flushometers, are the usual culprits, and the fix required by code is an approved water hammer arrestor installed near the quick-closing valve. An old-style capped air chamber is not an accepted permanent solution because it waterlogs; a manufactured arrestor with a sealed piston or bellows keeps its air charge. Arrestors are sized and located per the manufacturer's listing, which the code adopts by reference. Beyond arrestors, valve placement is a code requirement in its own right. There must be a shutoff on the water service, a shutoff for each dwelling unit, a shutoff on the cold inlet of every water heater, and a stop at each fixture supply so one repair does not require draining a building. Valves must be accessible, which means reachable without removing permanent construction. Full-port ball valves and gate valves are used where free flow matters, while globe valves are used only where throttling is intended because they impose a much higher pressure drop.

Install water hammer arrestors at quick-closing valves
Any quick-closing valve, including clothes washer and dishwasher solenoids and flushometers, requires an approved arrestor installed and sized per the manufacturer's listing.
IPC §604.9
Capped air chambers are not a substitute
An unsealed air chamber eventually absorbs its air into the water and stops working. Only listed mechanical arrestors satisfy the requirement.
Provide a shutoff at the service, each unit, and each fixture
One valve on the water service, one per dwelling unit, one on the water heater cold inlet, and a stop at every fixture supply.
IPC §606.1
Valves must remain accessible
A shutoff behind drywall or under a fixed cabinet does not meet the code. Access panels are acceptable, permanent concealment is not.
Kiểm tra kiến thức của bạn
Câu hỏi luyện tập về Water Service, Distribution, and Backflow Protection
Luyện tập ngay →

Last updated: July 2026

Báo lỗi