Water Supply & DistributionCâu 35 / 120
A potable water supply outlet discharges over a receptor and the effective opening of the outlet is 1 in. What is the minimum required air gap?
a.1 in
b.1-1/2 in
c.3 in
d.2 in
Giải thích
The air gap must be at least twice the diameter of the effective opening, so 2 x 1 in = 2 in. The 1 in answer is only the code minimum floor that applies to very small openings, not the calculated value here. The 1-1/2 in choice uses a 1.5 multiplier and 3 in uses a 3x multiplier, neither of which the code uses.
Trích dẫn luật: UPC §603.3.1Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Static pressure at the water meter reads 68 psi. The highest fixture served is 32 ft above the meter. Ignoring meter and friction losses, how much pressure remains at the elevation of that fixture?
- How many feet of vertical head are equivalent to 22 psi of water pressure?
- A supply outlet has an effective opening of 3/8 in. What minimum air gap must be provided above the flood level rim of the receiving vessel?
- A gauge on the building side of the meter shows a static street pressure of 96 psi with no flow. What does the plumbing code require?
- A 40 ft horizontal run of 3/4 in copper water tube is installed in a ceiling. Using a maximum horizontal support spacing of 6 ft for copper 1-1/2 in and smaller, what is the minimum number of hangers required?
- A 24 ft horizontal run of 1/2 in CPVC water distribution pipe is supported at the maximum spacing of 3 ft. What is the minimum number of supports required?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Plumber Licensing Exam (UPC/IPC-based) · Quy trình kiểm tra