Water Supply & DistributionCâu 37 / 120
A gauge on the building side of the meter shows a static street pressure of 96 psi with no flow. What does the plumbing code require?
a.An approved pressure-reducing valve limiting downstream pressure to not more than 80 psi
b.Nothing, because the pressure is still under 100 psi
c.An increase of one pipe size on the water service
d.An approved vacuum relief valve on the water service
Giải thích
Where static pressure exceeds 80 psi, an approved pressure-reducing valve must be installed to hold the downstream distribution system at 80 psi or less. The 100 psi threshold does not exist in the code; 80 psi is the trigger. Upsizing pipe lowers friction loss but does nothing to static pressure, and a vacuum relief valve protects against collapse or siphoning, not high pressure.
Trích dẫn luật: UPC §608.2Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- How many feet of vertical head are equivalent to 22 psi of water pressure?
- A potable water supply outlet discharges over a receptor and the effective opening of the outlet is 1 in. What is the minimum required air gap?
- A supply outlet has an effective opening of 3/8 in. What minimum air gap must be provided above the flood level rim of the receiving vessel?
- A 40 ft horizontal run of 3/4 in copper water tube is installed in a ceiling. Using a maximum horizontal support spacing of 6 ft for copper 1-1/2 in and smaller, what is the minimum number of hangers required?
- A 24 ft horizontal run of 1/2 in CPVC water distribution pipe is supported at the maximum spacing of 3 ft. What is the minimum number of supports required?
- PEX tubing runs horizontally for 16 ft above a suspended ceiling. Using the maximum horizontal support spacing of 32 in for PEX, what is the minimum number of supports?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Plumber Licensing Exam (UPC/IPC-based) · Quy trình kiểm tra