Type III — Low-Pressure第 169 / 240 题

Frequent operation of the purge unit on a low-pressure chiller is usually a sign that:

a.The machine has a leak drawing air in
b.The refrigerant charge is too high
c.The condenser water is too cold
d.The compressor is overcharged with oil

解析

A rising purge rate means air is leaking into the vacuum side of the chiller, so the purge unit runs more often to remove it. The correct response is to find and repair the leak, not simply purge more. Modern high-efficiency purge units also track how much they run as a diagnostic.

免费刷完整 240 道题库 — 无需注册。