Chapter 5 of 620% of exam

Alarm Service and False Alarm Prevention

Most false alarms trace to users, the rest to equipment and installation. Service work is about finding the cause, fixing it and leaving the customer able to use the system.

Why false alarms happen

User error is the leading cause: wrong codes, doors left unsecured and leaving after the exit delay ends. Environmental causes include heat sources, pets, insects and moving objects in a motion detector's pattern, loose doors with wide contact gaps, and damaged or corroded wiring. Hands-on training of every user at turnover is the most effective prevention step.

Panel features that help

Features aimed at user-caused alarms include audible exit warnings, exit time restart, an abort window that lets a user disarm before the signal is sent, swinger shutdown that stops one zone from sending repeated alarms, and cross-zoning that needs two zones to trip. Monitoring centers use enhanced call verification, calling the premises and then a second number before requesting dispatch.

Troubleshooting and service

A multimeter measures loop resistance and voltage. A supervised zone should read about the value of its end-of-line resistor; near zero suggests a short and an open circuit reads infinite. Dividing a loop in half narrows down an intermittent fault. The technician places the account on test before working, takes it off test afterward, leaves the system operational, documents any bypass and tells the customer what is unprotected. A service record shows the date, the problem, the work and the tests.

What the Act requires in service

A licensee notifies the owner of a defect it finds in a system it installed and provides the warranty service it agreed to (§7599.58). False reports are a violation (§7599.48). Local false alarm ordinances commonly use fines or suspended response; under §7592.8 the operator answers only for fines caused by its own error, improper installation or defective equipment.