Seismic Forces: Non-Building Structures, Components and Equipment

Tanks, signs, equipment, parapets and partitions are designed with their own equations. Expect direct calculations of the component force Fp and its limits.

Nonstructural component force

The horizontal design force on a component is Fp = 0.4·ap·SDS·Wp·(1 + 2z/h) / (Rp/Ip) (ASCE 7-16 Section 13.3.1). It need not exceed 1.6·SDS·Ip·Wp and may not be less than 0.3·SDS·Ip·Wp. The term z/h is the attachment height as a fraction of the roof height, so the same item attracts three times the amplification at the roof that it does at grade.

Component factors

The amplification factor ap reflects how flexible the component is, the response modification factor Rp its ductility, and the importance factor Ip is 1.0 or 1.5; 1.5 applies to life-safety components, components containing hazardous materials and those needed for continued operation of a Risk Category IV facility (Section 13.1.3). Exam stems supply ap and Rp because the tables are not reproduced.

Nonbuilding structures

Structures such as tanks, silos, towers and racks are covered by ASCE 7-16 Chapter 15. Those similar to buildings use the building procedures with their own R values and height limits; those not similar to buildings have separate coefficients and minimum base shear values. A rigid nonbuilding structure, with a period under 0.06 s, uses V = 0.30·SDS·W·Ie (Section 15.4.2).