California Civil Engineer: Seismic Principles — All Questions

42 questions

Seismic Forces: Non-Building Structures, Components and Equipment

Determine the horizontal seismic design force for a rigidly mounted piece of mechanical equipment: Wp = 2,000 lb, ap = 1, Rp = 2.5, Ip = 1, SDS = 1g, attached at height z = 40 ft in a building with roof height h = 40 ft.

  • a.960 lb✓
  • b.1,200 lb
  • c.1,248 lb
  • d.3,200 lb

ASCE 7-16 Eq. 13.3-1: Fp = 0.4 ap SDS Wp (1 + 2z/h)/(Rp/Ip) = 0.4 x 1 x 1 x 2,000 x (1 + 2 x 40/40) / (2.5/1) = 960 lb. Limits: 0.3 SDS Ip Wp = 600 lb minimum (Eq. 13.3-3) and 1.6 SDS Ip Wp = 3,200 lb maximum (Eq. 13.3-2). The calculated value is between the limits, so it governs: Fp = 960 lb. Omitting the (1 + 2z/h) height amplification is the most common slip.

Seismic Forces: Non-Building Structures, Components and Equipment

Determine the horizontal seismic design force for a spring-isolated air handler (ap and Rp as given): Wp = 3,500 lb, ap = 2.5, Rp = 2, Ip = 1, SDS = 1.2g, attached at height z = 30 ft in a building with roof height h = 60 ft.

  • a.1,260 lb
  • b.2,100 lb
  • c.4,200 lb✓
  • d.6,720 lb

ASCE 7-16 Eq. 13.3-1: Fp = 0.4 ap SDS Wp (1 + 2z/h)/(Rp/Ip) = 0.4 x 2.5 x 1.2 x 3,500 x (1 + 2 x 30/60) / (2/1) = 4,200 lb. Limits: 0.3 SDS Ip Wp = 1,260 lb minimum (Eq. 13.3-3) and 1.6 SDS Ip Wp = 6,720 lb maximum (Eq. 13.3-2). The calculated value is between the limits, so it governs: Fp = 4,200 lb. Omitting the (1 + 2z/h) height amplification is the most common slip.

Seismic Forces: Non-Building Structures, Components and Equipment

Determine the horizontal seismic design force for an interior nonstructural partition: Wp = 600 lb, ap = 1, Rp = 2.5, Ip = 1, SDS = 0.9g, attached at height z = 12 ft in a building with roof height h = 48 ft.

  • a.86 lb
  • b.108 lb
  • c.130 lb
  • d.162 lb✓

ASCE 7-16 Eq. 13.3-1: Fp = 0.4 ap SDS Wp (1 + 2z/h)/(Rp/Ip) = 0.4 x 1 x 0.9 x 600 x (1 + 2 x 12/48) / (2.5/1) = 130 lb. Limits: 0.3 SDS Ip Wp = 162 lb minimum (Eq. 13.3-3) and 1.6 SDS Ip Wp = 864 lb maximum (Eq. 13.3-2). The calculated value is below the minimum, so the minimum governs: Fp = 162 lb. Omitting the (1 + 2z/h) height amplification is the most common slip.

Seismic Forces: Non-Building Structures, Components and Equipment

Determine the horizontal seismic design force for an emergency generator required to function after the earthquake: Wp = 8,000 lb, ap = 1, Rp = 2.5, Ip = 1.5, SDS = 1g, attached at height z = 0 ft in a building with roof height h = 50 ft.

  • a.1,920 lb
  • b.2,412 lb
  • c.2,880 lb
  • d.3,600 lb✓

ASCE 7-16 Eq. 13.3-1: Fp = 0.4 ap SDS Wp (1 + 2z/h)/(Rp/Ip) = 0.4 x 1 x 1 x 8,000 x (1 + 2 x 0/50) / (2.5/1.5) = 1,920 lb. Limits: 0.3 SDS Ip Wp = 3,600 lb minimum (Eq. 13.3-3) and 1.6 SDS Ip Wp = 19,200 lb maximum (Eq. 13.3-2). The calculated value is below the minimum, so the minimum governs: Fp = 3,600 lb. Omitting the (1 + 2z/h) height amplification is the most common slip.

Seismic Forces: Non-Building Structures, Components and Equipment

Determine the horizontal seismic design force for an unbraced cantilever parapet: Wp = 450 lb, ap = 2.5, Rp = 2.5, Ip = 1, SDS = 1.1g, attached at height z = 30 ft in a building with roof height h = 30 ft.

  • a.148 lb
  • b.594 lb✓
  • c.772 lb
  • d.792 lb

ASCE 7-16 Eq. 13.3-1: Fp = 0.4 ap SDS Wp (1 + 2z/h)/(Rp/Ip) = 0.4 x 2.5 x 1.1 x 450 x (1 + 2 x 30/30) / (2.5/1) = 594 lb. Limits: 0.3 SDS Ip Wp = 148 lb minimum (Eq. 13.3-3) and 1.6 SDS Ip Wp = 792 lb maximum (Eq. 13.3-2). The calculated value is between the limits, so it governs: Fp = 594 lb. Omitting the (1 + 2z/h) height amplification is the most common slip.

Seismic Forces: Non-Building Structures, Components and Equipment

Determine the horizontal seismic design force for a distribution-system component with flexible response: Wp = 1,200 lb, ap = 2.5, Rp = 6, Ip = 1.5, SDS = 1.4g, attached at height z = 20 ft in a building with roof height h = 80 ft.

  • a.420 lb
  • b.630 lb
  • c.756 lb✓
  • d.4,032 lb

ASCE 7-16 Eq. 13.3-1: Fp = 0.4 ap SDS Wp (1 + 2z/h)/(Rp/Ip) = 0.4 x 2.5 x 1.4 x 1,200 x (1 + 2 x 20/80) / (6/1.5) = 630 lb. Limits: 0.3 SDS Ip Wp = 756 lb minimum (Eq. 13.3-3) and 1.6 SDS Ip Wp = 4,032 lb maximum (Eq. 13.3-2). The calculated value is below the minimum, so the minimum governs: Fp = 756 lb. Omitting the (1 + 2z/h) height amplification is the most common slip.

Seismic Forces: Non-Building Structures, Components and Equipment

A rigid nonbuilding structure (fundamental period less than 0.06 s) weighs 150 kips including operating contents. SDS = 1g, Ie = 1. What is the design lateral force?

  • a.7 kips
  • b.45 kips✓
  • c.60 kips
  • d.150 kips

ASCE 7-16 Section 15.4.2 (Eq. 15.4-5): V = 0.30 SDS W Ie = 0.30 x 1 x 150 x 1 = 45 kips, distributed with height according to the mass distribution. A rigid structure moves with the ground, so no R factor and no period-based reduction apply; the 0.044 SDS Ie expression is a minimum Cs for flexible structures, not the rigid-structure force.

Seismic Forces: Non-Building Structures, Components and Equipment

A rigid nonbuilding structure (fundamental period less than 0.06 s) weighs 80 kips including operating contents. SDS = 1.2g, Ie = 1.25. What is the design lateral force?

  • a.29 kips
  • b.36 kips✓
  • c.48 kips
  • d.120 kips

ASCE 7-16 Section 15.4.2 (Eq. 15.4-5): V = 0.30 SDS W Ie = 0.30 x 1.2 x 80 x 1.25 = 36 kips, distributed with height according to the mass distribution. A rigid structure moves with the ground, so no R factor and no period-based reduction apply; the 0.044 SDS Ie expression is a minimum Cs for flexible structures, not the rigid-structure force.

Seismic Forces: Non-Building Structures, Components and Equipment

A rigid nonbuilding structure (fundamental period less than 0.06 s) weighs 420 kips including operating contents. SDS = 0.8g, Ie = 1.5. What is the design lateral force?

  • a.101 kips
  • b.151 kips✓
  • c.202 kips
  • d.504 kips

ASCE 7-16 Section 15.4.2 (Eq. 15.4-5): V = 0.30 SDS W Ie = 0.30 x 0.8 x 420 x 1.5 = 151 kips, distributed with height according to the mass distribution. A rigid structure moves with the ground, so no R factor and no period-based reduction apply; the 0.044 SDS Ie expression is a minimum Cs for flexible structures, not the rigid-structure force.

Seismic Forces: Non-Building Structures, Components and Equipment

Compute the base shear for a ground-supported steel storage rack type structure treated as a nonbuilding structure not similar to buildings: W = 200 kips, SDS = 1g, SD1 = 0.6g, S1 below 0.6g, R = 4, Ie = 1, T = 0.4 s.

  • a.8.8 kips
  • b.30.0 kips
  • c.40.0 kips
  • d.50.0 kips✓

Chapter 15 of ASCE 7-16 uses the Chapter 12 base shear with a modified floor: Cs = SDS/(R/Ie) = 0.250, need not exceed SD1/[T(R/Ie)] = 0.375, and for nonbuilding structures not similar to buildings may not be less than 0.044 SDS Ie = 0.044 nor 0.03 (Section 15.4.1). Governing Cs = 0.250; V = 0.250 x 200 = 50.0 kips. The 0.30 SDS W Ie formula is reserved for rigid structures with T below 0.06 s.

Seismic Forces: Non-Building Structures, Components and Equipment

Compute the base shear for a skirt-supported vertical vessel (nonbuilding structure not similar to buildings): W = 90 kips, SDS = 1.2g, SD1 = 0.7g, S1 below 0.6g, R = 2, Ie = 1.25, T = 0.3 s.

  • a.5.9 kips
  • b.67.5 kips✓
  • c.94.5 kips
  • d.131.2 kips

Chapter 15 of ASCE 7-16 uses the Chapter 12 base shear with a modified floor: Cs = SDS/(R/Ie) = 0.750, need not exceed SD1/[T(R/Ie)] = 1.458, and for nonbuilding structures not similar to buildings may not be less than 0.044 SDS Ie = 0.066 nor 0.03 (Section 15.4.1). Governing Cs = 0.750; V = 0.750 x 90 = 67.5 kips. The 0.30 SDS W Ie formula is reserved for rigid structures with T below 0.06 s.

Seismic Forces: Non-Building Structures, Components and Equipment

Compute the base shear for a tall, flexible steel stack (nonbuilding structure not similar to buildings): W = 300 kips, SDS = 0.5g, SD1 = 0.25g, S1 below 0.6g, R = 3, Ie = 1, T = 3 s.

  • a.9.0 kips✓
  • b.12.6 kips
  • c.45.0 kips
  • d.50.0 kips

Chapter 15 of ASCE 7-16 uses the Chapter 12 base shear with a modified floor: Cs = SDS/(R/Ie) = 0.167, need not exceed SD1/[T(R/Ie)] = 0.028, and for nonbuilding structures not similar to buildings may not be less than 0.044 SDS Ie = 0.022 nor 0.03 (Section 15.4.1). Governing Cs = 0.030; V = 0.030 x 300 = 9.0 kips. The 0.30 SDS W Ie formula is reserved for rigid structures with T below 0.06 s.

Seismic Forces: Non-Building Structures, Components and Equipment

An equipment support structure weighs 50 kips (with contents) and has a lateral stiffness of 30 kips/in. What is its fundamental period, used to decide whether it is rigid (T less than 0.06 s)? (g = 386.4 in./s^2)

  • a.0.066 s
  • b.0.206 s
  • c.0.413 s✓
  • d.0.825 s

T = 2 pi sqrt(W/(g k)) = 2 pi sqrt(50/(386.4 x 30)) = 0.413 s. This is above 0.06 s, so the structure is not rigid and its dynamic amplification must be considered under ASCE 7-16 Chapter 15 (and for components, Section 13.3 uses the same 0.06 s threshold to separate rigid from flexible). Omitting the 2 pi gives 0.066 s.

Seismic Forces: Non-Building Structures, Components and Equipment

An equipment support structure weighs 18 kips (with contents) and has a lateral stiffness of 4 kips/in. What is its fundamental period, used to decide whether it is rigid (T less than 0.06 s)? (g = 386.4 in./s^2)

  • a.0.339 s
  • b.0.678 s✓
  • c.1.356 s
  • d.2.034 s

T = 2 pi sqrt(W/(g k)) = 2 pi sqrt(18/(386.4 x 4)) = 0.678 s. This is above 0.06 s, so the structure is not rigid and its dynamic amplification must be considered under ASCE 7-16 Chapter 15 (and for components, Section 13.3 uses the same 0.06 s threshold to separate rigid from flexible). Omitting the 2 pi gives 0.108 s.

Seismic Forces: Non-Building Structures, Components and Equipment

An equipment support structure weighs 200 kips (with contents) and has a lateral stiffness of 900 kips/in. What is its fundamental period, used to decide whether it is rigid (T less than 0.06 s)? (g = 386.4 in./s^2)

  • a.0.075 s
  • b.0.151 s✓
  • c.0.301 s
  • d.0.452 s

T = 2 pi sqrt(W/(g k)) = 2 pi sqrt(200/(386.4 x 900)) = 0.151 s. This is above 0.06 s, so the structure is not rigid and its dynamic amplification must be considered under ASCE 7-16 Chapter 15 (and for components, Section 13.3 uses the same 0.06 s threshold to separate rigid from flexible). Omitting the 2 pi gives 0.024 s.

Seismic Forces: Non-Building Structures, Components and Equipment

Regardless of ap, Rp or attachment height, what is the upper-bound horizontal seismic force Fp for a 5,000-lb nonstructural component with Ip = 1 where SDS = 1g?

  • a.1,500 lb
  • b.8,000 lb✓
  • c.10,000 lb
  • d.12,000 lb

ASCE 7-16 Eq. 13.3-2 caps the component force at Fp = 1.6 SDS Ip Wp = 1.6 x 1 x 1 x 5,000 = 8,000 lb. The value 1,500 lb is the lower bound 0.3 SDS Ip Wp (Eq. 13.3-3), and 0.4 SDS Ip Wp is only the ground-level form of Eq. 13.3-1 with ap/Rp = 1.

Seismic Forces: Non-Building Structures, Components and Equipment

Regardless of ap, Rp or attachment height, what is the upper-bound horizontal seismic force Fp for a 2,400-lb nonstructural component with Ip = 1.5 where SDS = 1.3g?

  • a.1,404 lb
  • b.1,872 lb
  • c.7,488 lb✓
  • d.9,360 lb

ASCE 7-16 Eq. 13.3-2 caps the component force at Fp = 1.6 SDS Ip Wp = 1.6 x 1.3 x 1.5 x 2,400 = 7,488 lb. The value 1,404 lb is the lower bound 0.3 SDS Ip Wp (Eq. 13.3-3), and 0.4 SDS Ip Wp is only the ground-level form of Eq. 13.3-1 with ap/Rp = 1.

Seismic Forces: Non-Building Structures, Components and Equipment

Regardless of ap, Rp or attachment height, what is the upper-bound horizontal seismic force Fp for a 900-lb nonstructural component with Ip = 1 where SDS = 0.75g?

  • a.202 lb
  • b.1,080 lb✓
  • c.1,350 lb
  • d.1,620 lb

ASCE 7-16 Eq. 13.3-2 caps the component force at Fp = 1.6 SDS Ip Wp = 1.6 x 0.75 x 1 x 900 = 1,080 lb. The value 202 lb is the lower bound 0.3 SDS Ip Wp (Eq. 13.3-3), and 0.4 SDS Ip Wp is only the ground-level form of Eq. 13.3-1 with ap/Rp = 1.

Seismic Forces: Non-Building Structures, Components and Equipment

What component amplification factor ap applies to a rigid, rigidly attached component?

  • a.0.4
  • b.2.5
  • c.1.0✓
  • d.3.5

ASCE 7-16 Section 13.3.1 and the Chapter 13 tables use ap = 1.0 for rigid components and 2.5 for flexible components or flexibly attached ones, reflecting dynamic amplification of the floor motion. No tabulated value exceeds 2.5.

Seismic Forces: Non-Building Structures, Components and Equipment

A component is considered flexible, rather than rigid, when its fundamental period exceeds what value?

  • a.0.01 s
  • b.0.5 s
  • c.1.0 s
  • d.0.06 s✓

ASCE 7-16 Section 11.2 defines a rigid component as one with a fundamental period of 0.06 s or less and a flexible one as longer than 0.06 s. The same threshold separates rigid nonbuilding structures in Chapter 15.

Seismic Forces: Non-Building Structures, Components and Equipment

Which component is assigned a component importance factor Ip of 1.5?

  • a.A rooftop sign on a retail building that holds no hazardous material
  • b.A bookshelf under 6 ft tall in a Risk Category II office building
  • c.A decorative light fixture in a private office of an ordinary building
  • d.A fire sprinkler system needed for life safety after the earthquake✓

ASCE 7-16 Section 13.1.3 assigns Ip = 1.5 to components required to function for life safety after an earthquake (including fire sprinklers and egress stairways), to those containing hazardous substances beyond threshold quantities, and to components needed for continued operation of Risk Category IV facilities. All others use 1.0.

Seismic Forces: Non-Building Structures, Components and Equipment

In the component force equation, what does the term (1 + 2z/h) account for?

  • a.Higher accelerations at higher elevations in the building✓
  • b.The ductility of the anchorage attaching the component
  • c.Reduced accelerations at higher elevations in the building
  • d.The importance of the building occupancy to the public

ASCE 7-16 Eq. 13.3-1 amplifies the force linearly from 1.0 at the base (z = 0) to 3.0 at the roof (z = h), representing how floor accelerations grow up the height. Ductility of the component is captured by Rp and importance by Ip.

Seismic Forces: Non-Building Structures, Components and Equipment

At what location and in which direction is the component force Fp applied?

  • a.At the component's center of gravity, independently in at least two orthogonal horizontal directions✓
  • b.At the top of the component, acting simultaneously in all three orthogonal directions at full value
  • c.At the base of the component only, acting in the single direction parallel to the nearest wall
  • d.At the point of anchorage, acting vertically only in combination with the full dead load

ASCE 7-16 Section 13.3.1 applies Fp at the component's center of gravity, distributed relative to its mass, independently in at least two orthogonal horizontal directions in combination with service loads. A concurrent vertical force of plus or minus 0.2 SDS Wp is also considered.

Seismic Forces: Non-Building Structures, Components and Equipment

What concurrent vertical seismic force is considered in component design?

  • a.Plus or minus 0.4 SDS Wp
  • b.Plus or minus 1.6 SDS Wp
  • c.Plus or minus 0.044 SDS Wp
  • d.Plus or minus 0.2 SDS Wp✓

ASCE 7-16 Section 13.3.1.2 requires a concurrent vertical force of plus or minus 0.2 SDS Wp, which matters for overturning and anchor tension. The 1.6 coefficient is the cap on horizontal Fp, and 0.044 belongs to the minimum base shear.

Seismic Forces: Non-Building Structures, Components and Equipment

May friction caused by gravity be relied on to resist seismic forces on a nonstructural component?

  • a.No; components must be positively attached without relying on gravity friction✓
  • b.Yes; friction may resist one-half of the design force in every design category
  • c.No; unless the component is installed at or below the grade level of the building
  • d.Yes; friction may resist the full force when the component exceeds 400 lb

ASCE 7-16 Section 13.4 requires a continuous load path through positive attachment (bolting, welding or equivalent) and states that frictional resistance produced by gravity shall not be considered. Vertical earthquake motion can reduce the normal force just when friction is needed.

Seismic Forces: Non-Building Structures, Components and Equipment

A nonbuilding structure is supported by a building, and its weight is less than 25% of the combined effective seismic weight. How are its design forces determined?

  • a.As a nonstructural component under Chapter 13✓
  • b.As a building under the provisions of Chapter 12
  • c.By a combined model of both structures only
  • d.No seismic design is required in this case

ASCE 7-16 Section 15.3.1: where the supported nonbuilding structure weighs less than 25% of the combined weight, its forces come from Chapter 13 with Rp and ap. At 25% or more (Section 15.3.2), interaction matters and a combined analysis is generally needed.

Seismic Forces: Non-Building Structures, Components and Equipment

Which is an example of a nonbuilding structure NOT similar to buildings?

  • a.A braced-frame boiler support frame
  • b.A ground-supported liquid storage tank✓
  • c.A steel pipe rack with moment frames
  • d.A concrete-frame industrial structure

ASCE 7-16 Chapter 15 distinguishes structures with building-like frames (pipe racks, boiler frames, Table 15.4-1) from those that respond very differently, such as tanks, vessels, stacks and silos (Table 15.4-2). Tanks have fluid-structure interaction and no story framing.

Seismic Forces: Non-Building Structures, Components and Equipment

In the seismic analysis of a ground-supported liquid storage tank, what is the convective component?

  • a.The soil mass beneath the tank that moves with the foundation
  • b.The portion of the liquid that moves rigidly with the tank shell
  • c.The sloshing portion of the liquid, which responds at a long period✓
  • d.The weight of the tank roof and its supporting rafter structure

Tank liquid is modeled as an impulsive mass moving with the shell at a short period and a convective (sloshing) mass with a period of several seconds. ASCE 7-16 Section 15.7 combines them and requires freeboard for the sloshing wave. The roof and shell weights are separate inertial terms.

Seismic Forces: Non-Building Structures, Components and Equipment

Why is freeboard provided above the liquid surface in a tank in a seismic region?

  • a.To reduce the hydrostatic pressure acting on the tank floor
  • b.To accommodate the sloshing wave without damage or spilling✓
  • c.To increase the impulsive weight and stabilize the shell
  • d.To shorten the period of the convective mode of the liquid

ASCE 7-16 Section 15.7.6.1.2 requires freeboard based on the sloshing wave height so the wave does not damage the roof or spill contents (critical for hazardous liquids). Freeboard does not change hydrostatic pressure at the bottom for a given liquid depth.

Seismic Forces: Non-Building Structures, Components and Equipment

How is the design force distributed over the height of a rigid nonbuilding structure?

  • a.According to the distribution of mass✓
  • b.As a uniform pressure on the windward face
  • c.As a single force applied at the top
  • d.As an inverted triangle in every case

ASCE 7-16 Section 15.4.2: for a rigid nonbuilding structure the force V = 0.30 SDS W Ie is distributed with height in accordance with the mass distribution, since every point moves with the ground acceleration. The inverted triangle reflects first-mode response of a flexible structure.

Seismic Forces: Non-Building Structures, Components and Equipment

A mechanical component in a Seismic Design Category D building has Ip = 1.0, is positively attached, weighs 350 lb, and has its center of mass 3 ft above the floor. Is seismic design of the component required under ASCE 7-16 Chapter 13?

  • a.Yes; every component in SDC D must be designed
  • b.No; it falls under the 400-lb, 4-ft exemption✓
  • c.Yes; only components under 20 lb are exempt
  • d.No; all components with Ip = 1.0 are exempt

ASCE 7-16 Section 13.1.4 exempts mechanical and electrical components in SDC D through F with Ip = 1.0 that are positively attached, weigh 400 lb or less, and have a center of mass 4 ft or less above the adjacent floor, provided flexible connections are used. A separate exemption covers items of 20 lb or less.

Seismic Forces: Non-Building Structures, Components and Equipment

For which Seismic Design Category are architectural components (other than parapets) with Ip = 1.0 generally exempt from Chapter 13?

  • a.Seismic Design Category F
  • b.Seismic Design Category D
  • c.Seismic Design Category B✓
  • d.Seismic Design Category E

ASCE 7-16 Section 13.1.4 exempts architectural components in SDC B, other than parapets, when Ip is 1.0. In SDC D through F architectural components such as partitions, ceilings and cladding must be designed for Fp and for relative displacements.

Seismic Forces: Non-Building Structures, Components and Equipment

What is the function of the component response modification factor Rp?

  • a.It increases Fp to reflect the dynamic amplification that occurs within a flexible component
  • b.It reduces Fp for components located in low-occupancy storage buildings
  • c.It reduces Fp for the energy-absorbing capacity of the component and its attachment✓
  • d.It increases Fp to reflect the height of the component within the building

Rp plays the role for components that R plays for buildings: ductile, deformable components and attachments get higher Rp and lower design forces (ASCE 7-16 Tables 13.5-1 and 13.6-1). Amplification is handled by ap and height by the (1 + 2z/h) term.

Seismic Forces: Non-Building Structures, Components and Equipment

Exterior precast cladding panels are connected to a building frame. What must the connections be designed to accommodate, in addition to Fp?

  • a.The thermal expansion of the roof membrane above the top panel
  • b.The overturning moment of the entire building at the foundation
  • c.The full dead load of the story above transferred down through the panel body
  • d.The seismic relative displacement (story drift) between attachment points✓

ASCE 7-16 Section 13.5.3 requires exterior nonstructural wall panel connections and joints to accommodate the seismic relative displacement DpI of Section 13.3.2, using slotted holes, long rods or similar ductile, sliding details. Panels are not meant to carry frame gravity or overturning forces.

Seismic Forces: Non-Building Structures, Components and Equipment

How is the seismic relative displacement used for component design, DpI, obtained from the displacement Dp?

  • a.DpI = Dp divided by the response modification factor R
  • b.DpI = Dp multiplied by the building importance factor Ie✓
  • c.DpI = Dp divided by the amplification factor Cd
  • d.DpI = Dp multiplied by the component factor ap

ASCE 7-16 Eq. 13.3-6: DpI = Dp x Ie, where Dp is the difference in inelastic deflections (already including Cd) at the two attachment points. Dividing by R or Cd would return to elastic values and understate what glazing, cladding and piping must accommodate.

Seismic Forces: Non-Building Structures, Components and Equipment

Which component type has ap = 2.5 because it responds as a flexible cantilever?

  • a.A rigid floor-mounted pump
  • b.A wall braced above its center of mass
  • c.An unbraced parapet✓
  • d.A full-height interior partition

ASCE 7-16 Table 13.5-1 assigns ap = 2.5 to cantilever elements unbraced or braced below their center of mass, such as parapets and chimneys, which whip at the roof where accelerations are highest. Walls braced above the center of mass and rigid equipment use ap = 1.0.

Seismic Forces: Non-Building Structures, Components and Equipment

Active mechanical equipment with Ip = 1.5 that must remain operable after the design earthquake requires what, in addition to anchorage design?

  • a.Special certification by shake-table testing or experience data✓
  • b.An annual inspection performed by the local fire marshal
  • c.A waiver of the relative displacement requirements for piping
  • d.A doubling of the anchor bolt diameter over the calculated size

ASCE 7-16 Section 13.2.2 requires active mechanical and electrical equipment that must remain operable (designated seismic systems) to be certified by the manufacturer through approved shake-table testing or experience data. Anchorage alone keeps equipment in place but does not show it will still run.

Seismic Forces: Non-Building Structures, Components and Equipment

Under ASCE 7-16, what additional factor is applied to seismic forces when designing certain anchors in concrete or masonry for nonstructural components?

  • a.The live load reduction factor from Chapter 4
  • b.The redundancy factor of 1.3 taken from Chapter 12
  • c.The deflection amplification factor Cd of the supporting building
  • d.The component overstrength factor from the Chapter 13 tables✓

ASCE 7-16 Section 13.4.2 and the overstrength column added to Tables 13.5-1 and 13.6-1 require the overstrength factor for anchors in concrete or masonry where required by the tables, so a brittle anchor does not fail before the component yields. Redundancy does not apply to components.

Seismic Forces: Non-Building Structures, Components and Equipment

For a nonbuilding structure not similar to buildings, what is the absolute minimum seismic response coefficient Cs under ASCE 7-16 Section 15.4.1?

  • a.0.03✓
  • b.0.30
  • c.0.01
  • d.0.10

ASCE 7-16 Section 15.4.1 replaces the building minimum with Cs = 0.044 SDS Ie, not less than 0.03, for nonbuilding structures not similar to buildings. The 0.01 floor applies to buildings, and 0.30 is the coefficient in the rigid-structure formula.

Seismic Forces: Non-Building Structures, Components and Equipment

Which document or quantity determines the importance factor Ie for a nonbuilding structure?

  • a.The response modification coefficient R that is assigned to the system
  • b.The largest value from the risk category, reference documents or hazard✓
  • c.The component importance factor Ip of the equipment that it supports
  • d.The site class that was established in the geotechnical investigation

ASCE 7-16 Section 15.4.1.1 takes the importance factor and risk category for a nonbuilding structure as the largest value from the applicable reference document, from Table 1.5-2, or as specified elsewhere in Chapter 15 based on the hazard of the contents and function.

Seismic Forces: Non-Building Structures, Components and Equipment

The component force equation yields a value below 0.3 SDS Ip Wp for a floor-mounted item at grade. Which force is used for design?

  • a.1.6 SDS Ip Wp, the maximum
  • b.0.3 SDS Ip Wp, the minimum✓
  • c.Zero, since it is at grade
  • d.The lower calculated value

ASCE 7-16 Eq. 13.3-3 sets a floor of 0.3 SDS Ip Wp. At grade with high Rp the basic equation often falls below the floor, so the minimum governs. The 1.6 SDS Ip Wp value is an upper cap, used only when the calculated force is larger than it.

Seismic Forces: Non-Building Structures, Components and Equipment

A suspended piping system crosses a seismic separation joint between two buildings. What is the key design consideration?

  • a.A larger pipe diameter so that the stress in the pipe wall is reduced
  • b.Insulation thick enough to dampen the vibration of the pipe contents
  • c.A rigid anchor on each side so the pipe ties the two buildings together
  • d.Flexibility to accommodate the relative displacement between the buildings✓

Components attached to two structures must accommodate the relative displacements of ASCE 7-16 Section 13.3.2.2 between them, typically with flexible couplings or loops. Rigidly tying the pipe across the joint makes it a strut that will rupture when the buildings move out of phase.