California Civil Engineer: Seismic Principles — All Questions

78 questions

Seismic Forces: Building Structures

Estimate the approximate fundamental period Ta of a steel moment-resisting frame with structural height hn = 60 ft. Use Ct = 0.028 and x = 0.8.

  • a.0.29 s
  • b.0.50 s
  • c.0.74 s✓
  • d.1.68 s

ASCE 7-16 Eq. 12.8-7: Ta = Ct x hn^x = 0.028 x 60^0.8 = 0.74 s, with hn in feet. Dropping the exponent gives 1.68 s, and multiplying by an upper-limit coefficient Cu belongs to the check on a computed period, not to Ta itself.

Seismic Forces: Building Structures

Estimate the approximate fundamental period Ta of a concrete moment-resisting frame with structural height hn = 48 ft. Use Ct = 0.016 and x = 0.9.

  • a.0.40 s
  • b.0.52 s✓
  • c.0.73 s
  • d.0.77 s

ASCE 7-16 Eq. 12.8-7: Ta = Ct x hn^x = 0.016 x 48^0.9 = 0.52 s, with hn in feet. Dropping the exponent gives 0.77 s, and multiplying by an upper-limit coefficient Cu belongs to the check on a computed period, not to Ta itself.

Seismic Forces: Building Structures

Estimate the approximate fundamental period Ta of a concrete shear wall building (classified as 'all other structural systems') with structural height hn = 40 ft. Use Ct = 0.02 and x = 0.75.

  • a.0.13 s
  • b.0.23 s
  • c.0.25 s
  • d.0.32 s✓

ASCE 7-16 Eq. 12.8-7: Ta = Ct x hn^x = 0.02 x 40^0.75 = 0.32 s, with hn in feet. Dropping the exponent gives 0.80 s, and multiplying by an upper-limit coefficient Cu belongs to the check on a computed period, not to Ta itself.

Seismic Forces: Building Structures

Estimate the approximate fundamental period Ta of a steel buckling-restrained braced frame with structural height hn = 75 ft. Use Ct = 0.03 and x = 0.75.

  • a.0.76 s✓
  • b.0.96 s
  • c.1.07 s
  • d.2.25 s

ASCE 7-16 Eq. 12.8-7: Ta = Ct x hn^x = 0.03 x 75^0.75 = 0.76 s, with hn in feet. Dropping the exponent gives 2.25 s, and multiplying by an upper-limit coefficient Cu belongs to the check on a computed period, not to Ta itself.

Seismic Forces: Building Structures

A building has approximate period Ta = 0.60 s. A properly substantiated computer analysis gives T = 1.05 s. With Cu = 1.4, what period may be used to compute base shear for strength design?

  • a.0.60 s
  • b.0.82 s
  • c.0.84 s✓
  • d.1.05 s

ASCE 7-16 Section 12.8.2 caps the computed period at Cu x Ta = 1.4 x 0.60 = 0.84 s. The analysis value of 1.05 s is longer, so the cap of 0.84 s governs. Using Ta = 0.60 s is permitted but more conservative than required, and averaging the two has no code basis.

Seismic Forces: Building Structures

A building has approximate period Ta = 0.45 s. A properly substantiated computer analysis gives T = 0.52 s. With Cu = 1.4, what period may be used to compute base shear for strength design?

  • a.0.42 s
  • b.0.45 s
  • c.0.48 s
  • d.0.52 s✓

ASCE 7-16 Section 12.8.2 caps the computed period at Cu x Ta = 1.4 x 0.45 = 0.63 s. The analysis value of 0.52 s is below the cap, so it may be used directly. Using Ta = 0.45 s is permitted but more conservative than required, and averaging the two has no code basis.

Seismic Forces: Building Structures

A building has approximate period Ta = 0.80 s. A properly substantiated computer analysis gives T = 1.40 s. With Cu = 1.5, what period may be used to compute base shear for strength design?

  • a.1.20 s✓
  • b.1.40 s
  • c.1.50 s
  • d.2.10 s

ASCE 7-16 Section 12.8.2 caps the computed period at Cu x Ta = 1.5 x 0.80 = 1.20 s. The analysis value of 1.40 s is longer, so the cap of 1.20 s governs. Using Ta = 0.80 s is permitted but more conservative than required, and averaging the two has no code basis.

Seismic Forces: Building Structures

Given SDS = 1g, SD1 = 0.6g, S1 = 0.6g, R = 8, Ie = 1 and T = 1.2 s (T is less than TL), what seismic response coefficient Cs governs under the equivalent lateral force procedure?

  • a.0.0625✓
  • b.0.0938
  • c.0.1000
  • d.0.1250

ASCE 7-16 Section 12.8.1.1: Cs = SDS/(R/Ie) = 0.1250; it need not exceed SD1/[T(R/Ie)] = 0.0625; it may not be less than 0.044 SDS Ie = 0.0440 (nor 0.01); and because S1 is at least 0.6g, not less than 0.5 S1/(R/Ie) = 0.0375. Here the SD1/(T R/Ie) limit governs: Cs = 0.0625. Picking the plateau value without checking the period-dependent cap, or the cap without checking the minimums, are the usual errors.

Seismic Forces: Building Structures

Given SDS = 1.2g, SD1 = 0.5g, S1 = 0.5g, R = 6, Ie = 1 and T = 0.3 s (T is less than TL), what seismic response coefficient Cs governs under the equivalent lateral force procedure?

  • a.0.0528
  • b.0.1600
  • c.0.2000✓
  • d.0.2778

ASCE 7-16 Section 12.8.1.1: Cs = SDS/(R/Ie) = 0.2000; it need not exceed SD1/[T(R/Ie)] = 0.2778; it may not be less than 0.044 SDS Ie = 0.0528 (nor 0.01). Here the basic SDS/(R/Ie) value governs: Cs = 0.2000. Picking the plateau value without checking the period-dependent cap, or the cap without checking the minimums, are the usual errors.

Seismic Forces: Building Structures

Given SDS = 0.9g, SD1 = 0.45g, S1 = 0.45g, R = 5, Ie = 1.25 and T = 0.9 s (T is less than TL), what seismic response coefficient Cs governs under the equivalent lateral force procedure?

  • a.0.0495
  • b.0.1250✓
  • c.0.2250
  • d.0.2812

ASCE 7-16 Section 12.8.1.1: Cs = SDS/(R/Ie) = 0.2250; it need not exceed SD1/[T(R/Ie)] = 0.1250; it may not be less than 0.044 SDS Ie = 0.0495 (nor 0.01). Here the SD1/(T R/Ie) limit governs: Cs = 0.1250. Picking the plateau value without checking the period-dependent cap, or the cap without checking the minimums, are the usual errors.

Seismic Forces: Building Structures

Given SDS = 1.4g, SD1 = 0.7g, S1 = 0.8g, R = 8, Ie = 1 and T = 2.2 s (T is less than TL), what seismic response coefficient Cs governs under the equivalent lateral force procedure?

  • a.0.0398
  • b.0.0493
  • c.0.0616✓
  • d.0.1750

ASCE 7-16 Section 12.8.1.1: Cs = SDS/(R/Ie) = 0.1750; it need not exceed SD1/[T(R/Ie)] = 0.0398; it may not be less than 0.044 SDS Ie = 0.0616 (nor 0.01); and because S1 is at least 0.6g, not less than 0.5 S1/(R/Ie) = 0.0500. Here the minimum governs: Cs = 0.0616. Picking the plateau value without checking the period-dependent cap, or the cap without checking the minimums, are the usual errors.

Seismic Forces: Building Structures

Given SDS = 1g, SD1 = 0.55g, S1 = 0.55g, R = 6.5, Ie = 1.5 and T = 0.25 s (T is less than TL), what seismic response coefficient Cs governs under the equivalent lateral force procedure?

  • a.0.2308✓
  • b.0.2885
  • c.0.3462
  • d.0.5077

ASCE 7-16 Section 12.8.1.1: Cs = SDS/(R/Ie) = 0.2308; it need not exceed SD1/[T(R/Ie)] = 0.5077; it may not be less than 0.044 SDS Ie = 0.0660 (nor 0.01). Here the basic SDS/(R/Ie) value governs: Cs = 0.2308. Picking the plateau value without checking the period-dependent cap, or the cap without checking the minimums, are the usual errors.

Seismic Forces: Building Structures

A building has an effective seismic weight W = 3,200 kips and a governing seismic response coefficient Cs = 0.125. What is the design seismic base shear?

  • a.280 kips
  • b.308 kips
  • c.320 kips
  • d.400 kips✓

ASCE 7-16 Eq. 12.8-1: V = Cs x W = 0.125 x 3,200 = 400 kips. This is a strength-level force; multiplying by 0.7 converts the earthquake effect for allowable stress design load combinations but is not the base shear itself.

Seismic Forces: Building Structures

A building has an effective seismic weight W = 5,400 kips and a governing seismic response coefficient Cs = 0.0962. What is the design seismic base shear?

  • a.364 kips
  • b.519 kips✓
  • c.649 kips
  • d.727 kips

ASCE 7-16 Eq. 12.8-1: V = Cs x W = 0.0962 x 5,400 = 519 kips. This is a strength-level force; multiplying by 0.7 converts the earthquake effect for allowable stress design load combinations but is not the base shear itself.

Seismic Forces: Building Structures

A building has an effective seismic weight W = 880 kips and a governing seismic response coefficient Cs = 0.185. What is the design seismic base shear?

  • a.114 kips
  • b.125 kips
  • c.163 kips✓
  • d.228 kips

ASCE 7-16 Eq. 12.8-1: V = Cs x W = 0.185 x 880 = 163 kips. This is a strength-level force; multiplying by 0.7 converts the earthquake effect for allowable stress design load combinations but is not the base shear itself.

Seismic Forces: Building Structures

Determine the effective seismic weight contributed by a single-story warehouse (storage occupancy). Area = 40,000 sq ft, dead load = 22 psf, and the design includes a storage live load of 250 psf.

  • a.880 kips
  • b.3,380 kips✓
  • c.5,880 kips
  • d.10,880 kips

ASCE 7-16 Section 12.7.2 defines W as dead load plus specific additions: here 25% of the storage live load (0.25 x 250 = 62.5 psf). W = 40,000 x (22 + 62.5) / 1000 = 3,380 kips. Dead load alone (880 kips) leaves out a mass that will really be present during the earthquake.

Seismic Forces: Building Structures

Determine the effective seismic weight contributed by an office floor where a partition allowance is used in design. Area = 15,000 sq ft, dead load = 85 psf, and the design includes office live load of 50 psf.

  • a.1,425 kips✓
  • b.1,575 kips
  • c.1,781 kips
  • d.1,875 kips

ASCE 7-16 Section 12.7.2 defines W as dead load plus specific additions: here the larger of actual partition weight or 10 psf of floor area (10 psf here); ordinary office live load is not included. W = 15,000 x (85 + 10) / 1000 = 1,425 kips. Dead load alone (1,275 kips) leaves out a mass that will really be present during the earthquake.

Seismic Forces: Building Structures

Determine the effective seismic weight contributed by a roof where the flat roof snow load exceeds 30 psf. Area = 20,000 sq ft, dead load = 30 psf, and the design includes a flat roof snow load of 60 psf.

  • a.600 kips
  • b.672 kips
  • c.720 kips
  • d.840 kips✓

ASCE 7-16 Section 12.7.2 defines W as dead load plus specific additions: here 20% of the uniform design snow load (0.20 x 60 = 12 psf) because the flat roof snow load exceeds 30 psf. W = 20,000 x (30 + 12) / 1000 = 840 kips. Dead load alone (600 kips) leaves out a mass that will really be present during the earthquake.

Seismic Forces: Building Structures

A 2-story building has base shear V = 300 kips. Level data — 2nd floor: w = 400 kips at h = 12 ft; roof: w = 300 kips at h = 24 ft. Using the vertical distribution exponent k = 1, what lateral force is applied at the roof?

  • a.129 kips
  • b.150 kips
  • c.180 kips✓
  • d.200 kips

ASCE 7-16 Eqs. 12.8-11 and 12.8-12: Fx = Cvx x V with Cvx = wx hx^k / sum(wi hi^k). The products are 4,800, 7,200 (sum 12,000). Cvx for the roof = 7,200/12,000 = 0.600, so Fx = 0.600 x 300 = 180 kips. Distributing by weight alone ignores height, and an equal split per level ignores both.

Seismic Forces: Building Structures

A 3-story building has base shear V = 500 kips. Level data — 2nd floor: w = 600 kips at h = 12 ft; 3rd floor: w = 600 kips at h = 24 ft; roof: w = 400 kips at h = 36 ft. Using the vertical distribution exponent k = 1, what lateral force is applied at the roof?

  • a.125 kips
  • b.167 kips
  • c.200 kips✓
  • d.250 kips

ASCE 7-16 Eqs. 12.8-11 and 12.8-12: Fx = Cvx x V with Cvx = wx hx^k / sum(wi hi^k). The products are 7,200, 14,400, 14,400 (sum 36,000). Cvx for the roof = 14,400/36,000 = 0.400, so Fx = 0.400 x 500 = 200 kips. Distributing by weight alone ignores height, and an equal split per level ignores both.

Seismic Forces: Building Structures

A 2-story building has base shear V = 240 kips. Level data — 2nd floor: w = 500 kips at h = 14 ft; roof: w = 350 kips at h = 28 ft. Using the vertical distribution exponent k = 1, what lateral force is applied at the 2nd floor?

  • a.67 kips
  • b.80 kips
  • c.100 kips✓
  • d.141 kips

ASCE 7-16 Eqs. 12.8-11 and 12.8-12: Fx = Cvx x V with Cvx = wx hx^k / sum(wi hi^k). The products are 7,000, 9,800 (sum 16,800). Cvx for the 2nd floor = 7,000/16,800 = 0.417, so Fx = 0.417 x 240 = 100 kips. Distributing by weight alone ignores height, and an equal split per level ignores both.

Seismic Forces: Building Structures

A 3-story building has base shear V = 800 kips. Level data — 2nd floor: w = 900 kips at h = 15 ft; 3rd floor: w = 900 kips at h = 30 ft; roof: w = 700 kips at h = 45 ft. Using the vertical distribution exponent k = 1.25, what lateral force is applied at the roof?

  • a.381 kips✓
  • b.400 kips
  • c.457 kips
  • d.476 kips

ASCE 7-16 Eqs. 12.8-11 and 12.8-12: Fx = Cvx x V with Cvx = wx hx^k / sum(wi hi^k). The products are 26,568, 63,189, 81,586 (sum 171,343). Cvx for the roof = 81,586/171,343 = 0.476, so Fx = 0.476 x 800 = 381 kips. Distributing by weight alone ignores height, and an equal split per level ignores both.

Seismic Forces: Building Structures

A 3-story building has base shear V = 420 kips. Level data — 2nd floor: w = 450 kips at h = 10 ft; 3rd floor: w = 450 kips at h = 20 ft; roof: w = 300 kips at h = 30 ft. Using the vertical distribution exponent k = 1, what lateral force is applied at the 3rd floor?

  • a.84 kips
  • b.140 kips
  • c.158 kips
  • d.168 kips✓

ASCE 7-16 Eqs. 12.8-11 and 12.8-12: Fx = Cvx x V with Cvx = wx hx^k / sum(wi hi^k). The products are 4,500, 9,000, 9,000 (sum 22,500). Cvx for the 3rd floor = 9,000/22,500 = 0.400, so Fx = 0.400 x 420 = 168 kips. Distributing by weight alone ignores height, and an equal split per level ignores both.

Seismic Forces: Building Structures

Lateral seismic forces on a 3-story building are 60 kips at level 2, 110 kips at level 3, 150 kips at roof. What is the seismic story shear in the story immediately below level 3?

  • a.110 kips
  • b.260 kips✓
  • c.320 kips
  • d.325 kips

ASCE 7-16 Eq. 12.8-13: the story shear is the sum of the lateral forces at and above that story: 110 + 150 = 260 kips. Using only the force at level 3 (110 kips) omits what is delivered from the levels above, and summing the forces below the story runs the load path backward.

Seismic Forces: Building Structures

Lateral seismic forces on a 4-story building are 45 kips at level 2, 85 kips at level 3, 120 kips at level 4, 150 kips at roof. What is the seismic story shear in the story immediately below level 4?

  • a.120 kips
  • b.270 kips✓
  • c.338 kips
  • d.400 kips

ASCE 7-16 Eq. 12.8-13: the story shear is the sum of the lateral forces at and above that story: 120 + 150 = 270 kips. Using only the force at level 4 (120 kips) omits what is delivered from the levels above, and summing the forces below the story runs the load path backward.

Seismic Forces: Building Structures

Lateral seismic forces on a 2-story building are 80 kips at level 2, 140 kips at roof. What is the seismic story shear in the story immediately below level 2?

  • a.80 kips
  • b.150 kips
  • c.180 kips
  • d.220 kips✓

ASCE 7-16 Eq. 12.8-13: the story shear is the sum of the lateral forces at and above that story: 80 + 140 = 220 kips. Using only the force at level 2 (80 kips) omits what is delivered from the levels above, and summing the forces below the story runs the load path backward.

Seismic Forces: Building Structures

For a diaphragm at level x: the sum of design lateral forces at and above the level is 180 kips, the sum of seismic weights at and above the level is 900 kips, and the weight tributary to the diaphragm is wpx = 450 kips. SDS = 1g, Ie = 1. What is the diaphragm design force Fpx?

  • a.63 kips
  • b.90 kips✓
  • c.112 kips
  • d.180 kips

ASCE 7-16 Eq. 12.10-1: Fpx = (sum Fi / sum wi) x wpx = (180/900) x 450 = 90 kips. Limits (Eqs. 12.10-2 and 12.10-3): minimum 0.2 SDS Ie wpx = 90 kips, maximum 0.4 SDS Ie wpx = 180 kips. Here the calculated value lies between the limits and governs: Fpx = 90 kips. Reporting the unchecked ratio value, or the story force itself, skips the bounds.

Seismic Forces: Building Structures

For a diaphragm at level x: the sum of design lateral forces at and above the level is 520 kips, the sum of seismic weights at and above the level is 2,400 kips, and the weight tributary to the diaphragm is wpx = 800 kips. SDS = 1.2g, Ie = 1. What is the diaphragm design force Fpx?

  • a.192 kips✓
  • b.240 kips
  • c.384 kips
  • d.520 kips

ASCE 7-16 Eq. 12.10-1: Fpx = (sum Fi / sum wi) x wpx = (520/2,400) x 800 = 173 kips. Limits (Eqs. 12.10-2 and 12.10-3): minimum 0.2 SDS Ie wpx = 192 kips, maximum 0.4 SDS Ie wpx = 384 kips. Here the minimum governs: Fpx = 192 kips. Reporting the unchecked ratio value, or the story force itself, skips the bounds.

Seismic Forces: Building Structures

For a diaphragm at level x: the sum of design lateral forces at and above the level is 95 kips, the sum of seismic weights at and above the level is 1,500 kips, and the weight tributary to the diaphragm is wpx = 500 kips. SDS = 1g, Ie = 1. What is the diaphragm design force Fpx?

  • a.32 kips
  • b.70 kips
  • c.95 kips
  • d.100 kips✓

ASCE 7-16 Eq. 12.10-1: Fpx = (sum Fi / sum wi) x wpx = (95/1,500) x 500 = 32 kips. Limits (Eqs. 12.10-2 and 12.10-3): minimum 0.2 SDS Ie wpx = 100 kips, maximum 0.4 SDS Ie wpx = 200 kips. Here the minimum governs: Fpx = 100 kips. Reporting the unchecked ratio value, or the story force itself, skips the bounds.

Seismic Forces: Building Structures

For a diaphragm at level x: the sum of design lateral forces at and above the level is 150 kips, the sum of seismic weights at and above the level is 400 kips, and the weight tributary to the diaphragm is wpx = 400 kips. SDS = 0.9g, Ie = 1.25. What is the diaphragm design force Fpx?

  • a.90 kips
  • b.105 kips
  • c.120 kips
  • d.150 kips✓

ASCE 7-16 Eq. 12.10-1: Fpx = (sum Fi / sum wi) x wpx = (150/400) x 400 = 150 kips. Limits (Eqs. 12.10-2 and 12.10-3): minimum 0.2 SDS Ie wpx = 90 kips, maximum 0.4 SDS Ie wpx = 180 kips. Here the calculated value lies between the limits and governs: Fpx = 150 kips. Reporting the unchecked ratio value, or the story force itself, skips the bounds.

Seismic Forces: Building Structures

For a diaphragm at level x: the sum of design lateral forces at and above the level is 640 kips, the sum of seismic weights at and above the level is 1,600 kips, and the weight tributary to the diaphragm is wpx = 500 kips. SDS = 1.1g, Ie = 1. What is the diaphragm design force Fpx?

  • a.200 kips✓
  • b.220 kips
  • c.250 kips
  • d.640 kips

ASCE 7-16 Eq. 12.10-1: Fpx = (sum Fi / sum wi) x wpx = (640/1,600) x 500 = 200 kips. Limits (Eqs. 12.10-2 and 12.10-3): minimum 0.2 SDS Ie wpx = 110 kips, maximum 0.4 SDS Ie wpx = 220 kips. Here the calculated value lies between the limits and governs: Fpx = 200 kips. Reporting the unchecked ratio value, or the story force itself, skips the bounds.

Seismic Forces: Building Structures

A structural wall weighing 90 psf must be designed for an out-of-plane seismic force. With SDS = 1g and Ie = 1, what is the minimum design force normal to the wall surface?

  • a.18.0 psf
  • b.27.0 psf
  • c.28.8 psf
  • d.36.0 psf✓

ASCE 7-16 Section 12.11.1: Fp = 0.4 SDS Ie x (wall weight) = 0.4 x 1 x 1 x 90 = 36.0 psf, but not less than 10% of the wall weight (9.0 psf). Design force = 36.0 psf. This out-of-plane wall design force is separate from the larger wall anchorage force of Section 12.11.2.

Seismic Forces: Building Structures

A structural wall weighing 75 psf must be designed for an out-of-plane seismic force. With SDS = 1.2g and Ie = 1.25, what is the minimum design force normal to the wall surface?

  • a.22.5 psf
  • b.45.0 psf✓
  • c.56.2 psf
  • d.90.0 psf

ASCE 7-16 Section 12.11.1: Fp = 0.4 SDS Ie x (wall weight) = 0.4 x 1.2 x 1.25 x 75 = 45.0 psf, but not less than 10% of the wall weight (7.5 psf). Design force = 45.0 psf. This out-of-plane wall design force is separate from the larger wall anchorage force of Section 12.11.2.

Seismic Forces: Building Structures

A structural wall weighing 80 psf must be designed for an out-of-plane seismic force. With SDS = 0.15g and Ie = 1, what is the minimum design force normal to the wall surface?

  • a.8.0 psf✓
  • b.10.0 psf
  • c.12.0 psf
  • d.16.0 psf

ASCE 7-16 Section 12.11.1: Fp = 0.4 SDS Ie x (wall weight) = 0.4 x 0.15 x 1 x 80 = 4.8 psf, but not less than 10% of the wall weight (8.0 psf). Design force = 8.0 psf. The 10% floor governs at this low SDS. This out-of-plane wall design force is separate from the larger wall anchorage force of Section 12.11.2.

Seismic Forces: Building Structures

A concrete wall is anchored to a flexible diaphragm spanning 120 ft between the vertical elements that support it in the direction considered. The wall weight tributary to the anchorage is Wp = 900 lb per foot of wall. SDS = 1g and Ie = 1. What is the design anchorage force?

  • a.360 lb/ft
  • b.576 lb/ft
  • c.720 lb/ft✓
  • d.1,080 lb/ft

ASCE 7-16 Section 12.11.2.1: Fp = 0.4 SDS ka Ie Wp. For a flexible diaphragm ka = 1.0 + Lf/100 = 2.20 capped at 2.0. Fp = 0.4 x 1 x 2.00 x 1 x 900 = 720 lb/ft, which exceeds the floor of 0.2 ka Ie Wp = 360 lb/ft. Leaving ka at 1.0 for a flexible diaphragm understates the amplification seen in past tilt-up failures.

Seismic Forces: Building Structures

A concrete wall is anchored to a flexible diaphragm spanning 60 ft between the vertical elements that support it in the direction considered. The wall weight tributary to the anchorage is Wp = 750 lb per foot of wall. SDS = 1.2g and Ie = 1. What is the design anchorage force?

  • a.240 lb/ft
  • b.360 lb/ft
  • c.461 lb/ft
  • d.576 lb/ft✓

ASCE 7-16 Section 12.11.2.1: Fp = 0.4 SDS ka Ie Wp. For a flexible diaphragm ka = 1.0 + Lf/100 = 1.60. Fp = 0.4 x 1.2 x 1.60 x 1 x 750 = 576 lb/ft, which exceeds the floor of 0.2 ka Ie Wp = 240 lb/ft. Leaving ka at 1.0 for a flexible diaphragm understates the amplification seen in past tilt-up failures.

Seismic Forces: Building Structures

A concrete wall is anchored to a flexible diaphragm spanning 200 ft between the vertical elements that support it in the direction considered. The wall weight tributary to the anchorage is Wp = 1100 lb per foot of wall. SDS = 1g and Ie = 1.25. What is the design anchorage force?

  • a.550 lb/ft
  • b.880 lb/ft
  • c.1,100 lb/ft✓
  • d.1,650 lb/ft

ASCE 7-16 Section 12.11.2.1: Fp = 0.4 SDS ka Ie Wp. For a flexible diaphragm ka = 1.0 + Lf/100 = 3.00 capped at 2.0. Fp = 0.4 x 1 x 2.00 x 1.25 x 1100 = 1,100 lb/ft, which exceeds the floor of 0.2 ka Ie Wp = 550 lb/ft. Leaving ka at 1.0 for a flexible diaphragm understates the amplification seen in past tilt-up failures.

Seismic Forces: Building Structures

A concrete wall is anchored to a rigid concrete diaphragm. The wall weight tributary to the anchorage is Wp = 640 lb per foot of wall. SDS = 0.9g and Ie = 1. What is the design anchorage force?

  • a.128 lb/ft
  • b.230 lb/ft✓
  • c.323 lb/ft
  • d.461 lb/ft

ASCE 7-16 Section 12.11.2.1: Fp = 0.4 SDS ka Ie Wp. For a diaphragm that is not flexible ka = 1.0. Fp = 0.4 x 0.9 x 1.00 x 1 x 640 = 230 lb/ft, which exceeds the floor of 0.2 ka Ie Wp = 128 lb/ft. Leaving ka at 1.0 for a flexible diaphragm understates the amplification seen in past tilt-up failures.

Seismic Forces: Building Structures

A concrete wall is anchored to a flexible diaphragm spanning 40 ft between the vertical elements that support it in the direction considered. The wall weight tributary to the anchorage is Wp = 820 lb per foot of wall. SDS = 1.1g and Ie = 1. What is the design anchorage force?

  • a.230 lb/ft
  • b.361 lb/ft
  • c.505 lb/ft✓
  • d.722 lb/ft

ASCE 7-16 Section 12.11.2.1: Fp = 0.4 SDS ka Ie Wp. For a flexible diaphragm ka = 1.0 + Lf/100 = 1.40. Fp = 0.4 x 1.1 x 1.40 x 1 x 820 = 505 lb/ft, which exceeds the floor of 0.2 ka Ie Wp = 230 lb/ft. Leaving ka at 1.0 for a flexible diaphragm understates the amplification seen in past tilt-up failures.

Seismic Forces: Building Structures

A one-story frame is idealized as a single-degree-of-freedom system with a roof weight of 120 kips and a lateral stiffness of 85 kips/in. What is its fundamental period? (g = 386.4 in./s^2)

  • a.0.06 s
  • b.0.38 s✓
  • c.2.63 s
  • d.7.47 s

T = 2 pi sqrt(m/k) with m = W/g = 120/386.4 = 0.311 kip-s^2/in. T = 2 pi sqrt(0.311/85) = 0.38 s. Using weight in place of mass (forgetting g) gives an absurdly long 7.47 s, and 2.63 is the frequency in hertz, not the period.

Seismic Forces: Building Structures

A one-story frame is idealized as a single-degree-of-freedom system with a roof weight of 400 kips and a lateral stiffness of 150 kips/in. What is its fundamental period? (g = 386.4 in./s^2)

  • a.0.08 s
  • b.0.35 s
  • c.0.42 s
  • d.0.52 s✓

T = 2 pi sqrt(m/k) with m = W/g = 400/386.4 = 1.035 kip-s^2/in. T = 2 pi sqrt(1.035/150) = 0.52 s. Using weight in place of mass (forgetting g) gives an absurdly long 10.26 s, and 1.92 is the frequency in hertz, not the period.

Seismic Forces: Building Structures

A one-story frame is idealized as a single-degree-of-freedom system with a roof weight of 60 kips and a lateral stiffness of 20 kips/in. What is its fundamental period? (g = 386.4 in./s^2)

  • a.0.55 s✓
  • b.1.81 s
  • c.1.92 s
  • d.10.88 s

T = 2 pi sqrt(m/k) with m = W/g = 60/386.4 = 0.155 kip-s^2/in. T = 2 pi sqrt(0.155/20) = 0.55 s. Using weight in place of mass (forgetting g) gives an absurdly long 10.88 s, and 1.81 is the frequency in hertz, not the period.

Seismic Forces: Building Structures

A one-story frame is idealized as a single-degree-of-freedom system with a roof weight of 250 kips and a lateral stiffness of 400 kips/in. What is its fundamental period? (g = 386.4 in./s^2)

  • a.0.04 s
  • b.0.20 s
  • c.0.25 s✓
  • d.4.97 s

T = 2 pi sqrt(m/k) with m = W/g = 250/386.4 = 0.647 kip-s^2/in. T = 2 pi sqrt(0.647/400) = 0.25 s. Using weight in place of mass (forgetting g) gives an absurdly long 4.97 s, and 3.96 is the frequency in hertz, not the period.

Seismic Forces: Building Structures

What vertical distribution exponent k applies to a building with a fundamental period T = 1 s?

  • a.0.84
  • b.1.00
  • c.1.25✓
  • d.2.00

ASCE 7-16 Section 12.8.3: k = 1 for T of 0.5 s or less, k = 2 for T of 2.5 s or more, and linear interpolation between: k = 1 + (T - 0.5)/2 = 1 + (1 - 0.5)/2 = 1.25. Using 1.0 gives the straight-line (first-mode) pattern valid only for short periods; 2.0 is the parabolic pattern for long periods.

Seismic Forces: Building Structures

What vertical distribution exponent k applies to a building with a fundamental period T = 1.5 s?

  • a.1.00
  • b.1.50✓
  • c.1.60
  • d.2.00

ASCE 7-16 Section 12.8.3: k = 1 for T of 0.5 s or less, k = 2 for T of 2.5 s or more, and linear interpolation between: k = 1 + (T - 0.5)/2 = 1 + (1.5 - 0.5)/2 = 1.50. Using 1.0 gives the straight-line (first-mode) pattern valid only for short periods; 2.0 is the parabolic pattern for long periods.

Seismic Forces: Building Structures

A long-period building is located where S1 = 0.9g. With SDS = 1.2g, R = 8 and Ie = 1, what is the minimum seismic response coefficient Cs that applies regardless of period?

  • a.0.0100
  • b.0.0300
  • c.0.0528
  • d.0.0563✓

Two floors apply (ASCE 7-16 Eqs. 12.8-5 and 12.8-6): 0.044 SDS Ie = 0.0528 (not less than 0.01), and, because S1 is 0.6g or more, 0.5 S1/(R/Ie) = 0.5 x 0.9/(8/1) = 0.0563. The larger, 0.0563, governs. The near-fault floor exists because long-period pulses can drive demands the 1/T branch would otherwise understate.

Seismic Forces: Building Structures

A long-period building is located where S1 = 0.7g. With SDS = 1g, R = 6 and Ie = 1.5, what is the minimum seismic response coefficient Cs that applies regardless of period?

  • a.0.0100
  • b.0.0467
  • c.0.0660
  • d.0.0875✓

Two floors apply (ASCE 7-16 Eqs. 12.8-5 and 12.8-6): 0.044 SDS Ie = 0.0660 (not less than 0.01), and, because S1 is 0.6g or more, 0.5 S1/(R/Ie) = 0.5 x 0.7/(6/1.5) = 0.0875. The larger, 0.0875, governs. The near-fault floor exists because long-period pulses can drive demands the 1/T branch would otherwise understate.

Seismic Forces: Building Structures

Which item is included in the effective seismic weight W of an office building?

  • a.The full office floor live load
  • b.Operating weight of permanent equipment✓
  • c.The roof live load for maintenance
  • d.Wind pressure on the exterior wall cladding

ASCE 7-16 Section 12.7.2 defines W as dead load plus specified additions, including the total operating weight of permanent equipment. Ordinary floor live load and roof live load are transient and excluded, and wind pressure is a separate load, not a mass.

Seismic Forces: Building Structures

For a storage occupancy, what minimum portion of the floor live load is included in the effective seismic weight?

  • a.100%
  • b.50%
  • c.0%
  • d.25%✓

ASCE 7-16 Section 12.7.2 includes a minimum of 25% of floor live load in storage areas, since stored goods are likely to be present. Exceptions exist where the added weight is 5% or less of the level's weight and for public garages and open parking structures.

Seismic Forces: Building Structures

A roof has a flat roof snow load of 25 psf. How much of the snow load is included in the effective seismic weight?

  • a.None, because the flat roof snow load does not exceed 30 psf✓
  • b.All of it, because snow is a sustained environmental load
  • c.20% of the snow load, because snow is always included
  • d.50% of the snow load, because the roof is not heated

ASCE 7-16 Section 12.7.2 adds 20% of the uniform design snow load only where the flat roof snow load exceeds 30 psf. At 25 psf nothing is added. Including 100% would grossly overstate the mass likely to be on the roof during an earthquake.