Type II — High-PressureQuestion 124 of 240
A technician recovers R-22 with an older recovery unit manufactured before November 15, 1993 from a system holding 250 pounds. What is the required evacuation level?
a.15 inches Hg vacuum
b.10 inches Hg vacuum
c.4 inches Hg vacuum
d.0 inches Hg vacuum
Explanation
Recovery equipment manufactured before November 15, 1993 has lower required evacuation levels. For a high-pressure appliance holding 200 pounds or more, that older equipment must reach 4 inches Hg vacuum. Appliances under 200 pounds with pre-1993 equipment need only 0 inches Hg (atmospheric).
Law Reference: 40 CFR §82.156Practice all 240 questions free — no signup required.
Related questions on this topic
- A technician is certifying to work on R-22 and R-410A air conditioners, supermarket racks, and heat pumps. Which EPA technician type covers high-pressure and very-high-pressure appliances?
- A technician uses recovery equipment manufactured after November 15, 1993 on an R-22 split system that normally holds less than 200 pounds of refrigerant. To what level must the appliance be evacuated during recovery?
- A supermarket rack system holds 350 pounds of R-404A. Using recovery equipment manufactured after November 15, 1993, to what vacuum must the technician evacuate during recovery?
- A technician must recover a large liquid charge from a supermarket rack quickly. Which recovery method moves the most refrigerant in the least time for large systems?
- A technician wants to speed up vapor recovery from an R-410A condensing unit. Which practice will increase recovery speed?
- After replacing a compressor on an R-410A system, a technician needs to remove moisture and noncondensables before charging. Which procedure is the correct way to dehydrate the system?