Type II — High-PressureQuestion 132 of 240

A technician is checking the charge on a system equipped with a thermostatic expansion valve (TXV). Which measurement is the preferred way to verify the charge on a TXV system?

a.Subcooling at the condenser outlet (liquid line)
b.Superheat at the evaporator inlet
c.Suction pressure alone
d.Ambient temperature only

Explanation

On a TXV system, subcooling is the preferred method to check the charge because the valve maintains evaporator superheat fairly constant. Subcooling is the difference between the liquid-line saturation temperature and the actual liquid temperature. Superheat is the main check on fixed-orifice systems rather than TXV systems.

Practice all 240 questions free — no signup required.

Related questions on this topic

Last reviewed: · editorial process

PrepPass Editorial Team · Verified against EPA Section 608 Technician Certification Exam · How we review
Report