Type II — High-PressureQuestion 147 of 240

A technician recovers R-22 from a rooftop unit that holds 150 pounds using equipment made after November 15, 1993. To what vacuum must the system be evacuated during recovery?

a.10 inches Hg vacuum
b.15 inches Hg vacuum
c.4 inches Hg vacuum
d.0 inches Hg

Explanation

Because the unit holds less than 200 pounds and the recovery equipment is post-1993, the required recovery evacuation level is 10 inches Hg vacuum. Units holding 200 pounds or more require 15 inches Hg with post-1993 equipment. The 0 and 4 inches Hg figures apply only to pre-1993 recovery equipment.

Law Reference: 40 CFR §82.156