Chapter 1 of 10

Definitions, Theory and Plans

This area mixes three things: the Article 100 vocabulary that every other rule is written in, the circuit math you are expected to do without hesitation, and the general requirements of Article 110 that apply to every installation. On the Calculations portion the same area becomes Calculations and Theory, where the questions are short formula problems.

Article 100 words the questions are built on

Definition questions look easy and are missed often, because the wrong choices are real terms that sit one step away from the right one. Learn each term together with the term it gets confused with. Ampacity belongs to the conductor. It is the most current a conductor can carry continuously, under its conditions of use, without going over its temperature rating. It is not the rating of the breaker ahead of it. A continuous load is one whose maximum current is expected to last 3 hours or more. Bonded means connected together so there is electrical continuity and conductivity, which is what lets fault current get back to the source and open the overcurrent device. Connecting something to the earth is grounding, a related but separate idea, and the exam likes to offer it as the wrong answer to a bonding question. Two location terms need care. A feeder runs from the service equipment, from the source of a separately derived system, or from another supply source, to the final branch-circuit overcurrent device. So conductors from a transformer secondary to a panelboard are a feeder, not service conductors and not a branch circuit. The service lateral is the underground run between the utility system and the service point. Anything on the premises side of the service point has a different name, and that is the trap. Last, a Class A ground-fault circuit interrupter trips when the imbalance between the ungrounded and grounded conductor currents reaches about 4 to 6 milliamperes. That level protects people, not conductors.

Continuous load
A load whose maximum current is expected to continue for 3 hours or more.
2026 NEC Article 100
Feeder
Conductors between the service equipment or a separately derived source and the final branch-circuit overcurrent device.
2026 NEC Article 100
Class A GFCI
Trips at an imbalance of roughly 4 to 6 milliamperes to protect people.
2026 NEC Article 100

Circuit math you should not have to think about

These questions carry no Code reference. They test three relationships. Ohm's law: current equals voltage divided by resistance, so a 30-ohm element on 240 volts draws 8 amperes. Power: watts equal volts times amperes for a resistive load, so 120 volts at 12 amperes is 1,440 watts. When you know current and resistance, power is current squared times resistance, so 5 amperes through 20 ohms is 500 watts. The usual wrong answer forgets to square the current. Energy is power times time: a 1,500-watt heater running 4 hours uses 6 kilowatt-hours. In a series circuit resistances add and the same current flows through every part. Three resistors of 10, 15 and 25 ohms total 50 ohms, and on 120 volts the current is 2.4 amperes. Each resistor drops its share of the voltage: with 40 ohms and 20 ohms in series on 120 volts, the current is 2 amperes and the 40-ohm resistor drops 80 volts. In parallel, two resistors combine as product over sum, so 20 and 30 ohms give 12 ohms. Equal resistors in parallel divide by their count: three 30-ohm resistors make 10 ohms. A quick check that catches most errors: a parallel total is always smaller than the smallest branch.

Three-phase and transformer currents

Any three-phase current or power question uses the factor 1.732. Line current equals volt-amperes divided by 1.732 times the line voltage. A balanced 45 kVA load at 208 volts draws about 125 amperes, and a 75 kVA transformer with a 208Y/120-volt secondary delivers about 208 amperes. Dividing by the voltage alone, as if the load were single-phase, is the wrong answer that is always on the list. Single-phase is the plain division: a 25 kVA transformer at 240 volts supplies about 104 amperes. Know which quantity changes in each connection. In a wye, line voltage is 1.732 times phase voltage (120 becomes 208) and line current equals phase current. In a delta it reverses: line voltage equals phase voltage and line current is 1.732 times phase current, so 20 amperes of phase current is about 34.6 amperes on the line. True power adds the power factor: 1.732 times 480 volts times 40 amperes times 0.85 is about 28.3 kilowatts. Leave the power factor out and you have computed kVA instead. For a transformer, voltage and current move in opposite directions and the volt-amperes match on both sides. A 480-volt primary and a 120-volt secondary carrying 100 amperes means 25 amperes on the primary.

Voltage drop, with a worked example

Voltage drop is solved with one formula and conductor areas from Chapter 9, Table 8. For single-phase, drop equals 2 times K times current times one-way length, divided by circular mils. For three-phase, replace the 2 with 1.732. The questions give K as 12.9 for copper. On this exam conductors are copper unless the question says otherwise, and exceptions and optional methods are ignored unless the question calls for them. Worked example: a 120-volt single-phase circuit carries 16 amperes 150 feet on 10 AWG copper, which is 10,380 circular mils. Step 1, multiply the top: 2 x 12.9 x 16 x 150 = 61,920. Step 2, divide by the area: 61,920 / 10,380 is about 6.0 volts. Step 3, if a percentage is asked, divide by the circuit voltage: 6.0 / 120 is 5 percent. Dropping the factor of 2 gives 3.0 volts, which will be one of the choices. The formula also runs backward to size a conductor. For 20 amperes over 200 feet at 240 volts held to 3 percent, the allowed drop is 7.2 volts, and the required area is (2 x 12.9 x 20 x 200) / 7.2 = 14,333 circular mils. In Table 8, 10 AWG is too small and 8 AWG, at 16,510 circular mils, is the answer. Remember that the 3 percent branch-circuit figure is a guideline found in an Informational Note, not an enforceable limit.

Conductor area for voltage drop
Circular mil areas come from the conductor properties table, for example 10,380 for 10 AWG and 16,510 for 8 AWG.
2026 NEC Chapter 9, Table 8

Article 110: space, terminations and marking

Working space questions are table look-ups with one habit to build: enter Table 110.26(A)(1) with the voltage to ground, not the line voltage. A 208Y/120-volt panelboard is 120 volts to ground, and that row gives 3 feet of depth whatever is on the other side. A 480Y/277-volt switchboard is in the 151 to 600 volt row, where the depth depends on the condition. A concrete wall counts as a grounded surface, so live parts facing concrete need 3 feet 6 inches. Live parts on both sides need 4 feet. Width is the width of the equipment or 30 inches, whichever is greater, so a 20-inch panelboard still gets 30 inches. The dedicated space above indoor equipment runs to 6 feet above the equipment or to the structural ceiling, whichever is lower. A suspended ceiling is not a structural ceiling. Two more look-ups. At terminations, circuits rated 100 amperes or less use the 60 degrees C basis unless the equipment is listed and marked otherwise, and above 100 amperes the basis is 75 degrees C. On a 4-wire delta system with one winding midpoint grounded, the conductor with the higher voltage to ground is marked orange.

Working space depth
Enter the table with voltage to ground; 0 to 150 volts is 3 ft, and 151 to 600 volts is 3 ft 6 in. against a grounded surface or 4 ft with live parts on both sides.
2026 NEC Table 110.26(A)(1)
Working space width
The width of the equipment or 30 in., whichever is greater.
2026 NEC §110.26(A)(2)
Dedicated electrical space
Extends to 6 ft above the equipment or to the structural ceiling, whichever is lower.
2026 NEC §110.26(E)(1)
Termination temperature
Circuits rated 100 amperes or less are based on the 60 degrees C column unless the equipment is listed and marked otherwise.
2026 NEC §110.14(C)(1)
High-leg marking
The conductor with the higher voltage to ground on a 4-wire delta is identified orange.
2026 NEC §110.15

First load calculations and safe work practice

Load calculations now live in Article 120, and the journeyman questions stay with single steps. Dwelling general lighting is 2 VA per square foot of floor area measured from the outside dimensions, and open porches are not counted, so a 2,400 square foot house with a 300 square foot porch is 4,800 VA. Answers built on 3 VA per square foot are there to catch people working from an older book. For other occupancies, read the unit load from Table 120.42(A): a bank is treated as an office at 1.3 VA per square foot. A warehouse takes the first 12,500 VA at 100 percent and the rest at 50 percent, so 60,000 VA becomes 36,250 VA. Subtract the first block before you halve. Lighting track outside dwellings is 150 VA for every 2 feet or fraction of 2 feet, so 35 feet rounds up to 18 units and 2,700 VA. Four or more fastened-in-place dwelling appliances may be taken at 75 percent of their total nameplate. The neutral load is the maximum unbalanced load, so line-to-line loads add nothing to it. Safety questions are common sense stated precisely. Lockout/tagout exists to prevent unexpected energization or startup during servicing. To prove a circuit is dead, test the meter on a known live source, test the conductors, then test the meter on the live source again.

Dwelling floor area
Measured from outside dimensions and excluding open porches.
2026 NEC §120.5(C)
Warehouse lighting demand
First 12,500 VA at 100 percent and the remainder at 50 percent.
2026 NEC Table 120.45
Lighting track
In other than dwelling units, 150 VA for each 2 ft or fraction of 2 ft.
2026 NEC §120.46(B)
Fastened-in-place appliances
Four or more on the same dwelling feeder or service may be taken at 75 percent.
2026 NEC §120.53
Neutral load
The maximum net calculated load between the neutral and any one ungrounded conductor.
2026 NEC §120.61(A)