Texas Journeyman Electrician Exam — Study Guide
Free, topic-by-topic study notes for the Texas Journeyman Electrician Exam exam. Read a chapter, then practice it.
The exam is open book. The Code book answers every Code question on the exam, but only if you reach the right page in time. This part is about that: a book that is legal to bring, marked so your eye lands on the right line, and a way of working the clock.
1.1 A book PSI will let into the room
PSI's bulletin (updated September 15, 2026) sets these rules for the Code book you bring:
| Allowed | Not allowed |
|---|---|
| Any soft-bound edition of the NEC (questions follow the 2026 edition) | Loose-leaf, spiral-bound or ring-bound copies |
| Highlighting, underlining and notes made before the exam session | Writing, highlighting, underlining or marking the book during the session |
| Permanent index tabs made or supplied by the NEC book's publisher | Homemade, DIY or other non-NEC tabs |
| A non-programmable, silent, battery calculator with no alphabet keyboard and no paper tape | Any added paper: loose, taped, stapled or stuck in |
| The NEC Handbook |
PSI provides an electronic notepad. A candidate who arrives with a book that breaks these rules is offered three choices: test without the book, remove the non-compliant tabs, or forfeit the fee and test another day.
Two practical points follow. First, do all of your marking at home; the pen and highlighter stay outside. Second, check your tabs: if they did not come from the Code book's publisher, take them off before exam day.
1.2 Mark it up before exam day
Highlighting and notes are allowed as long as they are in the book before the session starts. Use that. A marked book turns a search into a glance.
A workable system:
- One colour for numbers you will be asked for (a distance, a percentage, an ampere rating). Highlight the number and the two or three words that say what it applies to.
- A second colour for the words that flip an answer: "not less than", "not more than", "continuous", "dwelling", "other than".
- Mark exceptions as exceptions. PSI says not to use an exception unless the question tells you to. Bracket each one in the margin so you do not read it as the main rule under time pressure.
- Write the next stop in the margin. Where a calculation sends you from one section to a table, write the table number beside the section. Chapter by chapter, this book gives you those chains.
- Write on the table pages which column to use. For ampacity questions the terminal temperature rating picks the column; note that beside the table heading.
Tabs
PSI's bulletin allows permanent index tabs manufactured or provided by the publisher of your Code book, and bars homemade, DIY and non-NEC tabs. A set from any other maker is not on the allowed list: do not put it on. A candidate who arrives with such tabs has to remove them, test without the book, or forfeit the fee and come back another day.
Putting a tab set on well takes about an hour:
- Check every tab against the 2026 contents first. A set printed for an earlier edition carries article numbers that have moved (see section 1.3).
- Start at the back of the book and work forward, so the tabs already placed never hide the page you are looking for.
- Put each tab on the right-hand page where its article or table begins, and step the tabs down the edge in rows so that no tab covers another.
- Press each tab down firmly. The bulletin's word for the tabs it allows is permanent, and it bars any added paper, loose or attached.
- If you have more tabs than patience, place these first: Article 100, Article 110, Article 120, Article 210, Article 215, Article 230, Article 240, Article 250, Article 300, Article 310, Article 314, Article 406, Article 430, Article 500, Article 501, Article 690, Chapter 9 tables. They are the articles this book sends you to most often.
Tabs get you to the article. Your highlighting gets you to the line. You need both.
The list below is where to start. These are the 40 places in the 2026 Code that this book's chapters and practice bank point to most often. That is a measure of this book, taken from its own pages; it does not predict what PSI will ask.
| Open to | What to mark there |
|---|---|
| Article 100 | Continuous load; Feeder; Class A GFCI |
| §110.26 | Working space width; Dedicated electrical space; Headroom |
| Table 110.26(A)(1) | Working space depth; Depth by condition |
| Table 120.45 | Warehouse lighting demand; Lighting demand |
| §120.53 | Fastened-in-place appliances |
| Table 120.55 | Household ranges |
| §120.61 | Neutral load; Neutral reduction threshold; Neutral reduction amount |
| §210.11 | Small-appliance circuits; Laundry circuit; Bathroom circuit |
| §210.20 | Device for continuous load |
| §210.23 | Cord-and-plug limit; Fastened-in-place limit; Circuits over 50 amperes |
| §210.52 | Wall space; Countertop spacing; Countertop height; Garage receptacles |
| §215.4 | Feeder conductor ampacity; Feeder versus small service |
| §215.5 | Feeder overcurrent device |
| §230.24 | Clearance over driveways and streets; Clearance over roofs |
| §230.71 | Two to six disconnects; Maximum number |
| §230.79 | One-family dwelling minimum; Dwelling minimum rating |
| §240.21 | No rounding up on taps; 25-foot tap termination; Transformer tap length; High bay tap minimum |
| §250.52 | Concrete-encased electrode |
| §250.53 | Water pipe must be supplemented; Single rod resistance; Rod spacing |
| Table 250.66 | GEC sizing |
| Table 250.122 | Size by device rating; Grounding conductor size |
| §250.122 | Upsized conductors; Proportional increase; Upper limit |
| §300.6 | Bored holes in wood; Roof decking clearance |
| Table 300.7(A) | Minimum cover |
| §310.15 | Apply both factors; Neutral as current-carrying |
| §314.16 | Device yoke |
| §314.27 | Fan support; Ceiling luminaire box; Wall luminaire on another box; Fan box marking |
| §314.28 | Straight pull; Angle pull |
| §406.9 | Damp-location cover; Wet-location cover; Tub and shower zone |
| §430.22 | Single motor conductor |
| §430.24 | Motor feeder conductor |
| §430.32 | Separate overload device; Will not start; Integral thermal protector |
| Table 430.52(C)(1) | Squirrel-cage maximums; Wound-rotor breaker |
| §430.102 | Controller disconnect; Motor disconnect; One switch for both |
| §430.110 | General rating; Torque motor; Assumed locked-rotor current |
| §500.5 | Class I, Division 1; Ventilation-dependent room; Metal dust |
| §501.15 | Shared seal; Seal fill |
| §690.8 | Conductor ampacity; Parallel modules; Common-return conductor |
| §690.12 | Array boundary; Outside the boundary; Initiation device location |
| Chapter 9, Table 8 | Conductor circular-mil areas for voltage drop |
1.3 What moved in the 2026 edition
If you trained on an earlier edition, or your notes and tabs came from one, these are the moves that matter most on this exam. Each was confirmed on the 2026 page.
| If your old notes say | In the 2026 Code look in |
|---|---|
| Article 220, load calculations | Article 120 |
| Table 300.5, burial cover | Table 300.7(A) |
| 215.2, feeder conductor rating and size | 215.4 |
| 215.3, feeder overcurrent protection | 215.5 |
| "In Sight From" in Article 100 | 110.29 |
| 450.3 and its tables, transformer overcurrent protection | 450.5 and Tables 450.5(A) and 450.5(B) |
The load-calculation move is the big one: every section you knew as 220.xx is now in Article 120, and a 2023 tab set will send you to the wrong place.
1.4 Working the clock
The Knowledge portion gives you 59 items in 130 minutes, about 2.2 minutes each. The Calculations portion gives you 26 items in 110 minutes, about 4.2 minutes each. One question shows at a time, the minutes remaining show at the top of the screen, and PSI's bulletin says you can go back to any question and change your answer while time remains.
That makes a two-pass method possible:
- First pass: answer what you can find quickly. Read the question, pick out the key word, go to the article, answer. If you have not found the rule in about the average time per item, enter your best choice, note the question number on the electronic notepad and move on.
- Second pass: return to your noted questions with the time you saved. A long search on one item now costs you nothing else.
- Last five minutes: make sure nothing is blank.
Three reading habits prevent most wrong answers:
- Find the condition before the number. "Continuous", "dwelling unit", "75 degree C terminals", "aluminum", "more than three current-carrying conductors": each of these changes the table, the column or the multiplier.
- Main rule unless told otherwise. No exceptions and no optional calculation method unless the question names one.
- Copper unless told otherwise.
And one for the calculation portion: write every step on the notepad in the order the chapter gives it. The wrong options are usually the result of skipping a step, so a number that matches an option is not proof that it is right.
1.5 Formula pages
The only reference PSI's bulletin lists for the exam room is your Code book, and it bars any added paper. Notes written in the book before the session are allowed, so the formulas you want at hand can be written on the pages where you will use them, at home, ahead of time.
Circuit formulas (not in the Code; know them cold)
| To find | Formula |
|---|---|
| Voltage, current, resistance | E = I x R; I = E / R; R = E / I |
| Power, single-phase or dc | P = E x I; P = I x I x R; P = (E x E) / R |
| Power, three-phase | P = 1.732 x E x I x power factor |
| Current from volt-amperes, single-phase | I = VA / E |
| Current from volt-amperes, three-phase | I = VA / (1.732 x E) |
| Horsepower to watts | 1 hp = 746 W |
| Efficiency | output / input |
| Percent voltage drop | (volts dropped / circuit voltage) x 100 |
Voltage drop and fault current
| To find | Formula | Open to |
|---|---|---|
| Voltage drop, single-phase | VD = (2 x K x I x L) / circular mils. L is the one-way length in feet; this book's worked examples use K = 12.9 for copper | Chapter 9, Table 8 for the circular-mil area |
| Voltage drop, three-phase | VD = (1.732 x K x I x L) / circular mils | Chapter 9, Table 8 |
| Smallest conductor for a voltage-drop limit | circular mils = (2 x K x I x L) / volts allowed, then the first size in the table with at least that area | Chapter 9, Table 8 |
| Transformer full-load current | VA / E single-phase; VA / (1.732 x E) three-phase | |
| Available fault current at transformer terminals (estimate) | full-load current / impedance as a decimal (2% is 0.02) |
Code calculations: the rule, in our words, and where to read it
Each row is a reminder of a rule this book teaches. Read the Code text at the place named before you rely on it, and write the next stop in the margin there.
Load calculations
| Step or rule | What to do | Open to |
|---|---|---|
| Dwelling floor area | Measured from outside dimensions and excluding open porches. | §120.5(C) |
| Dwelling lighting load | 2 VA per square foot, which also covers general-use receptacles. | §120.41 |
| Lighting track | In other than dwelling units, 150 VA for each 2 ft or fraction of 2 ft. | §120.46(B) |
| Small-appliance and laundry load | 1,500 VA for each required circuit. | §120.52 |
| Fastened-in-place appliances | Four or more on the same dwelling feeder or service may be taken at 75 percent. | §120.53 |
| Dryer load | Use 5,000 VA or the nameplate rating, whichever is larger. | §120.54 |
| Neutral load | The maximum net calculated load between the neutral and any one ungrounded conductor. | §120.61(A) |
| Neutral reduction threshold | For general loads, only the unbalanced load above 200 amperes may be reduced; the range, oven, cooking-unit and dryer portion may be taken at 70 percent under 120.61(B)(1). | §120.61(B) |
| Neutral reduction amount | The portion over 200 amperes is taken at 70 percent. | §120.61(B)(2) |
| Optional method general loads | First 8 kVA at 100 percent and the rest at 40 percent. | §120.82(B) |
Continuous loads: branch circuits, feeders, services
| Step or rule | What to do | Open to |
|---|---|---|
| Conductor for continuous load | Branch-circuit conductors must have an ampacity of at least 125 percent of the continuous load. | §210.19(A)(1) |
| Device for continuous load | Rate the overcurrent device at not less than 125 percent of the continuous load. | §210.20(A) |
| Feeder conductor ampacity | The conductor must carry the noncontinuous load plus 125 percent of the continuous load. | §215.4(A)(1) |
| Feeder versus small service | A feeder carrying the full load of service conductors of 55 amperes or less may not have less ampacity than they do. | §215.4(C) |
| Feeder overcurrent device | Rate the device for the noncontinuous load plus 125 percent of the continuous load, then go to the next standard size. | §215.5 |
| Service conductor ampacity | At least the noncontinuous load plus 125 percent of the continuous load. | §230.42(A)(1) |
Ampacity, adjustment and correction
| Step or rule | What to do | Open to |
|---|---|---|
| Termination temperature | Circuits rated 100 amperes or less are based on the 60 degrees C column unless the equipment is listed and marked otherwise. | §110.14(C)(1) |
| Termination temperature | With 75 degree C terminations the final ampacity comes from the 75 degree C column, even for 90 degree C wire. | §110.14(C)(1)(b) |
| 400-ampere dwelling service | The dwelling table lists 400 kcmil copper. | Table 310.12(A) |
| Adjustment factors | More than three current-carrying conductors: 80 percent for 4 to 6, 70 percent for 7 to 9, 50 percent for 10 to 20. | Table 310.15(C)(1) |
| Apply both factors | Ambient correction and conductor-count adjustment are multiplied together on the table ampacity. | §310.15 |
| Neutral as current-carrying | Count the neutral of a 4-wire wye circuit when most of the load is nonlinear. | §310.15(E) |
| Table ampacity | Read the column that matches the insulation for derating and the termination rating for the final size. | Table 310.16 |
Grounding and bonding sizes
| Step or rule | What to do | Open to |
|---|---|---|
| GEC sizing | Selected by the size of the ungrounded service conductors, with parallel sets added together. | Table 250.66 |
| Cap for rod, pipe or plate | Never required to be larger than 6 AWG copper. | §250.66(A) |
| Cap for concrete-encased electrode | Never required to be larger than 4 AWG copper. | §250.66(B) |
| Bonding jumper table | Main and supply-side bonding jumpers are sized from the ungrounded conductors, and where parallel conductors total more than 1,100 kcmil copper the jumper is at least 12.5 percent of that total area. | Table 250.102(C)(1) |
| Size by device rating | Read the copper column at the row for the overcurrent device ahead of the feeder. | Table 250.122 |
| Upsized conductors | Increase the equipment grounding conductor in proportion to the circular-mil increase of the ungrounded conductors. | §250.122(D) |
| Upper limit | The grounding conductor need not be larger than the circuit conductors. | §250.122(A) |
Box fill and raceway fill
| Step or rule | What to do | Open to |
|---|---|---|
| Volume allowance per conductor | Each conductor takes the volume for its own size: 2.00 cubic inches for 14 AWG, 2.25 for 12 AWG, 2.50 for 10 AWG. | Table 314.16(B)(4) |
| Device yoke | A yoke or strap counts as two allowances based on the largest conductor connected to the device. | §314.16(B)(4) |
| Fill percentages | One conductor may fill 53 percent of the raceway, two may fill 31 percent, and more than two may fill 40 percent. | Chapter 9, Table 1 |
| Short nipple | A nipple 24 inches or shorter between enclosures may be filled to 60 percent. | Chapter 9, Table 1, Note 4 |
| Rounding the conductor count | For conductors all the same size, round up only when the decimal is 0.8 or larger. | Chapter 9, Table 1 and Notes to Tables, Note 7 |
| Conductor area for voltage drop | Circular mil areas come from the conductor properties table, for example 10,380 for 10 AWG and 16,510 for 8 AWG. | Chapter 9, Table 8 |
Motors and air-conditioning equipment
| Step or rule | What to do | Open to |
|---|---|---|
| Table current for wire and protection | Conductors and short-circuit and ground-fault protection are sized from the Code full-load current tables, not from the nameplate. | §430.6(A)(1) |
| Single motor conductor | Ampacity must be at least 125 percent of the table full-load current. | §430.22 |
| Duty-cycle conductor | Intermittent duty with a 15-minute rated motor is sized at 85 percent of nameplate current. | Table 430.22(E) |
| Motor feeder conductor | 125 percent of the highest-rated motor plus the sum of the other full-load currents. | §430.24 |
| Separate overload device | 125 percent of nameplate with a service factor of 1.15 or more or a rise of 40 degrees C or less, otherwise 115 percent. | §430.32(A)(1) |
| Will not start | The overload may be raised to 140 percent for the better-rated motors and 130 percent for all others. | §430.32(C) |
| Integral thermal protector | Trip current is limited to 170, 156 or 140 percent depending on the table full-load current. | §430.32(A)(2) |
| Number of overload units | Three for a three-phase motor, one for a single-phase two-wire motor. | Table 430.37 |
| Squirrel-cage maximums | 175 percent for dual-element fuses, 250 percent for inverse-time breakers, 300 percent for non-time-delay fuses. | Table 430.52(C)(1) |
| Next size up | If the calculated value is not a standard rating, the next higher standard size may be used. | §430.52(C)(1) |
| Motor feeder device | Not more than the largest branch device plus the other full-load currents, rounded down to a standard size. | §430.62(A) |
| Compressor protection | The short-circuit and ground-fault device is sized at no more than 175 percent of rated-load current. | §440.22(A) |
| Manufacturer's maximum values | Where the maximum protective device ratings on the manufacturer's overload relay table for use with a motor controller are lower than the 440.22(A) or (B) value, the device may not exceed those marked values. | §440.22(C) |
| Compressor conductors | Conductors to a single motor-compressor carry at least 125 percent of rated-load or branch-circuit selection current. | §440.32 |
Transformers
| Step or rule | What to do | Open to |
|---|---|---|
| Primary-only protection | With primary current of 9 amperes or more, the primary device may be 125 percent of that current, or the next higher standard rating. | Table 450.5(B) |
Photovoltaic circuits
| Step or rule | What to do | Open to |
|---|---|---|
| Conductor ampacity | Take 125 percent of short-circuit current for maximum current, then 125 percent again for the conductor. | §690.8 |
| Parallel modules | Sum the parallel short-circuit currents, then multiply by 125 percent. | §690.8(A)(1)(a)(1) |
| Common-return conductor | Its ampacity is at least the sum of the individual circuit overcurrent device ratings. | §690.8(C) |
Definitions, Theory and Plans
This area mixes three things: the Article 100 vocabulary that every other rule is written in, the circuit math you are expected to do without hesitation, and the general requirements of Article 110 that apply to every installation. On the Calculations portion the same area becomes Calculations and Theory, where the questions are short formula problems.
Services, Service Equipment and Separately Derived Systems
The service is where utility power becomes your responsibility, and it is the one place in a building where the neutral and the grounding system are deliberately tied together. This area tests two articles almost entirely: Article 230 for the service conductors and disconnects, and Article 250 for grounding and bonding at the service and at transformers. Nearly every question is a number you can look up, so the skill is knowing which section or table holds it.
Electrical Feeders: Sizing, Protection and Load Calculations
A feeder is the set of conductors between the service equipment and the last branch-circuit overcurrent device, so every feeder question comes down to three things: how much load it carries, what protects it, and what size wire that requires. This chapter walks through the feeder rules in the order you would use them on a job, with the 2026 Code sections to tab in your book. Most of the calculation items are short: one factor, one table, one answer.
Branch Circuits and Conductors
Branch circuits are where most of your daily work happens, and the exam covers them from both sides: the rules questions on required circuits, receptacle placement and protection, and the calculation questions on continuous loads, ampacity and voltage drop. This chapter groups the rules by where they sit in the 2026 Code so you can find them fast with the book open.
Wiring Methods and Materials
This area is where the open book pays off, because most of its questions are settled by a table: raceway fill in Chapter 9, box fill in Article 314, burial cover in Article 300. Your job is to know which table answers which question and to run the short arithmetic without slipping. This chapter walks through the rules the journeyman questions draw on most and the wrong answers built around each one.
Electrical Equipment and Devices
Equipment and devices questions ask how the gear at the end of the circuit is protected, where it may be placed and how much room it needs. Most are one-line look-ups in Articles 110, 406, 440 and 450, with a few short calculations for compressors and transformers. Learn where each rule lives and what the standard wrong answers are.
Motors and Generators: Four Numbers for Every Motor Circuit
Almost every motor question on the journeyman exam asks for one of four things: the conductor, the short-circuit and ground-fault device, the overload device, or the feeder. Each one has its own percentage and its own starting current. This chapter shows which current and which percentage belong to each, then finishes with the two generator rules in the bank.
Control Devices and Disconnecting Means: Where It Goes and How Big It Is
Disconnect questions come in two kinds. Location questions ask where the switch must be and what it must be in sight of. Rating questions ask for a minimum ampere value, usually one multiplication. This chapter covers both for motors, air-conditioning equipment, services and detached buildings, with the section to open for each.
Special Occupancies, Equipment and Conditions
This area covers the places where the general wiring rules are not enough: hazardous locations, garages, health care, mobile homes, marinas, pools and emergency systems. Most questions are look-ups of one number in one article, so your job is to know which article owns the topic and which neighbouring number the wrong answers are borrowed from. A few short calculations come from the mobile home and pool rules.
Renewable Energy Technologies: Photovoltaics and EV Chargers
This area covers two articles you will use more every year: electric vehicle charging equipment and photovoltaic systems. The EV questions are mostly single look-ups. The PV questions lean on a small set of multipliers, and the main skill is knowing how many times to apply 125 percent.
Practice by topic
Jump straight into free practice questions for any single Texas Journeyman Electrician Exam topic.

Practice stays free. The full Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) study guide is the material itself, taught start to finish — a downloadable PDF + EPUB you keep.