Which of the following is NOT a standard ampere rating for fuses and inverse-time circuit breakers?
- a.110 amperes
- b.45 amperes
- c.70 amperes
- d.55 amperes✓
The standard ratings listed in 240.6(A) include 45, 50, 60, 70, 80, 90, 100 and 110 amperes, but 55 amperes is not among them. Knowing this list matters because calculated loads are routinely rounded up to the next standard rating, and selecting a size that does not exist is a common exam trap.2026 NEC §240.6(A)
A single receptacle is installed on an individual 20-ampere branch circuit. What is the minimum ampere rating of that receptacle?
- a.20 amperes✓
- b.30 amperes
- c.25 amperes
- d.15 amperes
A single receptacle on an individual branch circuit must have an ampere rating not less than the branch-circuit rating: 20 A. See NEC 210.21(B)(1).2026 NEC §210.21(B)(1)
A hermetic refrigerant motor-compressor has a rated-load current of 20 amperes. What is the maximum branch-circuit short-circuit and ground-fault protective device at the standard 175 percent figure?
- a.60 amperes
- b.25 amperes
- c.45 amperes
- d.35 amperes✓
Protection for a motor-compressor is sized at not more than 175 percent of the rated-load current: 20 x 1.75 = 35 A, which is a standard rating. Where that device still will not carry the starting current it may be increased, but never above 225 percent, which here would be 45 amperes. A 25-ampere device is below the calculated value and would nuisance trip on start.2026 NEC §440.22(A)
A single hermetic refrigerant motor-compressor with a rated-load current of 20 amperes is supplied alone, and no larger branch-circuit selection current is marked. What minimum conductor ampacity is required?
- a.35 amperes
- b.20 amperes
- c.25 amperes✓
- d.30 amperes
Branch-circuit conductors for a single motor-compressor must have an ampacity of at least 125 percent of the rated-load current or the branch-circuit selection current, whichever is greater: 20 x 1.25 = 25 A. The 35-ampere figure is the 175 percent protective device calculation, and 20 amperes omits the required multiplier entirely.2026 NEC §440.32
A 25-kVA, single-phase transformer has a 480-volt primary and is protected by primary overcurrent protection only, sized at 125 percent. With a primary full-load current of 9 amperes or more, what is the maximum standard primary overcurrent device rating?
- a.60 amperes
- b.50 amperes
- c.65 amperes
- d.70 amperes✓
Primary current is 25,000 / 480 = 52.1 amperes, and 52.1 x 1.25 = 65.1 amperes. Because that value is not a standard rating, the next higher standard size of 70 amperes is permitted. 65 amperes is not a standard overcurrent device rating, and 60 amperes would be below the calculated value.2026 NEC Table 450.5(B)
A cord-and-plug-connected room air conditioner is the only load on its branch circuit. Its total rating must not exceed what percentage of the branch-circuit rating?
- a.100 percent
- b.80 percent✓
- c.50 percent
- d.125 percent
Where the room air conditioner is the only load on the circuit, its marked rating may not exceed 80 percent of the branch-circuit rating. If lighting units or other appliances are also supplied by the circuit, that ceiling drops to 50 percent.2026 NEC §440.62(B)
An air-conditioning condensing unit is marked minimum circuit ampacity 28.4 amperes. Using 75 degrees C copper, what is the minimum branch-circuit conductor size?
- a.8 AWG copper
- b.14 AWG copper
- c.10 AWG copper✓
- d.12 AWG copper
The marked minimum circuit ampacity sizes the conductors. In the 75 degrees C column 12 AWG copper (25 A) is too small for 28.4 A and 10 AWG copper (35 A) is adequate. See NEC 440.35, 440.4(B) and Table 310.16.2026 NEC §440.35
A hermetic refrigerant motor-compressor has a rated-load current of 22 amperes. Applying the 175 percent figure and the exception that permits the next higher standard rating, what is the maximum branch-circuit short-circuit and ground-fault protective device?
- a.45 amperes
- b.50 amperes
- c.40 amperes✓
- d.35 amperes
The basic limit is 175 percent of the rated-load current: 22 x 1.75 = 38.5 A, which is not a standard rating. Exception No. 1 to 440.22(A) permits the next higher standard rating, which is 40 A. Without that exception the device could not exceed 38.5 A, so 35 A would be the largest choice. See NEC 440.22(A) and Table 240.6(A).2026 NEC §440.22(A)
A single hermetic refrigerant motor-compressor with a rated-load current of 22 amperes is supplied alone, and no larger branch-circuit selection current is marked. What minimum conductor ampacity is required?
- a.30 amperes
- b.22 amperes
- c.38.5 amperes
- d.27.5 amperes✓
Branch-circuit conductors for a single motor-compressor must be at least 125 percent of the rated-load or branch-circuit selection current: 22 x 1.25 = 27.5 A, which calls for 10 AWG copper. See NEC 440.32.2026 NEC §440.32
A 15-kVA, single-phase transformer has a 480-volt primary and is protected by primary overcurrent protection only at 125 percent. What is the maximum standard primary overcurrent device rating?
- a.35 amperes
- b.45 amperes
- c.40 amperes✓
- d.50 amperes
Primary full-load current = 15,000 / 480 = 31.25 A, and 31.25 x 1.25 = 39.06 A. That is not a standard rating, so the next higher standard rating of 40 A is permitted. See NEC 450.5(B) and Table 450.5(B).2026 NEC Table 450.5(B)
Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
A cord-and-plug-connected room air conditioner shares its branch circuit with lighting outlets. Its total marked rating must not exceed what percentage of the branch-circuit rating?
- a.100 percent
- b.80 percent
- c.50 percent✓
- d.125 percent
Where lighting units or other appliances are also supplied, a room air conditioner may not exceed 50 percent of the branch-circuit rating; if it is the only load, the limit is 80 percent. See NEC 440.62(B) and (C).2026 NEC §440.62(C)
A 45 kVA, three-phase transformer has a 480-volt primary. If only primary overcurrent protection is provided at 125 percent, what is the maximum standard primary device rating?
- a.90 amperes
- b.60 amperes
- c.80 amperes
- d.70 amperes✓
Primary full-load current is 45,000 / (1.732 x 480) = 54.1 A, and 54.1 x 1.25 = 67.6 A. Because the calculated value does not correspond to a standard rating, the next higher standard size of 70 amperes is permitted. The 60-ampere answer rounds down and would nuisance trip, while 80 and 90 amperes skip past the next standard size.2026 NEC Table 450.5(B)
How must a panelboard be protected against overcurrent?
- a.By an overcurrent device rated at 125 percent of the panelboard rating
- b.By the sum of the branch-circuit devices installed in it
- c.By an overcurrent device having a rating not greater than the panelboard rating✓
- d.No separate protection is required if the feeder conductors are properly sized
Each panelboard must be protected by an overcurrent device rated no higher than the panelboard rating, located either in the panelboard itself as a main or ahead of it in the feeder. Summing the branch devices routinely exceeds the panelboard rating because of diversity, and no code rule allows protecting a panelboard at 125 percent of its rating.2026 NEC §408.36
A 30 kVA, three-phase transformer has a 480-volt primary and is protected by primary overcurrent protection only at 125 percent. What is the maximum standard primary overcurrent device rating?
- a.60 amperes
- b.50 amperes✓
- c.45 amperes
- d.40 amperes
Primary full-load current = 30,000 / (1.732 x 480) = 36.1 A, and 36.1 x 1.25 = 45.1 A. Where 125 percent does not land on a standard rating, the next higher standard rating may be used. 45.1 A is above the standard 45-ampere rating, so 50 A is the maximum. See NEC 450.5(B), Table 450.5(B) Note 1 and Table 240.6(A).2026 NEC Table 450.5(B)
A 480-volt panelboard is mounted on a wall with a grounded concrete wall directly behind the working space. What is the minimum depth of working space?
- a.2 and 1/2 feet
- b.3 feet
- c.4 feet
- d.3 and 1/2 feet✓
For nominal voltages of 151 to 600 volts to ground, Condition 2 exists when exposed live parts face a grounded surface such as a concrete or masonry wall, and the required depth is 3 and 1/2 feet. Condition 1, with no live or grounded parts opposite, requires 3 feet, and Condition 3, with exposed live parts on both sides, requires 4 feet.2026 NEC Table 110.26(A)(1)
What is the minimum width of working space in front of electrical equipment?
- a.30 inches in all cases regardless of equipment width
- b.30 inches, or the width of the equipment, whichever is greater✓
- c.36 inches, or the width of the equipment, whichever is greater
- d.24 inches, measured from the centerline of the equipment
The working space in front of the equipment must be at least 30 inches wide or as wide as the equipment, whichever is greater, and it must let equipment doors and hinged panels open at least 90 degrees. See NEC 110.26(A)(2).2026 NEC §110.26(A)(2)
Entrances at each end of the working space are generally required for equipment rated at least what value and over 6 feet wide?
- a.1,000 amperes
- b.800 amperes
- c.1,200 amperes✓
- d.600 amperes
Large equipment rated 1,200 amperes or more and over 6 feet wide that contains overcurrent, switching or control devices needs an entrance to and egress from the working space at each end, so a worker is not trapped behind a fault. See NEC 110.26(C)(2). The 800-ampere figure belongs to the separate personnel door rule in 110.26(C)(3).2026 NEC §110.26(C)(2)
The dedicated equipment space above a panelboard extends from the top of the equipment to what height?
- a.It extends all the way up to the structural ceiling in every case, with no allowance to stop at any lower height
- b.It extends only 3 feet above the top of the equipment in all cases, regardless of the height of the structural ceiling
- c.6 feet above the equipment or to the structural ceiling, whichever is lower✓
- d.6 and 1/2 feet above the finished floor
The dedicated space is the footprint of the equipment extended from the floor to a height of 6 feet above the equipment or to the structural ceiling, whichever is lower, and no foreign piping, ducts or equipment may be installed in it. Suspended ceilings with removable panels are not considered structural ceilings, and the 6 and 1/2-foot dimension is the minimum headroom of working space, a separate requirement.2026 NEC §110.26(E)(1)
A 480-volt panelboard is mounted so there are no live or grounded parts opposite the working space. What is the minimum required depth of working space?
- a.3 feet✓
- b.3 and 1/2 feet
- c.2 and 1/2 feet
- d.4 feet
For 151 to 600 volts to ground, Condition 1 (no live or grounded parts opposite) requires 3 feet of depth. Condition 2 requires 3 and 1/2 feet and Condition 3 requires 4 feet. See NEC 110.26(A)(1).2026 NEC Table 110.26(A)(1)
A 480-volt panelboard has exposed energized parts on both sides of the working space. What is the minimum required depth of working space?
- a.3 feet
- b.5 feet
- c.4 feet✓
- d.3 and 1/2 feet
For 151 to 600 volts to ground, Condition 3, with exposed live parts on both sides of the working space, requires a depth of 4 feet. See NEC 110.26(A)(1).2026 NEC Table 110.26(A)(1)
What is the minimum headroom of the working space about electrical equipment such as panelboards?
- a.6 and 1/2 feet✓
- b.3 feet
- c.7 and 1/2 feet
- d.6 feet
The minimum headroom of working space is 6 and 1/2 feet, or the height of the equipment if taller. See NEC 110.26(A)(3).2026 NEC §110.26(A)(3)
Working spaces about service equipment, switchboards, panelboards or motor control centers installed indoors must be provided with what?
- a.A dedicated telephone
- b.Illumination✓
- c.A portable fire extinguisher
- d.A rubber grounding mat
Indoor working spaces about service equipment, switchboards, panelboards and motor control centers must have illumination. See NEC 110.26(D).2026 NEC §110.26(D)
A 15-ampere, 125-volt receptacle is installed outdoors in a wet location. What type of cover is required?
- a.Any weatherproof cover, effective only when the receptacle is unused
- b.A standard thermoplastic wall plate
- c.A cover that is weatherproof only when no plug is inserted
- d.A cover that is weatherproof whether or not an attachment plug is inserted✓
Receptacles in wet locations must have an enclosure that is weatherproof whether or not an attachment plug is inserted, commonly an in-use or bubble cover, because cords are often left plugged in outdoors. A cover that seals only when empty meets the lesser damp-location standard, not the wet-location rule.2026 NEC §406.9(B)(1)
In a dwelling unit, 125-volt and 250-volt, 15- and 20-ampere receptacles must generally be what type?
- a.Isolated-ground type
- b.Listed tamper-resistant type✓
- c.Hospital-grade type
- d.Twist-lock type
To prevent children from inserting objects into energized slots, these receptacles in dwelling units must be listed tamper-resistant. Hospital-grade and isolated-ground receptacles address other concerns and are not the general dwelling requirement.2026 NEC §406.26
A 15-ampere, 125-volt receptacle is installed in a damp location such as under a roofed open porch. What cover is required?
- a.A cover that is weatherproof when no attachment plug is inserted✓
- b.A cover that is weatherproof whether or not a plug is inserted
- c.No cover is required in a damp location
- d.A standard indoor wall plate
In damp locations a receptacle needs an enclosure that is weatherproof when the cover is closed and no plug is inserted. The stricter in-use cover, weatherproof with a plug inserted, is required in wet locations. See 2026 NEC 406.9(A)(1) and 406.9(B)(1).2026 NEC §406.9(A)(1)
Receptacles installed outdoors in wet or damp locations must be which listed type?
- a.Twist-lock
- b.Weather-resistant✓
- c.Hospital-grade
- d.Isolated-ground
Nonlocking 125- and 250-volt receptacles installed in damp or wet locations must be the listed weather-resistant type. See 2026 NEC 406.9(A)(1) and 406.9(B)(1).2026 NEC §406.9(A)(1) and §406.9(B)(1)
Receptacles are not permitted inside a tub or shower space or within a zone around it. Measured from the outside edge of a bathtub and from the top of the tub rim, how far does that zone extend?
- a.2 ft horizontally and 6 ft vertically
- b.5 ft horizontally and 8 ft vertically
- c.6 ft horizontally and 7 ft vertically
- d.3 ft horizontally and 8 ft vertically✓
Section 406.9(C)(1) keeps receptacles out of the tub or shower space and out of a zone that reaches 3 ft horizontally from the outside edge of the tub or shower and 8 ft vertically above the tub rim or shower threshold. The zone takes in the space directly over the tub or shower as well. The other pairs of numbers do not appear in this rule.2026 NEC §406.9(C)(1)
A receptacle has screwless push-in terminals. On which conductors and circuits may those terminals be used?
- a.14 AWG solid copper on circuits rated 15 A or less✓
- b.12 AWG solid copper on circuits up to 20 A
- c.14 AWG stranded copper on 15-A circuits
- d.12 AWG copper-clad aluminum on 20-A circuits
Section 406.10 limits screwless push-in terminals on receptacles to circuits of 15 amperes or less and to 14 AWG solid copper conductors only. A 12 AWG conductor on a 20-A circuit has to go under a screw or pressure-plate terminal instead. Stranded wire and aluminum are both outside what the push-in terminal is allowed to take.2026 NEC §406.10
How is a receptacle with an isolated grounding conductor connection, installed to reduce electromagnetic interference, required to be identified?
- a.A green dot on the face of the receptacle
- b.A red faceplate over the outlet box
- c.The letters IG stamped on the yoke
- d.An orange triangle on the face of the receptacle✓
Section 406.11(C) requires an isolated ground receptacle to be identified by an orange triangle on the face of the receptacle. The mark has to be on the device face, so a colored faceplate or a mark on the yoke hidden behind the plate does not meet the rule. A green dot is not the isolated ground marking.2026 NEC §406.11(C)
A two-wire nongrounding receptacle on a circuit with no equipment grounding conductor is replaced with a GFCI-type receptacle. What marking is required on the GFCI receptacle or its cover plate?
- a.GFCI Protected Outlet
- b.No Equipment Ground✓
- c.Ungrounded Circuit Only
- d.Two-Wire Supply Only
Section 406.12(D)(2) allows a nongrounding receptacle to be replaced with a GFCI-type receptacle where there is no equipment grounding conductor in the box, and the receptacle or its cover plate must be marked to show there is no equipment ground. An equipment grounding conductor must not be run from that GFCI receptacle to any outlet it supplies. The marking tells the user that the grounding slot is not connected to ground.2026 NEC §406.12(D)(2)
Arc-fault circuit-interrupter and ground-fault circuit-interrupter type receptacles must be installed in a location that is:
- a.Accessible behind a fixed appliance
- b.Within sight of the panelboard
- c.At least 12 in. above the floor
- d.Readily accessible✓
Section 406.12(D) requires AFCI-type and GFCI-type receptacles to be installed in a readily accessible location, so that the test and reset buttons can be reached without moving anything or using a ladder. A device behind a fixed appliance does not meet that. The rule sets no mounting height and no line of sight to the panelboard.2026 NEC §406.12(D)
A box used at a ceiling luminaire outlet must be designed so a luminaire can be attached, and it must be able to support a luminaire weighing at least:
- a.6 lb
- b.35 lb
- c.50 lb✓
- d.70 lb
Section 314.27(A)(2) requires boxes at ceiling luminaire outlets to support a luminaire weighing at least 50 lb. A heavier luminaire needs support independent of the box unless the box is listed for the weight. The 35 lb and 70 lb figures belong to the ceiling fan rule, and 6 lb is the limit for a wall luminaire hung on a box that is not a luminaire box.2026 NEC §314.27(A)(2)
A wall-mounted luminaire is to be supported on a box that is not designed for luminaire support. This is permitted if the luminaire is secured to the box with at least two No. 6 or larger screws and weighs not more than:
- a.6 lb✓
- b.15 lb
- c.35 lb
- d.50 lb
Section 314.27(A)(1) allows a wall-mounted luminaire or lampholder weighing not more than 6 lb to be supported on other boxes, such as a device box, when it is secured with no fewer than two No. 6 or larger screws. The 50 lb figure is the weight a box designed for luminaires is expected to carry, so it does not apply to an ordinary device box.2026 NEC §314.27(A)(1)
The mounting screws that came with a listed receptacle are lost. What may be used instead to attach the receptacle to the box?
- a.Sheet metal screws with 18 threads per inch
- b.Drywall screws at least 1-1/4 in. long
- c.Machine screws with 32 threads per inch✓
- d.Self-tapping screws with 24 threads per inch
Section 406.14 requires the screws that attach a receptacle to a box to be the type supplied with the listed receptacle, or machine screws having 32 threads per inch. Machine screws of that thread match the tapped holes in the box. Drywall and sheet metal screws cut their own coarse thread and damage those holes.2026 NEC §406.14
A 62-lb chandelier will hang below a standard ceiling outlet box. The box is not listed for more than the minimum weight required of a ceiling luminaire box. How must the chandelier be supported?
- a.Supported independently of the ceiling outlet box✓
- b.Hung from the box with two No. 6 screws
- c.Hung from any listed ceiling outlet box
- d.Supported by the raceway entering the box
A ceiling luminaire box only has to carry 50 lb. Under 314.27(A)(2), a luminaire over 50 lb must be supported independently of the outlet box unless the box is listed for at least the weight to be supported. At 62 lb and with a box not listed for that weight, the chandelier needs its own support from the structure. Two No. 6 screws are the method for a wall luminaire of 6 lb or less.2026 NEC §314.27(A)(2)
An old house has two-wire circuits with no equipment grounding conductor. An electrician installs a GFCI receptacle at the first outlet and replaces three downstream nongrounding receptacles with ordinary grounding-type receptacles fed from its load side. What must be marked on the three downstream receptacles or their cover plates?
- a."GFCI Protected" only
- b."No Equipment Ground" only
- c."Isolated Ground" and "GFCI Protected"
- d."GFCI Protected" and "No Equipment Ground"✓
Section 406.12(D)(2) allows nongrounding receptacles to be replaced with grounding-type receptacles where they are supplied through a GFCI, and those receptacles or their cover plates must carry both markings: that they are GFCI protected and that there is no equipment ground. No equipment grounding conductor is connected between them. The single marking about no equipment ground is for the GFCI receptacle itself, not for the grounding-type receptacles it feeds.2026 NEC §406.12(D)(2)
A 45-lb ceiling-suspended paddle fan will be supported only by the outlet box. Which box meets the requirement?
- a.One listed for luminaire support at 50 lb, with no fan marking
- b.Any metal octagon box fastened to a joist with two wood screws
- c.One listed for fan support, with no weight marking on the box
- d.One listed for fan support and marked with the maximum weight it supports✓
Section 314.27(B)(1) requires a box used as the sole support of a ceiling fan to be listed for that use, and a box that supports a fan weighing more than 35 lb must also be marked with the maximum weight it can support. At 45 lb the fan is over 35 lb, so the weight marking is required. A luminaire box rated 50 lb is not listed for the moving load of a fan.2026 NEC §314.27(B)(1)