25 questions

Renewable Energy Technologies

A photovoltaic source circuit uses modules with a rated short-circuit current of 10 amperes. What minimum conductor ampacity is required before any temperature or conduit-fill adjustments?

  • a.12.5 amperes
  • b.15.6 amperes✓
  • c.10 amperes
  • d.20 amperes

The maximum circuit current is 125 percent of the rated short-circuit current, or 10 x 1.25 = 12.5 A, and the conductor must then be sized at 125 percent of that value without adjustment factors: 12.5 x 1.25 = 15.6 A. The 12.5-ampere answer stops after only the first multiplier, and 10 amperes ignores both.2026 NEC §690.8

Renewable Energy Technologies

A photovoltaic source circuit uses modules with a rated short-circuit current of 8 amperes. What minimum conductor ampacity is required before any adjustment factors?

  • a.15.6 amperes
  • b.12.5 amperes✓
  • c.8 amperes
  • d.10 amperes

The maximum circuit current is 125 percent of the rated short-circuit current: 8 x 1.25 = 10 A, and the conductor is then sized at 125 percent of that value: 10 x 1.25 = 12.5 A. See NEC 690.8(A) and (B).2026 NEC §690.8

Renewable Energy Technologies

What is the highest PV system dc circuit voltage permitted on or in a one- or two-family dwelling?

  • a.600 V✓
  • b.1000 V
  • c.1500 V
  • d.2000 V

PV dc circuits on or in one- and two-family dwellings are limited to 600 V. The 1000 V figure is the limit for arrays on or attached to other buildings and for PV dc circuits inside buildings, so it is too high for a dwelling. The larger values are not limits this section gives for building-mounted systems. See 690.7.2026 NEC §690.7

Renewable Energy Technologies

PV system dc circuits on a building need dc arc-fault circuit protection when they operate at or above what voltage between any two conductors?

  • a.30 V dc
  • b.50 V dc
  • c.80 V dc✓
  • d.120 V dc

PV dc circuits operating at 80 V dc or more between any two conductors must be protected by a listed PV arc-fault circuit interrupter or equivalent listed components. 30 V is a rapid shutdown limit, not the arc-fault threshold, and 50 V and 120 V do not appear in this rule. See 690.11.2026 NEC §690.11

Renewable Energy Technologies

A PV source circuit has 12 crystalline silicon modules in series, each with a rated open-circuit voltage of 40 V. The lowest expected ambient temperature is -8°C. Using the Code's voltage correction table, what is the maximum PV source circuit voltage?

  • a.480 V
  • b.537.6 V
  • c.547.2 V✓
  • d.556.8 V

For crystalline silicon modules, the maximum voltage is the sum of the series modules' rated open-circuit voltages multiplied by the cold-temperature factor from the table. Twelve modules at 40 V give 480 V, and the factor for the -6 to -10°C band is 1.14, so 480 x 1.14 = 547.2 V. The 480 V answer skips the correction, and the other two use the factors from the bands on either side (1.12 and 1.16). See 690.7(A) and Table 690.7(A).2026 NEC Table 690.7(A)

Renewable Energy Technologies

After rapid shutdown is initiated, controlled conductors located outside the array boundary must be limited to what level?

  • a.Not more than 30 volts within 30 seconds✓
  • b.Not more than 80 volts within 30 seconds
  • c.Not more than 30 volts within 10 seconds
  • d.Not more than 80 volts within 10 seconds

Outside the array boundary, or more than 1 m (3 ft) from where the conductors enter the building, controlled conductors must drop to 30 volts or less within 30 seconds of initiation. The 80 volt figure belongs to conductors inside the array boundary. The 10 second answers use a time that this rule does not give. See 690.12(B)(1).2026 NEC §690.12(B)(1)

Renewable Energy Technologies

For rapid shutdown purposes, how far from the array in all directions does the array boundary extend?

  • a.150 mm (6 in.)
  • b.305 mm (1 ft)✓
  • c.1 m (3 ft)
  • d.3 m (10 ft)

The array boundary is set at 305 mm (1 ft) from the array in every direction. The 1 m (3 ft) figure is a different measurement in the same rule, the distance from the point of entry inside a building, and is a common mix-up. The 6 in. and 10 ft values are not used here. See 690.12(B).2026 NEC §690.12(B)

Renewable Energy Technologies

Three PV modules are connected in parallel in one PV source circuit. Each module has a highest short-circuit current rating of 12 A. Using the 125% method, what is the maximum current of this PV source circuit?

  • a.15 A
  • b.36 A
  • c.45 A✓
  • d.56.25 A

Under the 125% method, the maximum current is the sum of the parallel modules' short-circuit current ratings multiplied by 125%. Here 3 x 12 A = 36 A, and 36 A x 1.25 = 45 A. 36 A leaves out the 125%, 15 A applies it to only one module, and 56.25 A applies it twice. See 690.8(A)(1)(a)(1).2026 NEC §690.8(A)(1)(a)(1)

Renewable Energy Technologies

A rooftop PV system is installed on a one-family dwelling. Where must the rapid shutdown initiation device be located?

  • a.Inside the dwelling at the main panelboard
  • b.In the attic next to the inverter
  • c.On the roof inside the array boundary
  • d.At a readily accessible outdoor location✓

Initiation devices must be readily accessible, and for one- and two-family dwellings they must be at an outdoor location so firefighters can reach them without entering. A device inside at the panelboard or in the attic is not outdoors, and one on the roof is not readily accessible. See 690.12(C)(1).2026 NEC §690.12(C)(1)

Renewable Energy Technologies

On the building label that shows where the rapid shutdown initiation devices are, what is the minimum height of the capitalized title letters?

  • a.9.5 mm (3/8 in.)✓
  • b.13 mm (1/2 in.)
  • c.19 mm (3/4 in.)
  • d.25 mm (1 in.)

The title on the rapid shutdown label must be in capital letters at least 9.5 mm (3/8 in.) high, with legible text that contrasts with the background. The larger sizes are more than the rule asks for and are not the stated minimum. See 690.12(D).2026 NEC §690.12(D)

Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Renewable Energy Technologies

Which marking, or its equivalent, must be permanently placed on each PV system disconnecting means?

  • a.SOLAR MAIN BREAKER
  • b.INVERTER OUTPUT CIRCUIT
  • c.RAPID SHUTDOWN SWITCH
  • d.PV SYSTEM DISCONNECT✓

Each PV system disconnecting means must be permanently marked to identify it as the PV system disconnect, using that wording or an equivalent. The rapid shutdown switch wording belongs on the label for the rapid shutdown switch, which is a separate requirement. The other two phrases are not markings this section calls for. See 690.13(C).2026 NEC §690.13(C)

Renewable Energy Technologies

In which location is PV system equipment and its disconnecting means not permitted to be installed?

  • a.Attics
  • b.Garages
  • c.Basements
  • d.Bathrooms✓

PV system equipment and disconnecting means may not be installed in bathrooms. This section does not name attics, garages, or basements as prohibited locations, and it separately allows power converters to be mounted in areas that are not readily accessible. See 690.4(D).2026 NEC §690.4(D)

Renewable Energy Technologies

A PV circuit has a maximum current of 16 A calculated under 690.8(A). The overcurrent device is not part of an assembly listed for continuous operation at 100% of its rating. Before rounding up to a standard size, what is the minimum overcurrent device rating?

  • a.12.8 A
  • b.16 A
  • c.20 A✓
  • d.25 A

A PV overcurrent device that is not in a 100% rated assembly must be rated at least 125% of the maximum current. 16 A x 1.25 = 20 A. 16 A would be right only for a 100% rated assembly, 12.8 A applies 80% in the wrong direction, and 25 A applies the 125% twice. See 690.9(B)(1).2026 NEC §690.9(B)(1)

Renewable Energy Technologies

A calculation made under Article 690 produces a result of 12.4. Using the rounding that the article permits, what value may be used?

  • a.12✓
  • b.12.5
  • c.13
  • d.15

Article 690 calculations may be rounded to the nearest whole number, and a fraction smaller than 0.5 may be dropped. Since 0.4 is less than 0.5, 12.4 becomes 12. Rounding up to 13 would apply only at 0.5 or more, and 12.5 and 15 are not whole-number rounding at all. See 690.4(G).2026 NEC §690.4(G)

Renewable Energy Technologies

For applying Article 690, the output of an ac module is treated as which type of circuit?

  • a.A PV source circuit
  • b.A PV dc circuit
  • c.A dc-to-dc converter circuit
  • d.An inverter output circuit✓

An ac module has its inverter built in, so its output is treated as an inverter output circuit. The PV source circuit rules do not apply to ac modules, and the other two answers are dc circuits that an ac module does not present to the installer. See 690.6(A) and 690.6(B).2026 NEC §690.6(B)

Renewable Energy Technologies

Three PV circuits share a common-return conductor. The individual circuits are protected by overcurrent devices rated 15 A, 15 A, and 20 A. What is the minimum ampacity of the common-return conductor?

  • a.35 A
  • b.50 A✓
  • c.62.5 A
  • d.78.1 A

A common-return conductor must have an ampacity at least equal to the sum of the overcurrent device ratings of the individual circuits. 15 A + 15 A + 20 A = 50 A. 35 A leaves one circuit out, and 62.5 A and 78.1 A add 125% multipliers that this rule does not require. See 690.8(C).2026 NEC §690.8(C)

Renewable Energy Technologies

Equipment that interconnects a power production source so it runs in parallel with the primary source must meet which requirement?

  • a.Be rated at 125% of the service rating
  • b.Be approved by the utility in place of listing
  • c.Be listed or field labeled for the interactive function✓
  • d.Be marked as suitable for stand-alone use only

Interconnection and interactive equipment must be listed for the interactive function, or be evaluated for that function and carry a field label, or both. Utility approval does not replace this, and equipment for stand-alone use only is not intended to run in parallel with another source. The 125% answer borrows a sizing idea that has nothing to do with listing. See 705.2.2026 NEC §705.2

Renewable Energy Technologies

An outlet supplying EVSE must be on an individual branch circuit when the EVSE is rated more than 120 volts or more than how many amperes?

  • a.16 A✓
  • b.20 A
  • c.24 A
  • d.30 A

Each outlet that supplies EVSE rated above 16 amperes or above 120 volts needs its own individual branch circuit. The higher values would let larger chargers share a circuit, which the rule does not allow unless a load management arrangement covered elsewhere in the article is used. See 625.40.2026 NEC §625.40

Renewable Energy Technologies

For sizing the supply circuit, how does the Code classify EVSE loads?

  • a.Continuous loads✓
  • b.Noncontinuous loads
  • c.Intermittent loads
  • d.Optional standby loads

EVSE and wireless power transfer equipment, including bidirectional equipment, are treated as continuous loads. That is why the circuit is sized with the continuous load rules instead of at 100% of the charger current. The other answers would undersize the circuit or describe a different kind of system. See 625.41.2026 NEC §625.41

Renewable Energy Technologies

A cord-and-plug-connected EVSE has a maximum rating of 24 A. What is the minimum ampere rating of its attachment plug?

  • a.24 A
  • b.30 A✓
  • c.37.5 A
  • d.48 A

Cord-and-plug-connected electric vehicle equipment needs an attachment plug rated at least 125% of the equipment's maximum rating. 24 A x 1.25 = 30 A. 24 A ignores the 125%, 37.5 A applies it twice, and 48 A doubles the rating. See 625.44.2026 NEC §625.44

Renewable Energy Technologies

Unless the listed EVSE has a cable management system, what is the maximum overall usable length of the output cable to the electric vehicle?

  • a.3.7 m (12 ft)
  • b.4.6 m (15 ft)
  • c.7.5 m (25 ft)✓
  • d.15 m (50 ft)

The overall usable length of the output cable is limited to 7.5 m (25 ft) unless a cable management system that is part of the listed equipment is provided. The 15 ft figure is a limit for a power-supply cord arrangement, not the output cable, and 12 ft and 50 ft are not in this rule. See 625.17(C).2026 NEC §625.17(C)

Renewable Energy Technologies

Fixed EVSE that is not specifically listed and marked for its location is installed outdoors. What is the minimum height above grade for storing the coupling means?

  • a.300 mm (12 in.)
  • b.450 mm (18 in.)
  • c.600 mm (24 in.)✓
  • d.900 mm (36 in.)

Unless the equipment is specifically listed and marked for the location, the coupling means must be stored at least 600 mm (24 in.) above grade outdoors. The 450 mm (18 in.) figure is the indoor height above the floor, which is the usual mix-up. The other two values are not in the rule. See 625.50.2026 NEC §625.50

Renewable Energy Technologies

Which receptacles installed for connecting electric vehicle charging equipment need GFCI protection for personnel?

  • a.Only 125-volt, 15- and 20-ampere receptacles
  • b.Only receptacles located outdoors
  • c.Only receptacles in dwelling unit garages
  • d.All receptacles installed for EV charging✓

Every receptacle installed for the connection of electric vehicle charging must have ground-fault circuit-interrupter protection for personnel. The rule is not limited by voltage, ampere rating, or location, so each of the narrower answers leaves some charging receptacles unprotected. See 625.54.2026 NEC §625.54

Renewable Energy Technologies

An indoor charging area has EVSE listed for vehicles that require ventilation. Three vehicles can charge at the same time, each from a 208 V single-phase, 40 A branch circuit. The table gives 171 cfm per vehicle for that rating. What is the minimum total ventilation?

  • a.171 cfm
  • b.296 cfm
  • c.342 cfm
  • d.513 cfm✓

The table value applies to each vehicle that can be charged at one time, so the per-vehicle figure is multiplied by the number of vehicles. 3 x 171 cfm = 513 cfm. 171 cfm covers only one vehicle, 342 cfm covers two, and 296 cfm is the per-vehicle figure from the 208 V three-phase column. See 625.52(B)(1) and Table 625.52(B)(1)(2).2026 NEC Table 625.52(B)(1)(2)

Renewable Energy Technologies

An installer wants to put a 50-ampere receptacle for cord-and-plug-connected EVSE on a 40-ampere branch circuit, as the general receptacle rating table referenced in 210.24 would otherwise allow. What does Article 625 say?

  • a.Permitted where the EVSE draws 32 A or less
  • b.Permitted only at one-family dwellings
  • c.Permitted where GFCI protection is added
  • d.Not permitted for EVSE receptacles✓

Article 625 overrides the general table for this case: a 50-ampere receptacle for EVSE may not go on a 40-ampere branch circuit. The rule has no allowance based on charger current, occupancy type, or added GFCI protection. See 625.44.2026 NEC §625.44