What is the line current of a balanced 45 kVA, three-phase, 208-volt load?
- a.216 amperes
- b.125 amperes✓
- c.72 amperes
- d.144 amperes
For a three-phase load, I = VA / (1.732 x E) = 45,000 / (1.732 x 208) = 45,000 / 360.3, or about 125 A. The 216-ampere answer divides by the voltage alone as if the load were single-phase, 72 amperes divides by three times the voltage, and 144 amperes does not follow from the formula.
A 120-volt single-phase circuit carries 16 amperes 150 feet on 10 AWG copper (10,380 circular mils). Using K = 12.9, what is the approximate voltage drop?
- a.3.0 volts
- b.12.0 volts
- c.6.0 volts✓
- d.9.0 volts
Single-phase VD = (2 x K x I x L) / CM = (2 x 12.9 x 16 x 150) / 10,380 = 61,920 / 10,380, about 6.0 V. Omitting the factor of 2 gives the 3.0-V trap. See NEC Chapter 9, Table 8.2026 NEC Chapter 9, Table 8
A 480-volt three-phase feeder carries 30 amperes 300 feet on 4 AWG copper (41,740 circular mils). Using K = 12.9, what is the approximate voltage drop?
- a.4.8 volts✓
- b.9.6 volts
- c.5.6 volts
- d.2.8 volts
Three-phase VD = (1.732 x K x I x L) / CM = (1.732 x 12.9 x 30 x 300) / 41,740, about 4.8 V. Using 2 instead of 1.732 gives the 5.6-V answer. See NEC Chapter 9, Table 8.2026 NEC Chapter 9, Table 8
A 240-volt circuit must carry 20 amperes 200 feet with voltage drop held to 3 percent. Using K = 12.9 for copper, what is the smallest conductor that meets the target?
- a.6 AWG
- b.10 AWG
- c.8 AWG✓
- d.12 AWG
Three percent of 240 V is 7.2 V, so required area = (2 x 12.9 x 20 x 200) / 7.2 = 103,200 / 7.2 = 14,333 circular mils. From Chapter 9, Table 8, 10 AWG (10,380 cmil) fails and 8 AWG (16,510 cmil) meets it. Voltage-drop sizing is advisory per the Informational Notes to NEC 210.19 and 215.4.2026 NEC Chapter 9, Table 8
A 120-volt branch circuit shows a measured voltage drop of 4.8 volts. What is the percentage voltage drop?
- a.4 percent✓
- b.5 percent
- c.3 percent
- d.2 percent
Percentage voltage drop is the volts dropped divided by the circuit voltage: 4.8 / 120 = 0.04, or 4 percent. The 5 percent answer divides by 96 instead of 120, and 3 or 2 percent understate the measured drop.
What is the secondary full-load current of a 75 kVA transformer with a 208Y/120-volt, three-phase secondary?
- a.120 amperes
- b.361 amperes
- c.208 amperes✓
- d.104 amperes
Secondary current is I = VA / (1.732 x E) = 75,000 / (1.732 x 208) = 75,000 / 360.3, or about 208 amperes. The 361-ampere answer divides by the voltage alone, 120 amperes uses the phase voltage incorrectly, and 104 amperes is roughly half the correct value.
How is the load on a feeder or service neutral (grounded) conductor determined?
- a.By the maximum unbalanced load, the maximum net current between the neutral and any one ungrounded conductor✓
- b.By the sum of all ungrounded conductor currents
- c.It is always the same size as the ungrounded conductors
- d.By taking 125 percent of the load on the largest single ungrounded conductor and applying that resulting value to the neutral conductor
The neutral carries only the imbalance among the ungrounded conductors, so its calculated load is the maximum unbalanced load: the maximum net calculated load between the neutral and any one ungrounded conductor. Loads connected line to line, such as 240-volt appliances with no neutral connection, add nothing to the neutral.2026 NEC §120.61(A)
What is the secondary full-load current of a 112.5 kVA transformer with a 208Y/120-volt three-phase secondary?
- a.541 amperes
- b.312 amperes✓
- c.270 amperes
- d.156 amperes
Secondary current = VA / (1.732 x E) = 112,500 / (1.732 x 208) = 112,500 / 360.3, about 312 amperes. Dividing by voltage alone gives the 541-ampere trap.
A heating element of 30 ohms is connected across 240 volts. What current flows?
- a.8 amperes✓
- b.0.125 ampere
- c.7,200 amperes
- d.12 amperes
Ohm's law gives I = E / R = 240 / 30 = 8 amperes. The 0.125-ampere answer inverts the division, 7,200 multiplies voltage by resistance instead of dividing, and 12 amperes would require a 20-ohm element.
What power is consumed by a 120-volt load drawing 12 amperes at unity power factor?
- a.1,440 watts✓
- b.10 watts
- c.132 watts
- d.1,200 watts
Power in a resistive single-phase circuit is P = E x I = 120 x 12 = 1,440 watts. The 10-watt answer divides instead of multiplying, 132 watts adds the two values, and 1,200 watts does not follow from the given numbers.
Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
How much power is dissipated when 5 amperes flows through a 20-ohm resistor?
- a.100 watts
- b.500 watts✓
- c.4 watts
- d.2,000 watts
Using P = I squared x R, the calculation is 5 x 5 x 20 = 500 watts. The 100-watt answer multiplies current by resistance without squaring the current, 4 watts divides the wrong way, and 2,000 watts squares the resistance instead of the current.
Three resistors of 10, 15 and 25 ohms are connected in series across 120 volts. What is the circuit current?
- a.24 amperes
- b.2.4 amperes✓
- c.4.8 amperes
- d.0.42 ampere
Series resistances add: 10 + 15 + 25 = 50 ohms, so I = 120 / 50 = 2.4 amperes. The 24-ampere answer misplaces the decimal, 4.8 amperes would result from a 25-ohm total, and 0.42 ampere inverts the division.
A 20-ohm resistor and a 30-ohm resistor are connected in parallel. What is the total resistance?
- a.50 ohms
- b.12 ohms✓
- c.25 ohms
- d.10 ohms
For two resistors in parallel, R total = (R1 x R2) / (R1 + R2) = (20 x 30) / 50 = 600 / 50 = 12 ohms. The 50-ohm answer adds them as if they were in series, and 25 ohms averages them, but total parallel resistance is always less than the smallest branch resistance.
A balanced three-phase load draws 40 amperes at 480 volts with a power factor of 0.85. What is the true power?
- a.Approximately 33.3 kilowatts
- b.Approximately 28.3 kilowatts✓
- c.Approximately 19.2 kilowatts
- d.Approximately 16.3 kilowatts
True power for a three-phase load is P = 1.732 x E x I x PF = 1.732 x 480 x 40 x 0.85, or about 28,270 watts. The 33.3-kilowatt answer omits the power factor and gives apparent power in kVA instead, 19.2 kilowatts leaves out the 1.732 factor, and 16.3 kilowatts omits both.
On a 208Y/120-volt wye system, what is the relationship between line voltage and phase voltage?
- a.Line voltage equals phase voltage divided by 1.732
- b.Line voltage equals phase voltage
- c.Line voltage equals phase voltage multiplied by 3
- d.Line voltage equals phase voltage multiplied by 1.732✓
In a wye configuration the line voltage is the square root of three times the phase voltage: 120 x 1.732 = 208 volts, while line current equals phase current. In a delta configuration the relationship reverses, with line voltage equal to phase voltage and line current equal to 1.732 times phase current.
A balanced delta-connected load has a phase current of 20 amperes. What is the line current?
- a.20 amperes
- b.Approximately 34.6 amperes✓
- c.Approximately 11.5 amperes
- d.60 amperes
In a delta connection each line conductor feeds two phase windings, so line current equals 1.732 times phase current: 20 x 1.732 = 34.6 amperes. The 20-ampere answer describes a wye connection, 11.5 amperes divides instead of multiplying, and 60 amperes triples the value rather than applying the square root of three.
A single-phase transformer has a 480-volt primary and a 120-volt secondary. If the secondary carries 100 amperes, what is the approximate primary current?
- a.50 amperes
- b.100 amperes
- c.400 amperes
- d.25 amperes✓
Voltage and current transform inversely, so the 4 to 1 voltage ratio produces a 1 to 4 current ratio: 100 / 4 = 25 amperes on the primary. Neglecting losses, the volt-amperes match on both sides, 480 x 25 = 120 x 100 = 12,000 VA. The 400-ampere answer inverts the ratio and would represent an impossible power gain.
What is the secondary full-load current of a 25 kVA single-phase transformer with a 240-volt secondary?
- a.Approximately 60 amperes
- b.Approximately 104 amperes✓
- c.Approximately 208 amperes
- d.Approximately 52 amperes
For a single-phase transformer, I = VA / E = 25,000 / 240, or about 104 amperes. The 60-ampere answer wrongly applies the three-phase formula (25,000 / (1.732 x 240)), 208 amperes divides by 120 volts, and 52 amperes divides by 480 volts, which is half the correct value.
Which sequence correctly describes verifying that equipment is de-energized before beginning work?
- a.Test the meter on a known live source, test the de-energized conductors, then retest the meter on the known live source✓
- b.Test the de-energized conductors, then test the meter on a known live source
- c.Rely on the open position of the disconnect and the applied lock
- d.Test the de-energized conductors only, since the meter was checked at the start of the shift
The live-dead-live method proves the instrument is working both before and after the absence-of-voltage test, so a meter that failed during the check cannot lead a worker to treat energized conductors as safe. Locking and tagging the disconnect is required, but it does not by itself confirm that the conductors ahead of the work are actually de-energized, since backfeeds and mislabeled circuits are common.
As defined in Article 100, ampacity is best described as which of the following?
- a.The maximum current a conductor can carry continuously under the conditions of use without exceeding its temperature rating✓
- b.The current that will instantly melt the conductor
- c.The rated current of the overcurrent device protecting the conductor, taken directly from the marking on the breaker or fuse without regard to installation conditions
- d.The current at which voltage drop reaches 3 percent
Ampacity is the most current a conductor can carry continuously, under the conditions of use, without going over its temperature rating (NEC Article 100). It belongs to the conductor and its installation conditions, not to the rating of the breaker or fuse ahead of it.2026 NEC Article 100
Under the Article 100 definitions, what does it mean for metal parts to be bonded?
- a.Connected to the earth through a ground rod
- b.Insulated from all other metal parts
- c.Connected together to establish electrical continuity and conductivity✓
- d.Painted to prevent corrosion
Bonding means connecting parts together to establish electrical continuity and conductivity, which is what allows fault current to return to the source and open the overcurrent device. Connecting a part to the earth is grounding, a related but distinct concept.2026 NEC Article 100
Three 30-ohm resistors are connected in parallel. What is the total resistance?
- a.90 ohms
- b.10 ohms✓
- c.30 ohms
- d.15 ohms
For equal resistors in parallel, total resistance equals the value of one resistor divided by the number of resistors: 30 / 3 = 10 ohms. The 90-ohm answer adds them as if in series, and total parallel resistance is always less than the smallest branch.
How much energy does a 1,500-watt electric heater consume when operated continuously for 4 hours?
- a.375 watt-hours
- b.1.5 kilowatt-hours
- c.600 watt-hours
- d.6 kilowatt-hours✓
Energy equals power multiplied by time: 1,500 watts x 4 hours = 6,000 watt-hours, or 6 kilowatt-hours. The 1.5-kilowatt-hour answer reports only the power rating, and 375 watt-hours divides instead of multiplying.
A 40-ohm resistor and a 20-ohm resistor are connected in series across a 120-volt source. What is the voltage drop across the 40-ohm resistor?
- a.80 volts✓
- b.40 volts
- c.60 volts
- d.48 volts
In series the total resistance is 40 + 20 = 60 ohms, so the current is 120 / 60 = 2 amperes. The drop across the 40-ohm resistor is 2 x 40 = 80 volts, and the remaining 40 volts appears across the 20-ohm resistor, confirming the two drops sum to the source voltage.
A heating element of 10 ohms is connected across 120 volts. What current flows?
- a.1,200 amperes
- b.10 amperes
- c.12 amperes✓
- d.0.083 ampere
Ohm's law gives I = E / R = 120 / 10 = 12 amperes. Inverting the division gives the 0.083-ampere trap, and multiplying gives 1,200.
What power is consumed by a 240-volt resistive load drawing 15 amperes?
- a.16 watts
- b.3,000 watts
- c.255 watts
- d.3,600 watts✓
Power in a resistive single-phase circuit is P = E x I = 240 x 15 = 3,600 watts. Dividing gives 16 and adding gives 255.
How much power is dissipated when 6 amperes flows through a 25-ohm resistor?
- a.150 watts
- b.6.25 watts
- c.3,600 watts
- d.900 watts✓
Using P = I squared x R = 6 x 6 x 25 = 900 watts. Multiplying current by resistance without squaring gives 150 watts.
Three resistors of 5, 10 and 20 ohms are connected in series across 105 volts. What is the circuit current?
- a.0.33 ampere
- b.6 amperes
- c.30 amperes
- d.3 amperes✓
Series resistances add: 5 + 10 + 20 = 35 ohms, so I = 105 / 35 = 3 amperes.
A 10-ohm resistor and a 40-ohm resistor are connected in parallel. What is the total resistance?
- a.4 ohms
- b.8 ohms✓
- c.25 ohms
- d.50 ohms
For two resistors in parallel, R = (R1 x R2) / (R1 + R2) = (10 x 40) / 50 = 400 / 50 = 8 ohms. Total parallel resistance is always less than the smallest branch.
Three 60-ohm resistors are connected in parallel. What is the total resistance?
- a.30 ohms
- b.180 ohms
- c.20 ohms✓
- d.60 ohms
For equal resistors in parallel, total resistance equals one value divided by the number of resistors: 60 / 3 = 20 ohms. Adding them gives the 180-ohm series answer.
A balanced three-phase load draws 30 amperes at 208 volts with a power factor of 0.90. What is the true power?
- a.Approximately 6.2 kilowatts
- b.Approximately 10.8 kilowatts
- c.Approximately 5.6 kilowatts
- d.Approximately 9.7 kilowatts✓
True power = 1.732 x E x I x PF = 1.732 x 208 x 30 x 0.90, about 9,730 watts. Omitting the power factor gives about 10.8 kVA of apparent power.
On a 208Y/120-volt wye system, what is the relationship between line current and phase current?
- a.Line current equals phase current divided by 1.732
- b.Line current equals 3 times phase current
- c.Line current equals 1.732 times phase current
- d.Line current equals phase current✓
In a wye configuration the line current equals the phase current, while the line voltage is 1.732 times the phase voltage. In a delta configuration those relationships reverse.
A single-phase transformer has a 240-volt primary and a 48-volt secondary. If the secondary carries 50 amperes, what is the approximate primary current?
- a.5 amperes
- b.10 amperes✓
- c.50 amperes
- d.250 amperes
Voltage and current transform inversely and the volt-amperes match: 240 x I = 48 x 50, so I = 2,400 / 240 = 10 amperes. Inverting the ratio gives the 250-ampere trap.
What is the secondary full-load current of a 15 kVA single-phase transformer with a 240-volt secondary?
- a.62.5 amperes✓
- b.125 amperes
- c.31 amperes
- d.104 amperes
For a single-phase transformer, I = VA / E = 15,000 / 240 = 62.5 amperes.
How much energy does a 2,000-watt load consume when operated continuously for 3 hours?
- a.666 watt-hours
- b.2 kilowatt-hours
- c.6 kilowatt-hours✓
- d.0.67 kilowatt-hour
Energy equals power multiplied by time: 2,000 watts x 3 hours = 6,000 watt-hours, or 6 kilowatt-hours.
A 30-ohm resistor and a 60-ohm resistor are connected in series across a 90-volt source. What is the voltage drop across the 60-ohm resistor?
- a.60 volts✓
- b.30 volts
- c.90 volts
- d.45 volts
Total resistance is 30 + 60 = 90 ohms, so the current is 90 / 90 = 1 ampere. The drop across the 60-ohm resistor is 1 x 60 = 60 volts, and 30 volts appears across the 30-ohm resistor.
Article 100 defines a continuous load as one where the maximum current is expected to continue for how long?
- a.More than 24 hours
- b.Any duration over 100 amperes
- c.Only at night
- d.3 hours or more✓
A continuous load is one where the maximum current is expected to continue for 3 hours or more. See NEC Article 100.2026 NEC Article 100
What is the primary purpose of a lockout/tagout procedure?
- a.To improve the power factor of the circuit
- b.To increase the available fault current
- c.To reduce conductor voltage drop
- d.To prevent the unexpected energization or startup of equipment during servicing✓
Lockout/tagout keeps a disconnecting means in the open position so equipment cannot be unexpectedly energized or started while a worker is servicing it. This reflects OSHA 1910.147 and NFPA 70E safe-work practice.
A Class A ground-fault circuit interrupter is designed to trip when the difference between the ungrounded and grounded conductor currents reaches approximately what value?
- a.100 milliamperes
- b.20 amperes
- c.4 to 6 milliamperes✓
- d.1 ampere
A Class A GFCI trips when the ground-fault (imbalance) current reaches 4 to 6 milliamperes, the level intended to protect people from electrocution, not to protect the circuit conductors.2026 NEC Article 100
A 208Y/120-volt panelboard (120 volts to ground) has exposed live parts on both sides of the working space. What is the minimum depth of the working space?
- a.2 ft 6 in.
- b.3 ft✓
- c.3 ft 6 in.
- d.4 ft
Table 110.26(A)(1) gives one depth for the 0 to 150 volts-to-ground row no matter which condition applies, so live parts on both sides still need only 3 ft. The 3 ft 6 in. and 4 ft answers are the Condition 2 and Condition 3 depths from the 151 to 600 volt row, which does not apply at 120 volts to ground.2026 NEC Table 110.26(A)(1)
Exposed live parts of a 480Y/277-volt switchboard are on one side of the working space and a concrete wall is on the other side. What is the minimum depth of the working space?
- a.2 ft
- b.3 ft
- c.3 ft 6 in.✓
- d.4 ft
The table is entered with the voltage to ground, which is 277 volts, so the 151 to 600 volt row applies. A concrete wall is treated as a grounded surface, which makes this Condition 2 and a depth of 3 ft 6 in. The 3 ft answer treats the wall as ungrounded (Condition 1) and 4 ft is the depth for live parts on both sides.2026 NEC Table 110.26(A)(1)
A panelboard enclosure is 20 in. wide. What is the minimum width of the working space in front of it?
- a.24 in.
- b.30 in.✓
- c.36 in.
- d.42 in.
Section 110.26(A)(2) sets the width of the working space at the width of the equipment or 30 in., whichever is greater. A 20 in. panelboard is narrower than 30 in., so 30 in. governs. The 24 in. figure is the minimum entrance width for large equipment, not a working space width.2026 NEC §110.26(A)(2)
An indoor panelboard has its top 6 ft above the floor. A suspended ceiling is 9 ft above the floor and the structural ceiling is 14 ft above the floor. The dedicated electrical space above the panelboard extends up to what height?
- a.9 ft above the floor, at the suspended ceiling
- b.12 ft above the floor✓
- c.14 ft above the floor, at the structural ceiling
- d.6 ft 6 in. above the floor, the working space height
Section 110.26(E)(1)(a) runs the dedicated space from the floor to 6 ft above the equipment or to the structural ceiling, whichever is lower. Six feet above a 6 ft top is 12 ft, which is below the 14 ft structural ceiling, so 12 ft governs. A suspended ceiling is not a structural ceiling, and 6 1/2 ft is the working space height, a different rule.2026 NEC §110.26(E)(1)
Unless the equipment is listed and marked otherwise, conductor ampacity at equipment terminations is based on the 60 degrees C column for circuits rated up to and including what value?
- a.60 amperes
- b.100 amperes✓
- c.200 amperes
- d.400 amperes
Section 110.14(C)(1)(a) uses the 60 degrees C basis for terminations of circuits rated 100 amperes or less, or marked for 14 AWG through 1 AWG conductors. Above 100 amperes, 110.14(C)(1)(b) moves to the 75 degrees C basis. The 60 ampere answer mixes up the temperature with the current rating.2026 NEC §110.14(C)(1)
On a 4-wire, delta-connected system where the midpoint of one phase winding is grounded, the conductor with the higher voltage to ground must be durably and permanently marked with what color?
- a.Orange✓
- b.Purple
- c.Yellow
- d.Red
Section 110.15 requires the high leg to be durably marked orange, by an outer finish or by other effective means that leave orange visible at all splices and terminations, at each point where a connection is made if the grounded conductor is also present. The other colors are common field choices for phase conductors but are not the color this section names.2026 NEC §110.15
Conductors run from the secondary of a transformer that is the source of a separately derived system to a panelboard, where they end at the final branch-circuit overcurrent devices. Under Article 100, these conductors are which of the following?
- a.A feeder✓
- b.A branch circuit
- c.Service conductors
- d.Service-entrance conductors
Article 100 defines a feeder as the circuit conductors between the service equipment, the source of a separately derived system, or another power supply source and the final branch-circuit overcurrent device. A branch circuit starts at that final device and runs to the outlets. Service conductors run from the service point to the service disconnecting means, so they cannot originate at a premises transformer.2026 NEC Article 100
Under Article 100, the underground conductors between the utility electric supply system and the service point are which of the following?
- a.Underground service conductors
- b.Service-entrance conductors
- c.The service lateral✓
- d.The service drop
Article 100 defines the service lateral as the underground conductors between the utility supply system and the service point. Underground service conductors begin at the service point and run toward the premises, and the service drop is the overhead counterpart of the lateral. The trap is choosing a term that sits on the premises side of the service point.2026 NEC Article 100
A one-family dwelling measures 2,400 sq ft from the outside dimensions of the house. It also has a 300 sq ft open porch. At 2 VA per sq ft, what is the general lighting load before demand factors?
- a.4,800 VA✓
- b.5,400 VA
- c.7,200 VA
- d.8,100 VA
Dwelling floor area is taken from the outside dimensions and does not include open porches, so only the 2,400 sq ft counts: 2,400 x 2 = 4,800 VA. The 5,400 VA answer adds the porch. The two highest answers use a unit load of 3 VA per sq ft, which is not the value on the 2026 page. See 120.5(C) and 120.41.2026 NEC §120.5(C)
A warehouse has 50,000 sq ft of floor area. Using 1.2 VA per sq ft from Table 120.42(A) and the warehouse demand factors in Table 120.45, what is the net general lighting load?
- a.30,000 VA
- b.36,250 VA✓
- c.42,500 VA
- d.60,000 VA
Working: 50,000 x 1.2 = 60,000 VA. For warehouses the first 12,500 VA is taken at 100 percent and the remainder at 50 percent: 12,500 + (47,500 x 0.5) = 12,500 + 23,750 = 36,250 VA. The 30,000 VA answer halves the whole load, 42,500 VA fails to subtract the first 12,500 VA before halving, and 60,000 VA applies no demand factor. See Table 120.42(A) and Table 120.45.2026 NEC Table 120.45
A bank has 5,000 sq ft of floor area. Using the unit loads in Table 120.42(A), what is the general lighting load?
- a.6,000 VA
- b.6,500 VA✓
- c.7,500 VA
- d.9,500 VA
The table footnote places banks in the office occupancy type, which has a unit load of 1.3 VA per sq ft: 5,000 x 1.3 = 6,500 VA. The other answers use the unit loads for a different occupancy, such as 1.2, 1.5 or the 1.9 retail value. See Table 120.42(A).2026 NEC Table 120.42(A)