444 questions

Special Occupancies, Equipment, and Conditions

Shore power for boats must be supplied by single receptacles rated not less than:

  • a.30 amperes✓
  • b.15 amperes
  • c.20 amperes
  • d.50 amperes

Shore power must come from single receptacles rated at least 30 amperes. The 15 and 20 ampere ratings are for the general-purpose receptacles on the pier, not for shore power, and 50 amperes is permitted but is not the minimum. See 555.33(A)(4).2026 NEC §555.33(A)(4)

Special Occupancies, Equipment, and Conditions

An outlet for pool equipment is on a branch circuit operating above 150 volts to ground and not over 480 volts phase to phase. Where ground-fault protection is required, the special purpose GFCI may have a trip current of not more than:

  • a.20 mA✓
  • b.4 mA
  • c.5 mA
  • d.6 mA

Above 150 volts to ground a Class A device cannot be used, so the Code calls for a special purpose GFCI with a trip current of 20 mA or less. The lower values relate to ordinary personnel protection devices on circuits of 150 volts or less to ground. See 680.5(C).2026 NEC §680.5(C)

Special Occupancies, Equipment, and Conditions

An electric pool water heater with resistance elements must have its elements subdivided into loads of not more than:

  • a.30 amperes, protected at not over 40 amperes
  • b.60 amperes, protected at not over 80 amperes
  • c.80 amperes, protected at not over 100 amperes
  • d.48 amperes, protected at not over 60 amperes✓

Resistance pool heaters have their elements split into loads of 48 amperes or less, each protected at 60 amperes or less. The other pairs use numbers that are not in the rule. See 680.10(A)(1).2026 NEC §680.10(A)(1)

Special Occupancies, Equipment, and Conditions

At an indoor pool, a totally enclosed luminaire is on a GFCI-protected branch circuit. What is the lowest height above the maximum water level at which it may be installed over the pool?

  • a.5 ft
  • b.10 ft
  • c.7 ft 6 in.✓
  • d.12 ft

Indoors, a totally enclosed luminaire on a GFCI-protected circuit may come down to 7 ft 6 in. above the maximum water level. Twelve feet is the general clearance that applies without this allowance, and 5 ft is the figure used for existing luminaires and horizontal zones. See 680.22(B)(2).2026 NEC §680.22(B)(2)

Special Occupancies, Equipment, and Conditions

A wall-mounted underwater pool luminaire that is not listed for a lesser depth must have the top of its lens at least how far below the normal water level?

  • a.4 in.
  • b.6 in.
  • c.8 in.
  • d.18 in.✓

Unless the luminaire is listed and identified for shallower use, the top of the lens goes at least 18 in. below the normal water level. Four inches is the absolute floor that applies even to luminaires listed for lesser depths, so it is not the answer for an ordinary luminaire. See 680.23(A)(5).2026 NEC §680.23(A)(5)

Special Occupancies, Equipment, and Conditions

A wet-niche pool luminaire is supplied by a flexible cord. The equipment grounding conductor in the cord must be at least as large as the supply conductors and not smaller than:

  • a.18 AWG
  • b.14 AWG
  • c.16 AWG✓
  • d.12 AWG

The cord's insulated copper equipment grounding conductor must match the supply conductors in size and may not be smaller than 16 AWG. The 12 AWG minimum belongs to the branch-circuit equipment grounding conductor run to the luminaire, not to the cord. See 680.23(B)(3).2026 NEC §680.23(B)(3)

Special Occupancies, Equipment, and Conditions

A pool junction box has three conduit entries, each run extending directly to a forming shell. What is the fewest grounding terminals the box may have?

  • a.Four✓
  • b.Three
  • c.Five
  • d.Six

The box needs at least one more grounding terminal than it has conduit entries, so three entries call for four terminals. Three terminals forgets the extra one, and the larger counts are more than the minimum. See 680.24(D)(1).2026 NEC §680.24(D)(1)

Special Occupancies, Equipment, and Conditions

For a conductive pool shell, the perimeter surface bonding must be attached to the pool reinforcing steel or copper conductor grid at a minimum of how many uniformly spaced points?

  • a.Two points
  • b.Four points✓
  • c.Six points
  • d.Eight points

Perimeter bonding ties to the pool steel or grid at no fewer than four points spaced evenly around the pool. Two points is too few, and six or eight exceed the minimum. See 680.26(B)(2).2026 NEC §680.26(B)(2)

Special Occupancies, Equipment, and Conditions

Where no boxes or enclosures are encountered, exposed emergency circuit cable or raceway must be permanently marked as part of an emergency system at intervals of not more than:

  • a.50 ft
  • b.100 ft
  • c.25 ft✓
  • d.200 ft

Exposed emergency cable or raceway with no boxes along it must be marked at least every 25 ft so it can be recognized as emergency wiring. The longer spacings would leave too much unmarked run. See 700.10(A).2026 NEC §700.10(A)

Special Occupancies, Equipment, and Conditions

Storage batteries used to supply emergency illumination must be able to carry the total load for at least:

  • a.30 minutes
  • b.2 hours
  • c.4 hours
  • d.1 1/2 hours✓

Batteries and UPS equipment feeding emergency illumination must hold the full load for at least 1 1/2 hours. Two hours is the general minimum for other emergency power sources, which is the usual mix-up. See 700.12(B)(4).2026 NEC §700.12(B)(4)

Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Special Occupancies, Equipment, and Conditions

Which type of transfer equipment is not permitted to be used for an emergency system?

  • a.Bypass-isolation transfer switches
  • b.Meter-mounted transfer switches✓
  • c.Electrically operated transfer switches
  • d.Mechanically held transfer switches

Meter-mounted transfer switches may not be used on emergency systems. Automatic transfer switches for emergency use are in fact required to be electrically operated and mechanically held, and bypass-isolation equipment is a recognized way to service them. See 700.6(A).2026 NEC §700.6(A)

Special Occupancies, Equipment, and Conditions

An optional standby generator is connected to its load by a manual transfer switch. The system must have enough capacity to supply:

  • a.Only the largest single piece of equipment
  • b.The full connected load of the premises
  • c.125 percent of the largest motor load
  • d.All equipment intended to be operated at one time✓

With manual or nonautomatic transfer, the standby source only has to carry the equipment meant to run at the same time, and the user may choose that load. It does not have to carry everything on the premises, and sizing to the single largest item or a motor percentage is not the rule. See 702.4(A)(1).2026 NEC §702.4(A)(1)

Special Occupancies, Equipment, and Conditions

One alternate source supplies emergency, legally required standby, and optional standby loads through a load management system. Which loads get first priority for power?

  • a.Emergency circuits✓
  • b.Optional standby circuits
  • c.Legally required standby circuits
  • d.The largest motor circuits

Load management must keep power to emergency circuits first, then legally required standby circuits, then optional standby circuits. Motor size has nothing to do with the priority order. See 700.5(C).2026 NEC §700.5(C)

Special Occupancies, Equipment, and Conditions

An emergency generator relies on an on-site fuel supply. That supply must be enough to run the system for at least:

  • a.30 minutes
  • b.1 1/2 hours
  • c.2 hours✓
  • d.24 hours

The on-site fuel supply must be sufficient for at least 2 hours of system operation. The 1 1/2 hour figure applies to batteries feeding emergency illumination, not to generator fuel. See 700.12(B)(1).2026 NEC §700.12(B)(1)

Special Occupancies, Equipment, and Conditions

A mobile home measures 80 ft by 15 ft outside, coupler excluded. Using 3 VA per square foot at 120 volts, how many 15-ampere lighting circuits are required?

  • a.Two✓
  • b.One
  • c.Three
  • d.Four

Area is 80 x 15 = 1200 sq ft, and 1200 x 3 VA = 3600 VA. Dividing by 120 volts gives 30 amperes, and 30 / 15 = 2 circuits. One circuit comes from skipping part of the load or assuming a larger circuit, and three or four come from arithmetic slips. See 550.12(A).2026 NEC §550.12(A)

Special Occupancies, Equipment, and Conditions

In a mobile home, a single appliance rated 16 amperes is on an individual branch circuit. What is the highest overcurrent device rating this rule allows, based on the appliance rating?

  • a.16 amperes
  • b.20 amperes
  • c.32 amperes
  • d.24 amperes✓

For a single appliance rated 13.3 amperes or more on an individual branch circuit, the overcurrent device may not exceed 150 percent of the appliance rating. 16 x 1.5 = 24 amperes. Sixteen amperes applies no multiplier, 20 amperes uses 125 percent, and 32 amperes uses 200 percent. See 550.11(B).2026 NEC §550.11(B)

Special Occupancies, Equipment, and Conditions

A 20-ampere branch circuit in a mobile home has no other outlets and serves one cord-and-plug-connected appliance. What is the largest appliance rating allowed?

  • a.10 amperes
  • b.16 amperes✓
  • c.13.3 amperes
  • d.20 amperes

A single cord-and-plug-connected appliance on a circuit with no other outlets may be rated up to 80 percent of the circuit rating. 20 x 0.80 = 16 amperes. Twenty amperes ignores the 80 percent limit, and 10 amperes uses the 50 percent limit that applies when lighting outlets share the circuit. See 550.12(D).2026 NEC §550.12(D)

Special Occupancies, Equipment, and Conditions

A 15-ampere branch circuit in a mobile home supplies lighting outlets and also a fixed appliance. What is the largest total rating of fixed appliances allowed on that circuit?

  • a.10 amperes
  • b.12 amperes
  • c.15 amperes
  • d.7.5 amperes✓

When lighting outlets are on the same circuit, fixed appliances may total no more than 50 percent of the circuit rating. 15 x 0.50 = 7.5 amperes. Twelve amperes uses the 80 percent figure for motor or continuous loads, and 15 amperes is allowed only when there are no lighting outlets on the circuit. See 550.12(D).2026 NEC §550.12(D)

Special Occupancies, Equipment, and Conditions

An electric pool water heater has a total nameplate-rated load of 40 amperes. What is the minimum ampacity of its branch-circuit conductors?

  • a.50 amperes✓
  • b.32 amperes
  • c.40 amperes
  • d.60 amperes

Conductors and overcurrent devices for an electric pool water heater are sized at 125 percent of the total nameplate load or more. 40 x 1.25 = 50 amperes. Forty amperes applies no multiplier, 32 amperes multiplies by 80 percent instead, and 60 amperes uses 150 percent. See 680.10(A)(2).2026 NEC §680.10(A)(2)

Renewable Energy Technologies

A photovoltaic source circuit uses modules with a rated short-circuit current of 10 amperes. What minimum conductor ampacity is required before any temperature or conduit-fill adjustments?

  • a.12.5 amperes
  • b.15.6 amperes✓
  • c.10 amperes
  • d.20 amperes

The maximum circuit current is 125 percent of the rated short-circuit current, or 10 x 1.25 = 12.5 A, and the conductor must then be sized at 125 percent of that value without adjustment factors: 12.5 x 1.25 = 15.6 A. The 12.5-ampere answer stops after only the first multiplier, and 10 amperes ignores both.2026 NEC §690.8

Renewable Energy Technologies

A photovoltaic source circuit uses modules with a rated short-circuit current of 8 amperes. What minimum conductor ampacity is required before any adjustment factors?

  • a.15.6 amperes
  • b.12.5 amperes✓
  • c.8 amperes
  • d.10 amperes

The maximum circuit current is 125 percent of the rated short-circuit current: 8 x 1.25 = 10 A, and the conductor is then sized at 125 percent of that value: 10 x 1.25 = 12.5 A. See NEC 690.8(A) and (B).2026 NEC §690.8

Renewable Energy Technologies

What is the highest PV system dc circuit voltage permitted on or in a one- or two-family dwelling?

  • a.600 V✓
  • b.1000 V
  • c.1500 V
  • d.2000 V

PV dc circuits on or in one- and two-family dwellings are limited to 600 V. The 1000 V figure is the limit for arrays on or attached to other buildings and for PV dc circuits inside buildings, so it is too high for a dwelling. The larger values are not limits this section gives for building-mounted systems. See 690.7.2026 NEC §690.7

Renewable Energy Technologies

PV system dc circuits on a building need dc arc-fault circuit protection when they operate at or above what voltage between any two conductors?

  • a.30 V dc
  • b.50 V dc
  • c.80 V dc✓
  • d.120 V dc

PV dc circuits operating at 80 V dc or more between any two conductors must be protected by a listed PV arc-fault circuit interrupter or equivalent listed components. 30 V is a rapid shutdown limit, not the arc-fault threshold, and 50 V and 120 V do not appear in this rule. See 690.11.2026 NEC §690.11

Renewable Energy Technologies

A PV source circuit has 12 crystalline silicon modules in series, each with a rated open-circuit voltage of 40 V. The lowest expected ambient temperature is -8°C. Using the Code's voltage correction table, what is the maximum PV source circuit voltage?

  • a.480 V
  • b.537.6 V
  • c.547.2 V✓
  • d.556.8 V

For crystalline silicon modules, the maximum voltage is the sum of the series modules' rated open-circuit voltages multiplied by the cold-temperature factor from the table. Twelve modules at 40 V give 480 V, and the factor for the -6 to -10°C band is 1.14, so 480 x 1.14 = 547.2 V. The 480 V answer skips the correction, and the other two use the factors from the bands on either side (1.12 and 1.16). See 690.7(A) and Table 690.7(A).2026 NEC Table 690.7(A)

Renewable Energy Technologies

After rapid shutdown is initiated, controlled conductors located outside the array boundary must be limited to what level?

  • a.Not more than 30 volts within 30 seconds✓
  • b.Not more than 80 volts within 30 seconds
  • c.Not more than 30 volts within 10 seconds
  • d.Not more than 80 volts within 10 seconds

Outside the array boundary, or more than 1 m (3 ft) from where the conductors enter the building, controlled conductors must drop to 30 volts or less within 30 seconds of initiation. The 80 volt figure belongs to conductors inside the array boundary. The 10 second answers use a time that this rule does not give. See 690.12(B)(1).2026 NEC §690.12(B)(1)

Renewable Energy Technologies

For rapid shutdown purposes, how far from the array in all directions does the array boundary extend?

  • a.150 mm (6 in.)
  • b.305 mm (1 ft)✓
  • c.1 m (3 ft)
  • d.3 m (10 ft)

The array boundary is set at 305 mm (1 ft) from the array in every direction. The 1 m (3 ft) figure is a different measurement in the same rule, the distance from the point of entry inside a building, and is a common mix-up. The 6 in. and 10 ft values are not used here. See 690.12(B).2026 NEC §690.12(B)

Renewable Energy Technologies

Three PV modules are connected in parallel in one PV source circuit. Each module has a highest short-circuit current rating of 12 A. Using the 125% method, what is the maximum current of this PV source circuit?

  • a.15 A
  • b.36 A
  • c.45 A✓
  • d.56.25 A

Under the 125% method, the maximum current is the sum of the parallel modules' short-circuit current ratings multiplied by 125%. Here 3 x 12 A = 36 A, and 36 A x 1.25 = 45 A. 36 A leaves out the 125%, 15 A applies it to only one module, and 56.25 A applies it twice. See 690.8(A)(1)(a)(1).2026 NEC §690.8(A)(1)(a)(1)

Renewable Energy Technologies

A rooftop PV system is installed on a one-family dwelling. Where must the rapid shutdown initiation device be located?

  • a.Inside the dwelling at the main panelboard
  • b.In the attic next to the inverter
  • c.On the roof inside the array boundary
  • d.At a readily accessible outdoor location✓

Initiation devices must be readily accessible, and for one- and two-family dwellings they must be at an outdoor location so firefighters can reach them without entering. A device inside at the panelboard or in the attic is not outdoors, and one on the roof is not readily accessible. See 690.12(C)(1).2026 NEC §690.12(C)(1)

Renewable Energy Technologies

On the building label that shows where the rapid shutdown initiation devices are, what is the minimum height of the capitalized title letters?

  • a.9.5 mm (3/8 in.)✓
  • b.13 mm (1/2 in.)
  • c.19 mm (3/4 in.)
  • d.25 mm (1 in.)

The title on the rapid shutdown label must be in capital letters at least 9.5 mm (3/8 in.) high, with legible text that contrasts with the background. The larger sizes are more than the rule asks for and are not the stated minimum. See 690.12(D).2026 NEC §690.12(D)

Renewable Energy Technologies

Which marking, or its equivalent, must be permanently placed on each PV system disconnecting means?

  • a.SOLAR MAIN BREAKER
  • b.INVERTER OUTPUT CIRCUIT
  • c.RAPID SHUTDOWN SWITCH
  • d.PV SYSTEM DISCONNECT✓

Each PV system disconnecting means must be permanently marked to identify it as the PV system disconnect, using that wording or an equivalent. The rapid shutdown switch wording belongs on the label for the rapid shutdown switch, which is a separate requirement. The other two phrases are not markings this section calls for. See 690.13(C).2026 NEC §690.13(C)

Renewable Energy Technologies

In which location is PV system equipment and its disconnecting means not permitted to be installed?

  • a.Attics
  • b.Garages
  • c.Basements
  • d.Bathrooms✓

PV system equipment and disconnecting means may not be installed in bathrooms. This section does not name attics, garages, or basements as prohibited locations, and it separately allows power converters to be mounted in areas that are not readily accessible. See 690.4(D).2026 NEC §690.4(D)

Renewable Energy Technologies

A PV circuit has a maximum current of 16 A calculated under 690.8(A). The overcurrent device is not part of an assembly listed for continuous operation at 100% of its rating. Before rounding up to a standard size, what is the minimum overcurrent device rating?

  • a.12.8 A
  • b.16 A
  • c.20 A✓
  • d.25 A

A PV overcurrent device that is not in a 100% rated assembly must be rated at least 125% of the maximum current. 16 A x 1.25 = 20 A. 16 A would be right only for a 100% rated assembly, 12.8 A applies 80% in the wrong direction, and 25 A applies the 125% twice. See 690.9(B)(1).2026 NEC §690.9(B)(1)

Renewable Energy Technologies

A calculation made under Article 690 produces a result of 12.4. Using the rounding that the article permits, what value may be used?

  • a.12✓
  • b.12.5
  • c.13
  • d.15

Article 690 calculations may be rounded to the nearest whole number, and a fraction smaller than 0.5 may be dropped. Since 0.4 is less than 0.5, 12.4 becomes 12. Rounding up to 13 would apply only at 0.5 or more, and 12.5 and 15 are not whole-number rounding at all. See 690.4(G).2026 NEC §690.4(G)

Renewable Energy Technologies

For applying Article 690, the output of an ac module is treated as which type of circuit?

  • a.A PV source circuit
  • b.A PV dc circuit
  • c.A dc-to-dc converter circuit
  • d.An inverter output circuit✓

An ac module has its inverter built in, so its output is treated as an inverter output circuit. The PV source circuit rules do not apply to ac modules, and the other two answers are dc circuits that an ac module does not present to the installer. See 690.6(A) and 690.6(B).2026 NEC §690.6(B)

Renewable Energy Technologies

Three PV circuits share a common-return conductor. The individual circuits are protected by overcurrent devices rated 15 A, 15 A, and 20 A. What is the minimum ampacity of the common-return conductor?

  • a.35 A
  • b.50 A✓
  • c.62.5 A
  • d.78.1 A

A common-return conductor must have an ampacity at least equal to the sum of the overcurrent device ratings of the individual circuits. 15 A + 15 A + 20 A = 50 A. 35 A leaves one circuit out, and 62.5 A and 78.1 A add 125% multipliers that this rule does not require. See 690.8(C).2026 NEC §690.8(C)

Renewable Energy Technologies

Equipment that interconnects a power production source so it runs in parallel with the primary source must meet which requirement?

  • a.Be rated at 125% of the service rating
  • b.Be approved by the utility in place of listing
  • c.Be listed or field labeled for the interactive function✓
  • d.Be marked as suitable for stand-alone use only

Interconnection and interactive equipment must be listed for the interactive function, or be evaluated for that function and carry a field label, or both. Utility approval does not replace this, and equipment for stand-alone use only is not intended to run in parallel with another source. The 125% answer borrows a sizing idea that has nothing to do with listing. See 705.2.2026 NEC §705.2

Renewable Energy Technologies

An outlet supplying EVSE must be on an individual branch circuit when the EVSE is rated more than 120 volts or more than how many amperes?

  • a.16 A✓
  • b.20 A
  • c.24 A
  • d.30 A

Each outlet that supplies EVSE rated above 16 amperes or above 120 volts needs its own individual branch circuit. The higher values would let larger chargers share a circuit, which the rule does not allow unless a load management arrangement covered elsewhere in the article is used. See 625.40.2026 NEC §625.40

Renewable Energy Technologies

For sizing the supply circuit, how does the Code classify EVSE loads?

  • a.Continuous loads✓
  • b.Noncontinuous loads
  • c.Intermittent loads
  • d.Optional standby loads

EVSE and wireless power transfer equipment, including bidirectional equipment, are treated as continuous loads. That is why the circuit is sized with the continuous load rules instead of at 100% of the charger current. The other answers would undersize the circuit or describe a different kind of system. See 625.41.2026 NEC §625.41

Renewable Energy Technologies

A cord-and-plug-connected EVSE has a maximum rating of 24 A. What is the minimum ampere rating of its attachment plug?

  • a.24 A
  • b.30 A✓
  • c.37.5 A
  • d.48 A

Cord-and-plug-connected electric vehicle equipment needs an attachment plug rated at least 125% of the equipment's maximum rating. 24 A x 1.25 = 30 A. 24 A ignores the 125%, 37.5 A applies it twice, and 48 A doubles the rating. See 625.44.2026 NEC §625.44

Renewable Energy Technologies

Unless the listed EVSE has a cable management system, what is the maximum overall usable length of the output cable to the electric vehicle?

  • a.3.7 m (12 ft)
  • b.4.6 m (15 ft)
  • c.7.5 m (25 ft)✓
  • d.15 m (50 ft)

The overall usable length of the output cable is limited to 7.5 m (25 ft) unless a cable management system that is part of the listed equipment is provided. The 15 ft figure is a limit for a power-supply cord arrangement, not the output cable, and 12 ft and 50 ft are not in this rule. See 625.17(C).2026 NEC §625.17(C)

Renewable Energy Technologies

Fixed EVSE that is not specifically listed and marked for its location is installed outdoors. What is the minimum height above grade for storing the coupling means?

  • a.300 mm (12 in.)
  • b.450 mm (18 in.)
  • c.600 mm (24 in.)✓
  • d.900 mm (36 in.)

Unless the equipment is specifically listed and marked for the location, the coupling means must be stored at least 600 mm (24 in.) above grade outdoors. The 450 mm (18 in.) figure is the indoor height above the floor, which is the usual mix-up. The other two values are not in the rule. See 625.50.2026 NEC §625.50

Renewable Energy Technologies

Which receptacles installed for connecting electric vehicle charging equipment need GFCI protection for personnel?

  • a.Only 125-volt, 15- and 20-ampere receptacles
  • b.Only receptacles located outdoors
  • c.Only receptacles in dwelling unit garages
  • d.All receptacles installed for EV charging✓

Every receptacle installed for the connection of electric vehicle charging must have ground-fault circuit-interrupter protection for personnel. The rule is not limited by voltage, ampere rating, or location, so each of the narrower answers leaves some charging receptacles unprotected. See 625.54.2026 NEC §625.54

Renewable Energy Technologies

An indoor charging area has EVSE listed for vehicles that require ventilation. Three vehicles can charge at the same time, each from a 208 V single-phase, 40 A branch circuit. The table gives 171 cfm per vehicle for that rating. What is the minimum total ventilation?

  • a.171 cfm
  • b.296 cfm
  • c.342 cfm
  • d.513 cfm✓

The table value applies to each vehicle that can be charged at one time, so the per-vehicle figure is multiplied by the number of vehicles. 3 x 171 cfm = 513 cfm. 171 cfm covers only one vehicle, 342 cfm covers two, and 296 cfm is the per-vehicle figure from the 208 V three-phase column. See 625.52(B)(1) and Table 625.52(B)(1)(2).2026 NEC Table 625.52(B)(1)(2)

Renewable Energy Technologies

An installer wants to put a 50-ampere receptacle for cord-and-plug-connected EVSE on a 40-ampere branch circuit, as the general receptacle rating table referenced in 210.24 would otherwise allow. What does Article 625 say?

  • a.Permitted where the EVSE draws 32 A or less
  • b.Permitted only at one-family dwellings
  • c.Permitted where GFCI protection is added
  • d.Not permitted for EVSE receptacles✓

Article 625 overrides the general table for this case: a 50-ampere receptacle for EVSE may not go on a 40-ampere branch circuit. The rule has no allowance based on charger current, occupancy type, or added GFCI protection. See 625.44.2026 NEC §625.44