444 questions

Electrical Control Devices and Disconnecting Means

A power-operated circuit breaker is permitted as the service disconnecting means for the ungrounded service conductors provided that it:

  • a.Can be opened by hand if the power supply fails✓
  • b.Recloses by itself when the power is restored
  • c.Is rated at 125 percent of the calculated load
  • d.Is controlled only from a remote location

Section 230.76 allows either a manually operable switch or breaker, or a power-operated one that can still be opened by hand if its power supply fails. A device that could only be operated electrically, or only from a remote station, could not be opened in an outage.2026 NEC §230.76

Electrical Control Devices and Disconnecting Means

As a general rule, a circuit breaker must be installed so that the center of the grip of its operating handle, when in its highest position, is not more than what height above the floor or working platform?

  • a.6 ft
  • b.6 ft 7 in.✓
  • c.7 ft
  • d.8 ft

Section 240.24(A) requires circuit breakers and switches containing fuses to be readily accessible, with the center of the handle grip at its highest position no more than 6 ft 7 in. (2.0 m) above the floor, grade, or working platform. The measurement is to the handle, not to the top of the enclosure.2026 NEC §240.24(A)

Electrical Control Devices and Disconnecting Means

Overcurrent protective devices must not be located near easily ignitible material. Which location does the Code name as an example of this?

  • a.Attached garages
  • b.Mechanical rooms
  • c.Unfinished basements
  • d.Clothes closets✓

Section 240.24(D) prohibits overcurrent devices in the vicinity of easily ignitible material and gives clothes closets as the example. Bathrooms are also off limits, but that comes from a separate subsection, 240.24(E), and for a different reason.2026 NEC §240.24(D)

Electrical Control Devices and Disconnecting Means

A feeder supplies a detached building, and the building disconnecting means is installed outside the building. As a general rule, where must it be located?

  • a.At a readily accessible location on or within sight of the building✓
  • b.At the panelboard where the feeder originates
  • c.At any point on the premises that can be locked
  • d.At the first pole or pull box along the feeder

Section 225.31(B) says that a building disconnecting means located outside must be at a readily accessible location on the building or within sight of it as defined in 110.29. The breaker back at the supply panelboard does not satisfy this by itself.2026 NEC §225.31(B)

Electrical Control Devices and Disconnecting Means

The emergency disconnect for a one-family dwelling must be marked on the outside front of its enclosure. What colors and minimum letter height apply to that marking?

  • a.White background, red text, letters at least 1/2 in. high
  • b.Red background, white text, letters at least 1/4 in. high
  • c.Red background, white text, letters at least 1/2 in. high✓
  • d.Yellow background, black text, letters at least 1 in. high

Section 225.41(C) requires the emergency disconnect marking to be on the outside front of the enclosure with a red background and white text, in letters at least 1/2 in. (13 mm) high. Reversing the colors or shrinking the letters is the trap.2026 NEC §225.41(C)

Electrical Control Devices and Disconnecting Means

A motor disconnecting means has a current rating of 100 A. Applying the general current-rating rule for motor circuits rated 1000 volts or less, which of these is the highest motor full-load current it can serve?

  • a.71 A
  • b.77 A
  • c.83 A✓
  • d.88 A

Section 430.110(A) requires the disconnect rating to be at least 115 percent of the motor full-load current. Working backward, 100 A / 1.15 = 86.96 A, so the motor current cannot exceed about 87 A. Check: 83 A x 1.15 = 95.45 A, which fits, while 88 A x 1.15 = 101.2 A, which is over 100 A.2026 NEC §430.110(A)

Electrical Control Devices and Disconnecting Means

A stationary 1/2 hp, 115-volt motor has a full-load current of 9.8 A. If a general-use switch is used as its disconnecting means, what is the minimum ampere rating of the switch?

  • a.11.27 A
  • b.19.6 A✓
  • c.24.5 A
  • d.29.4 A

For stationary motors of 2 hp or less and 300 volts or less, 430.109(C)(1) permits a general-use switch with an ampere rating of at least twice the motor full-load current. 9.8 A x 2 = 19.6 A. Using 115 percent (11.27 A) applies the general disconnect rating rule, not the general-use switch rule.2026 NEC §430.109(C)(1)

Electrical Control Devices and Disconnecting Means

On an ac circuit, a 20 A general-use snap switch suitable only for ac is used as the disconnecting means for a stationary 240-volt motor rated under 2 hp. What is the highest motor full-load current this switch is permitted to serve?

  • a.16 A✓
  • b.17.4 A
  • c.20 A
  • d.25 A

Section 430.109(C)(2) allows an ac-only general-use snap switch for these small motors when the motor full-load current is no more than 80 percent of the switch ampere rating. 20 A x 0.80 = 16 A. Dividing by 1.15 (17.4 A) uses the wrong rule, and loading the switch to its full 20 A is not allowed.2026 NEC §430.109(C)(2)

Electrical Control Devices and Disconnecting Means

A small motor that is not covered by the Code motor current tables has a full-load current of 2.4 A. When rating a disconnecting means for a combination load, what locked-rotor current is assumed for this motor?

  • a.2.4 A
  • b.3 A
  • c.7.2 A
  • d.14.4 A✓

Section 430.110(C)(3) says that for small motors not covered by the motor current tables, the locked-rotor current is assumed to be six times the full-load current. 2.4 A x 6 = 14.4 A. Using three times (7.2 A) or adding only 25 percent (3 A) understates the starting current.2026 NEC §430.110(C)(3)

Electrical Control Devices and Disconnecting Means

A hermetic refrigerant motor-compressor has a nameplate rated-load current of 22 A and a branch-circuit selection current of 27 A. What is the minimum ampere rating of its disconnecting means?

  • a.25.3 A
  • b.27 A
  • c.31.05 A✓
  • d.40.5 A

Section 440.12(A)(1) requires an ampere rating of at least 115 percent of the rated-load current or the branch-circuit selection current, whichever is greater. The larger value is 27 A, so 27 x 1.15 = 31.05 A. Using the 22 A rated-load current (25.3 A) ignores the larger branch-circuit selection current.2026 NEC §440.12(A)(1)

Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Electrical Control Devices and Disconnecting Means

A torque motor has a nameplate current of 12 A. What is the minimum ampere rating of its disconnecting means?

  • a.12 A
  • b.13.8 A✓
  • c.15 A
  • d.24 A

Section 430.110(B) requires the disconnecting means for a torque motor to be rated at least 115 percent of the motor nameplate current. 12 A x 1.15 = 13.8 A. The 15 A answer uses 125 percent, which is a conductor sizing figure, not the disconnect figure.2026 NEC §430.110(B)

Electrical Control Devices and Disconnecting Means

A feeder supplies a detached workshop that is not a dwelling and contains five branch circuits. The calculated load is 48 A. What is the minimum rating of the building disconnecting means?

  • a.48 A
  • b.60 A✓
  • c.75 A
  • d.100 A

Section 225.39 requires the disconnect rating to be at least the calculated load and also at least the floor value for the type of installation. A building with five circuits that is not a one-family dwelling falls under all others in 225.39(D), which is 60 A. Since 48 A is below 60 A, the minimum is 60 A. The 100 A value applies to a one-family dwelling feeder.2026 NEC §225.39(D)

Special Occupancies, Equipment, and Conditions

An electric-vehicle supply equipment branch circuit serves a 40-ampere EV charging load. What minimum overcurrent device and conductor ampacity are required?

  • a.50 amperes✓
  • b.45 amperes
  • c.60 amperes
  • d.40 amperes

Electric-vehicle supply equipment is treated as a continuous load (625.41), so the overcurrent device and the conductors are sized at 125 percent under 210.20(A) and 210.19(A)(1): 40 x 1.25 = 50 A, a standard rating.2026 NEC §625.41

Special Occupancies, Equipment, and Conditions

What is the minimum distance a 125-volt, 15- or 20-ampere receptacle must be located from the inside wall of a permanently installed pool?

  • a.10 feet
  • b.6 feet✓
  • c.5 feet
  • d.3 feet

Receptacles must be at least 6 feet from the inside walls of a permanently installed pool, measured along the shortest path a cord would follow. At least one required receptacle must also be located between 6 and 20 feet from the pool, and every receptacle within 20 feet of the inside walls must have ground-fault protection.2026 NEC §680.22(A)

Special Occupancies, Equipment, and Conditions

A location is classified as Class I, Division 1 when which condition exists?

  • a.Combustible dust in ignitible concentrations is present in the surrounding air only during infrequent abnormal operating conditions
  • b.Easily ignitible fibers or flyings are handled or stored but are not normally likely to become suspended in the air
  • c.Ignitible concentrations of flammable gases or vapors can exist under normal operating conditions✓
  • d.Flammable liquids are stored only in sealed containers

Class I covers flammable gases and vapors, and Division 1 means ignitible concentrations can exist under normal operating conditions or frequently because of repair, maintenance or leakage. Combustible dust is Class II and ignitible fibers are Class III, so those descriptions point to different classifications.2026 NEC §500.5(B)(1)

Special Occupancies, Equipment, and Conditions

What is the smallest copper conductor permitted for the equipotential bonding required around a permanently installed pool?

  • a.6 AWG stranded aluminum
  • b.8 AWG solid copper✓
  • c.10 AWG solid copper
  • d.4 AWG insulated copper

The equipotential bonding around a pool uses a solid copper conductor not smaller than 8 AWG to tie together the reinforcing steel, perimeter surfaces, metal fittings and equipment so that everyone stands at the same potential. Section 680.26(B) also accepts 40 percent copper-clad steel of the same size, but aluminum is not among the listed conductors, 10 AWG is undersized, and 4 AWG is larger than the minimum.2026 NEC §680.26(B)

Special Occupancies, Equipment, and Conditions

At least one required 125-volt receptacle serving a permanently installed pool must be located within what distance range from the inside pool wall?

  • a.Between 10 feet and 25 feet
  • b.Between 6 feet and 20 feet✓
  • c.Between 5 feet and 15 feet
  • d.Between 3 feet and 10 feet

At least one 125-volt, 15- or 20-ampere general-purpose receptacle must be located no closer than 6 feet and no farther than 20 feet from the inside wall of a permanently installed pool. See 2026 NEC 680.22(A)(1).2026 NEC §680.22(A)(1)

Special Occupancies, Equipment, and Conditions

A location where combustible dust is present in ignitible concentrations is classified as which type?

  • a.Class IV
  • b.Class II✓
  • c.Class I
  • d.Class III

Class II locations are those made hazardous by combustible dust. Class I covers flammable gases and vapors and Class III covers combustible fibers and flyings. See 2026 NEC 500.5(C).2026 NEC §500.5(C)

Special Occupancies, Equipment, and Conditions

A solvent mixing room would reach ignitible vapor concentrations if its exhaust fans stopped, but positive mechanical ventilation normally prevents that. How is the room classified?

  • a.Class I, Division 1
  • b.Class II, Division 2
  • c.Unclassified
  • d.Class I, Division 2✓

Under 500.5(B)(2), a place where ignitible gas or vapor concentrations are normally prevented by positive mechanical ventilation, and would become hazardous only if that ventilation failed, is Class I, Division 2. Division 1 is for concentrations that exist in normal operation, Class II concerns dust rather than vapor, and the room cannot be unclassified because a fan failure creates the hazard.2026 NEC §500.5(B)(2)

Special Occupancies, Equipment, and Conditions

In a metal finishing shop, aluminum dust could be present in hazardous quantities, but only when the dust collection system malfunctions. Which classification applies?

  • a.Class II, Division 1✓
  • b.Class II, Division 2
  • c.Class III, Division 1
  • d.Class I, Division 2

Section 500.5(C)(1) makes a location Class II, Division 1 wherever Group E dusts, which are the combustible metal dusts such as aluminum, may be present in hazardous quantities under normal or abnormal conditions. Division 2 is the usual answer for dust present only abnormally, but that does not apply to metal dust. Class III is for fibers and flyings and Class I is for gases and vapors.2026 NEC §500.5(C)(1)

Special Occupancies, Equipment, and Conditions

Dust from grain handled in a storage elevator belongs to which material group?

  • a.Group D
  • b.Group E
  • c.Group F
  • d.Group G✓

Section 500.6(B) assigns combustible dusts that are neither metal dusts nor carbonaceous dusts to Group G, and it names flour, grain, wood, plastic, and chemicals as members. Group E is for metal dusts and Group F is for carbonaceous dusts such as coal. Group D is a Class I gas group, not a dust group.2026 NEC §500.6(B)

Special Occupancies, Equipment, and Conditions

Class II, Group F covers combustible carbonaceous dusts whose total entrapped volatiles exceed what percentage?

  • a.8 percent✓
  • b.12 percent
  • c.20 percent
  • d.40 percent

Section 500.6(B) defines Group F as combustible carbonaceous dusts having more than 8 percent total entrapped volatiles. The larger percentages are not found in the group definition.2026 NEC §500.6(B)

Special Occupancies, Equipment, and Conditions

In which locations is the dusttight protection technique permitted?

  • a.Class II, Division 1 or 2 only
  • b.Class II, Division 2 and Class III, Division 1 or 2✓
  • c.Class I, Division 2 and Class II, Division 2
  • d.Any Class I, II, or III location

Section 500.7(C) permits dusttight equipment in Class II, Division 2 and in Class III, Division 1 or 2. Class II, Division 1 calls for the dust-ignitionproof technique instead, so a choice that includes it is wrong. Dusttight is not a recognized technique for Class I gas or vapor locations.2026 NEC §500.7(C)

Special Occupancies, Equipment, and Conditions

Unless it is identified for low-temperature service, explosionproof equipment may not be used where the ambient temperature is below:

  • a.-40°C (-40°F)
  • b.-25°C (-13°F)✓
  • c.-10°C (14°F)
  • d.0°C (32°F)

Section 500.8 does not allow explosionproof or dust-ignitionproof equipment in ambient temperatures below -25°C (-13°F) unless the equipment is identified for low-temperature service. The freezing point and -10°C are warmer than the actual limit, and -40°C is colder than the limit the Code sets.2026 NEC §500.8

Special Occupancies, Equipment, and Conditions

In the temperature class table for hazardous location equipment, a T3 marking corresponds to what maximum surface temperature?

  • a.135°C (275°F)
  • b.160°C (320°F)
  • c.200°C (392°F)✓
  • d.300°C (572°F)

Table 500.8(C)(4) lists T3 at a maximum surface temperature of 200°C (392°F). The other values are neighbouring rows in the same table: 300°C is T2, 160°C is T3C, and 135°C is T4.2026 NEC Table 500.8(C)(4)

Special Occupancies, Equipment, and Conditions

A luminaire for a Class I location has a maximum surface temperature of 135°C (275°F). Which temperature class marking matches that value?

  • a.T3
  • b.T4✓
  • c.T5
  • d.T6

Table 500.8(C)(4) pairs a maximum surface temperature of 135°C (275°F) with temperature class T4. T3 is the 200°C row, T5 is the 100°C row, and T6 is the 85°C row.2026 NEC Table 500.8(C)(4)

Special Occupancies, Equipment, and Conditions

Field-threaded NPT conduit entering explosionproof equipment must be made up wrenchtight with at least how many threads fully engaged?

  • a.Three
  • b.Four
  • c.Five✓
  • d.Seven

Section 500.8(E)(1) requires NPT threaded entries into explosionproof equipment to be made up with at least five threads fully engaged. Three or four threads leave too short a flame path, and seven is more than the Code requires.2026 NEC §500.8(E)(1)

Special Occupancies, Equipment, and Conditions

Which method is NOT permitted as the bonding means for metal conduit in a hazardous (classified) location?

  • a.Standard double-locknut connections at the enclosure✓
  • b.Threaded couplings made up wrenchtight
  • c.Listed threaded hubs at the enclosure
  • d.Bushings fitted with bonding jumpers

Section 500.30(B) rules out locknut-bushing and double-locknut contacts as the bonding means in hazardous locations. Section 500.30(A) accepts wrenchtight threaded couplings, listed threaded hubs, and listed devices such as bushings with bonding jumpers, so those three choices are all allowed.2026 NEC §500.30(B)

Special Occupancies, Equipment, and Conditions

In a Class I, Division 2 location, a 4 ft length of listed LFMC with fittings listed for grounding supplies an instrument circuit. For the wire-type equipment bonding jumper to be omitted, overcurrent protection in the circuit must be limited to no more than:

  • a.10 amperes✓
  • b.15 amperes
  • c.20 amperes
  • d.30 amperes

Section 500.30(C)(2) lets the bonding jumper be left out in Division 2 only when three conditions are all met: listed LFMC of 6 ft or less with fittings listed for grounding, overcurrent protection of 10 amperes or less, and a load that is part of a meter, instrument, or relay circuit. The 15, 20, and 30 ampere choices are common branch-circuit ratings but exceed the limit.2026 NEC §500.30(C)(2)

Special Occupancies, Equipment, and Conditions

With a suitable gas group and temperature class, which Zone-marked equipment does Article 501 permit in a Class I, Division 1 location?

  • a.Zone 0, Zone 1, or Zone 2 equipment
  • b.Zone 0 or Zone 1 equipment
  • c.Zone 0 equipment only✓
  • d.No Zone-marked equipment

Section 501.5 permits Zone 0 equipment in Class I, Division 1 or Division 2 locations. Equipment marked for Zone 0, 1, or 2 is accepted only in Division 2, so Zone 1 and Zone 2 equipment cannot be used in Division 1 under this section. Saying no Zone equipment is allowed ignores the section altogether.2026 NEC §501.5

Special Occupancies, Equipment, and Conditions

Where PVC conduit is used underground as a Class I, Division 1 wiring method, it must be encased in a concrete envelope at least how thick?

  • a.1 in. (25 mm)
  • b.2 in. (50 mm)✓
  • c.3 in. (75 mm)
  • d.6 in. (150 mm)

Table 501.10(A)(1) accepts PVC conduit in Class I, Division 1 only where it is encased in a concrete envelope at least 2 in. (50 mm) thick, with at least 24 in. of cover to grade. One inch is too thin, and the thicker envelopes are more than the table requires.2026 NEC Table 501.10(A)(1)

Special Occupancies, Equipment, and Conditions

In a Class I, Division 1 location, how must rigid metal conduit connections be made?

  • a.Listed threadless compression fittings
  • b.Set-screw fittings with bonding jumpers
  • c.Any fittings listed for wet locations
  • d.Threaded connections✓

Table 501.10(A)(1) lists rigid metal conduit and intermediate metal conduit for Class I, Division 1 with the condition that conduit connections be threaded. Threadless fittings appear only in the Division 2 table, and set-screw or wet-location fittings do not give the tight threaded joint that Division 1 depends on.2026 NEC Table 501.10(A)(1)

Special Occupancies, Equipment, and Conditions

In a Class I, Division 1 location, a conduit enters an explosionproof enclosure that contains only splices. A conduit seal is required at that entry when the conduit is at least what size?

  • a.Trade size 1
  • b.Trade size 1-1/2
  • c.Trade size 2✓
  • d.Trade size 3

Section 501.15(A)(1) requires a seal at an entry to an explosionproof enclosure holding terminals, splices, or taps when the entry is trade size 2 (metric designator 53) or larger. Smaller entries to a splice-only enclosure do not trigger this rule, and waiting until trade size 3 would leave a trade size 2 entry unsealed.2026 NEC §501.15(A)(1)

Special Occupancies, Equipment, and Conditions

Two explosionproof enclosures in a Class I, Division 1 location are joined by a conduit nipple, and one seal placed within 18 in. of each enclosure is to serve both. What is the longest nipple permitted for this arrangement?

  • a.12 in.
  • b.18 in.
  • c.24 in.
  • d.36 in.✓

Section 501.15(A)(3) allows a single seal to serve two explosionproof enclosures joined by a nipple or conduit run of not more than 36 in., provided the seal is no more than 18 in. from either enclosure. The 18 in. figure is the seal distance, not the nipple length, and 12 in. and 24 in. are not the limit stated.2026 NEC §501.15(A)(3)

Special Occupancies, Equipment, and Conditions

The compound used in a Class I conduit sealing fitting must have a melting point of at least:

  • a.140°F (60°C)
  • b.167°F (75°C)
  • c.194°F (90°C)
  • d.200°F (93°C)✓

Section 501.15(C)(2) requires sealing compound to have a melting point of not less than 93°C (200°F). The three lower values all fall short of that minimum, so a compound with any of those melting points would not qualify.2026 NEC §501.15(C)(2)

Special Occupancies, Equipment, and Conditions

Unless a seal is specifically identified for a higher fill, the conductors in a conduit seal may occupy no more than what share of the cross-sectional area of a rigid metal conduit of the same trade size?

  • a.25 percent✓
  • b.31 percent
  • c.40 percent
  • d.53 percent

Section 501.15(C)(6) limits the conductors in a seal to 25 percent of the cross-sectional area of rigid metal conduit of the same trade size, unless the seal is identified for more. The 31, 40, and 53 percent choices all allow more conductor area than this section does, which would leave too little room for compound to surround each conductor.2026 NEC §501.15(C)(6)

Special Occupancies, Equipment, and Conditions

How may a garage that is used only for parking or storage of vehicles be classified?

  • a.Class I, Division 2 throughout
  • b.Unclassified✓
  • c.Class I, Division 1 at floor level
  • d.Class II, Division 2 throughout

Section 511.5(A) permits parking garages used for parking or storage to be unclassified. The Class I choices apply to repair garages where fuel vapors can be released during service work, and Class II is a dust classification that has nothing to do with vehicle storage.2026 NEC §511.5(A)

Special Occupancies, Equipment, and Conditions

In a repair garage, a Class I liquid that is not a motor fuel is dispensed from a drum. The Class I, Division 2 location extends in all directions how far from the dispensing point?

  • a.18 in.
  • b.3 ft✓
  • c.5 ft
  • d.10 ft

Section 511.5(B) makes the space within 3 ft (900 mm) of any fill or dispensing point for Class I liquids other than fuels, measured in every direction, a Class I, Division 2 location. Eighteen inches falls short of that boundary, and 5 ft and 10 ft overstate it.2026 NEC §511.5(B)

Special Occupancies, Equipment, and Conditions

A stock room beside a classified repair garage area is not likely to have flammable vapors released in it. If mechanical ventilation is the method relied on, what minimum rate allows the stock room to be unclassified?

  • a.Two air changes per hour
  • b.Four air changes per hour✓
  • c.Six air changes per hour
  • d.Twelve air changes per hour

Section 511.5(E)(1) treats adjacent areas such as stock rooms and switchboard rooms as unclassified when they are mechanically ventilated at four or more air changes per hour. Positive air pressure or an unpierced partition are the other ways to qualify. Two air changes is below the minimum, and six or twelve are more than the section requires.2026 NEC §511.5(E)(1)

Special Occupancies, Equipment, and Conditions

The Code figure for classified areas next to motor fuel dispensers shows the Class I, Division 2 area reaching how far horizontally from the dispenser?

  • a.5 ft (1.5 m)
  • b.10 ft (3 m)
  • c.20 ft (6 m)✓
  • d.50 ft (15 m)

Figure 514.5 draws the Class I, Division 2 area out to 20 ft (6 m) horizontally from the dispenser enclosure, in both the elevation and plan views. The shorter distances would leave part of the classified area unprotected, and 50 ft is far beyond what the figure shows.2026 NEC Figure 514.5

Special Occupancies, Equipment, and Conditions

A normal branch-circuit panelboard and an essential branch-circuit panelboard serve the same patient care vicinity. Their equipment grounding terminal buses must be connected together with an insulated continuous copper conductor no smaller than:

  • a.12 AWG
  • b.10 AWG✓
  • c.8 AWG
  • d.6 AWG

Section 517.14 requires the equipment grounding terminal buses of the normal and essential panelboards serving the same patient care vicinity to be tied together with an insulated continuous copper conductor not smaller than 10 AWG. A 12 AWG conductor is too small, and 8 AWG or 6 AWG is larger than the stated minimum.2026 NEC §517.14

Special Occupancies, Equipment, and Conditions

Where does Article 517 prohibit the installation of an isolated ground receptacle?

  • a.In any patient care space
  • b.In a facility business office
  • c.Outside a patient care vicinity
  • d.Within a patient care vicinity✓

Section 517.16(A) says an isolated ground receptacle shall not be installed within a patient care vicinity. Section 517.16(B) allows one in a patient care space when it is outside the vicinity, so a ban on every patient care space goes too far. Business offices are not addressed by this rule.2026 NEC §517.16(A)

Special Occupancies, Equipment, and Conditions

What is the largest listed feeder assembly (power-supply cord) permitted to supply a mobile home?

  • a.100 amperes
  • b.125 amperes
  • c.50 amperes✓
  • d.200 amperes

A mobile home may be supplied by no more than one listed mobile home feeder assembly, and that assembly is rated 50 amperes. The larger figures are service or feeder sizes that would call for a permanently installed feeder instead of a cord. See 550.10(A).2026 NEC §550.10(A)

Special Occupancies, Equipment, and Conditions

Measured from the end of the cord, including bared leads, to the face of the attachment plug cap, what is the longest overall length permitted for a mobile home feeder assembly?

  • a.36 1/2 ft✓
  • b.21 ft
  • c.25 ft
  • d.50 ft

The overall cord length has to fall between 21 ft and 36 1/2 ft, so 36 1/2 ft is the upper limit. The 21 ft figure is the minimum overall length, not the maximum, and the other values do not appear in the rule. See 550.10(D).2026 NEC §550.10(D)

Special Occupancies, Equipment, and Conditions

In a mobile home, the bottom of the distribution equipment must be at least how far above the floor level?

  • a.6 in.
  • b.1 ft
  • c.3 ft
  • d.24 in.✓

The bottom of the distribution equipment in a mobile home must sit at least 24 in. above the floor. The lower values would leave the panelboard too close to the floor, and 3 ft is more than the rule asks for. See 550.11(A).2026 NEC §550.11(A)

Special Occupancies, Equipment, and Conditions

A receptacle outlet is installed on the underside of a mobile home for pipe heating cable. It must be located within what distance of the cold water inlet?

  • a.10 ft
  • b.2 ft✓
  • c.18 in.
  • d.36 in.

The heat tape outlet goes within 2 ft of the cold water inlet so the cable can reach without an extension cord. The 36 in. figure belongs to the bathroom basin receptacle rule, and the other distances are not in this rule. See 550.13(G).2026 NEC §550.13(G)

Special Occupancies, Equipment, and Conditions

Mobile home service equipment must be rated at not less than what value at 120/240 volts?

  • a.60 amperes
  • b.125 amperes
  • c.200 amperes
  • d.100 amperes✓

Service equipment for a mobile home must be rated at least 100 amperes at 120/240 volts. Sixty amperes is below that floor, and the larger ratings are allowed but are not the minimum. See 550.51(C).2026 NEC §550.51(C)

Special Occupancies, Equipment, and Conditions

Supply conductors from an RV generator must terminate in a panelboard, enclosed transfer switch, or junction box with a receptacle located within what distance of the point where they enter the vehicle?

  • a.18 in.✓
  • b.3 ft
  • c.6 ft
  • d.10 ft

The generator supply conductors have to land in a panelboard, enclosed transfer switch, or junction box within 18 in. of where they enter the vehicle. The longer distances would leave too much unprotected conductor run inside the vehicle. See 551.30(E).2026 NEC §551.30(E)

Special Occupancies, Equipment, and Conditions

At a marina, a receptacle that provides shore power to a boat must have listed ground-fault protection of equipment rated at not more than:

  • a.6 mA
  • b.100 mA
  • c.30 mA✓
  • d.500 mA

Receptacles that provide shore power need listed ground-fault protection of equipment rated not more than 30 mA. The 100 mA value is the limit for feeders and branch circuits under 555.35(A), and 6 mA is the Class A GFCI trip level from Article 100, the personnel protection 555.35(C)(2) calls for on outlets other than shore power. See 555.35(C)(1).2026 NEC §555.35(C)(1)

Special Occupancies, Equipment, and Conditions

Service equipment for a floating dock must be located on land. What is the closest horizontal distance it may be to the structure it serves?

  • a.10 ft
  • b.20 ft
  • c.50 ft
  • d.5 ft✓

The service equipment sits on land, adjacent to the structure, but no closer than 5 ft horizontally and not on or in the structure itself. The larger distances are more than the rule requires. See 555.17.2026 NEC §555.17