Electrical Control Devices and Disconnecting Means

A 30-horsepower, 460-volt three-phase motor has a table full-load current of 40 amperes. What is the minimum ampere rating of the disconnecting means?

  • a.50 amperes
  • b.40 amperes
  • c.46 amperes✓
  • d.60 amperes

The disconnecting means must have an ampere rating of at least 115 percent of the full-load current: 40 x 1.15 = 46 A, so a 60-ampere switch would be the practical selection. The 40-ampere answer omits the 115 percent factor entirely, and 50 or 60 amperes are available equipment ratings rather than the calculated minimum the question asks for.2026 NEC §430.110(A)

Electrical Control Devices and Disconnecting Means

Where must a motor disconnecting means be located relative to the motor?

  • a.Within 25 feet of the motor in all cases
  • b.In sight from the motor location and from the driven machinery location✓
  • c.Anywhere on the same floor level as the motor
  • d.In sight from the motor controller only, on the theory that the controller disconnect is always sufficient and that no separate in-sight rule applies to the motor itself

Under 430.102(B) a disconnecting means must be in sight from the motor location and the driven machinery location. The controller disconnect required by 430.102(A) can do this job when it is in sight from both. An exception lets the motor disconnect be omitted only when the controller disconnect is lockable and, in addition, either an in-sight location is impracticable or adds hazards, or the site is an industrial installation with written safety procedures and qualified persons. Lockability alone is not enough. Under 110.29, in sight means visible and not more than 50 feet away.2026 NEC §430.102(B)

Electrical Control Devices and Disconnecting Means

Under NEC 110.29, what does 'in sight from' mean in terms of distance?

  • a.Anywhere on the same floor level
  • b.Visible and not more than 50 feet away✓
  • c.Within 75 feet whether visible or not
  • d.Visible and not more than 25 feet away

'In sight from' means the equipment is visible and not more than 50 feet distant from the other equipment. See NEC 110.29.2026 NEC §110.29

Electrical Control Devices and Disconnecting Means

A 40-horsepower, 460-volt, three-phase motor has a table full-load current of 52 amperes. What minimum ampere rating must the disconnecting means have?

  • a.46 amperes
  • b.65 amperes
  • c.52 amperes
  • d.59.8 amperes✓

The disconnecting means must be at least 115 percent of the full-load current: 52 x 1.15 = 59.8 A, so a 60-ampere or larger switch would be selected. See NEC 430.110(A).2026 NEC §430.110(A)

Electrical Control Devices and Disconnecting Means

An individual disconnecting means is provided for a 480-volt motor controller. Where must that disconnecting means be located?

  • a.Within 25 ft of the panelboard that supplies the motor
  • b.In sight from the controller location✓
  • c.In the same room as the driven machinery
  • d.Anywhere on the premises if it can be locked open

Section 430.102(A) calls for a disconnecting means for each motor controller, placed in sight from the controller location. The trap is tying the location to the supply panelboard or the driven machine. The machinery matters for the motor disconnect in 430.102(B), not for the controller disconnect.2026 NEC §430.102(A)

Electrical Control Devices and Disconnecting Means

The disconnecting means for a motor controller is also permitted to serve as the disconnecting means for the motor when it is:

  • a.Rated at 200 percent of the motor full-load current
  • b.Located in the same building as the motor
  • c.Marked with the horsepower of the motor
  • d.In sight from the motor location and the driven machinery location✓

Under 430.102(B)(2), the controller disconnect can double as the motor disconnect only if it is in sight from both the motor location and the driven machinery location. A larger rating or a marking does not replace the in-sight condition. Being somewhere in the same building is not enough.2026 NEC §430.102(B)(2)

Electrical Control Devices and Disconnecting Means

When a motor disconnecting means is opened, which conductors must it disconnect?

  • a.All ungrounded supply conductors together✓
  • b.Only one ungrounded conductor, as long as the motor stops
  • c.All ungrounded conductors, each one on its own separate handle
  • d.Only the conductors that feed the motor overload relays

Section 430.103 requires the disconnecting means to open all ungrounded supply conductors, built so that no pole can be operated independently. Opening a single phase may stop the motor but leaves the other conductors energized. Separate handles for each pole are exactly what the rule rules out.2026 NEC §430.103

Electrical Control Devices and Disconnecting Means

A motor circuit has two disconnecting means, one at the controller and one at the motor. How many of them must be readily accessible?

  • a.Neither one, if both can be locked open
  • b.Only the one mounted nearest the motor
  • c.At least one of them✓
  • d.Both of them in every installation

Section 430.107 requires at least one of the disconnecting means to be readily accessible. It does not say which one, so it need not be the one nearest the motor. A lock-open provision does not remove the requirement.2026 NEC §430.107

Electrical Control Devices and Disconnecting Means

Which statement is correct for a motor controller that does not also serve as the disconnecting means?

  • a.It must open every ungrounded conductor to the motor
  • b.It must open the grounded conductor before the others
  • c.It must open the equipment grounding conductor as well
  • d.It need not open all conductors to the motor✓

Section 430.84 says a controller is not required to open all conductors to the motor. That is why a separate disconnecting means, which does open all ungrounded supply conductors, is required. The trap is applying the disconnect rule to the controller.2026 NEC §430.84

Electrical Control Devices and Disconnecting Means

Which mounting location is prohibited for the disconnecting means of an air-conditioning condensing unit?

  • a.On the building wall within sight of the unit
  • b.Within the air-conditioning equipment itself
  • c.On a panel designed to allow access to the equipment✓
  • d.On the unit where the nameplate stays visible

Section 440.14 allows the disconnect to be on or within the equipment, but not on panels that are designed to allow access to the equipment and not where it hides the equipment nameplate. A wall location within sight of and readily accessible from the unit is the ordinary compliant choice.2026 NEC §440.14

Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Electrical Control Devices and Disconnecting Means

A single-phase, 240-volt room air conditioner uses its attachment plug and receptacle as the disconnecting means. For this to be permitted without a separate disconnect, the manual controls on the unit must be readily accessible and within what distance of the floor?

  • a.4 ft
  • b.6 ft✓
  • c.6 ft 7 in.
  • d.8 ft

Section 440.63 lets the plug and receptacle serve as the disconnect for a single-phase room air conditioner rated 250 volts or less when its manual controls are readily accessible and within 6 ft of the floor. Otherwise an approved manual disconnect must be installed in a readily accessible location within sight of the unit. The 6 ft 7 in. figure is the handle height limit for switches and breakers, a different rule.2026 NEC §440.63

Electrical Control Devices and Disconnecting Means

The disconnecting means for a rooftop refrigeration unit is readily accessible to unqualified persons. An enclosure door or hinged cover that exposes energized parts when open must be:

  • a.Painted red and marked with the circuit voltage
  • b.Interlocked with the compressor contactor coil
  • c.Removed and replaced with a dead-front cover
  • d.Locked or require a tool to open✓

Section 440.11 says that where the disconnecting means is readily accessible to unqualified persons, any enclosure door or hinged cover that exposes energized parts when open must be locked or need a tool to open. Color, signs, or interlocks are not what this rule asks for.2026 NEC §440.11

Electrical Control Devices and Disconnecting Means

What is the maximum number of service disconnects permitted for each service?

  • a.2
  • b.4
  • c.6✓
  • d.8

Section 230.71 starts from one service disconnect per service, and 230.71(B) permits two to six. Six is therefore the ceiling for each service. Disconnects used only for items such as surge-protective devices or power monitoring equipment are not counted toward the six.2026 NEC §230.71(B)

Electrical Control Devices and Disconnecting Means

As a general rule, where must the service disconnect for a one-family dwelling be installed?

  • a.In a readily accessible indoor location nearest the service conductor entrance
  • b.In a readily accessible outdoor location on or within sight of the dwelling✓
  • c.In any accessible location inside an attached garage
  • d.In the basement within 10 ft of the meter socket

Section 230.70(A)(1) puts the service disconnect for one- and two-family dwellings in a readily accessible outdoor location, either on the dwelling or within sight of it. The indoor location nearest the point of entrance is the choice allowed for other occupancies under 230.70(A)(2), and that is the trap here.2026 NEC §230.70(A)(1)

Electrical Control Devices and Disconnecting Means

A service has four service disconnects. As a general rule, how must they be arranged and identified?

  • a.Spread out, with at least 10 ft between each one
  • b.Grouped, with only the largest one marked
  • c.Placed on separate floors, each marked with voltage
  • d.Grouped, with each one marked to show the load it serves✓

Section 230.72(A) requires the two to six service disconnects to be grouped, and each one must be marked to indicate the load served. Scattering them defeats the purpose, which is to let someone shut off the whole building from one place.2026 NEC §230.72(A)

Electrical Control Devices and Disconnecting Means

A power-operated circuit breaker is permitted as the service disconnecting means for the ungrounded service conductors provided that it:

  • a.Can be opened by hand if the power supply fails✓
  • b.Recloses by itself when the power is restored
  • c.Is rated at 125 percent of the calculated load
  • d.Is controlled only from a remote location

Section 230.76 allows either a manually operable switch or breaker, or a power-operated one that can still be opened by hand if its power supply fails. A device that could only be operated electrically, or only from a remote station, could not be opened in an outage.2026 NEC §230.76

Electrical Control Devices and Disconnecting Means

As a general rule, a circuit breaker must be installed so that the center of the grip of its operating handle, when in its highest position, is not more than what height above the floor or working platform?

  • a.6 ft
  • b.6 ft 7 in.✓
  • c.7 ft
  • d.8 ft

Section 240.24(A) requires circuit breakers and switches containing fuses to be readily accessible, with the center of the handle grip at its highest position no more than 6 ft 7 in. (2.0 m) above the floor, grade, or working platform. The measurement is to the handle, not to the top of the enclosure.2026 NEC §240.24(A)

Electrical Control Devices and Disconnecting Means

Overcurrent protective devices must not be located near easily ignitible material. Which location does the Code name as an example of this?

  • a.Attached garages
  • b.Mechanical rooms
  • c.Unfinished basements
  • d.Clothes closets✓

Section 240.24(D) prohibits overcurrent devices in the vicinity of easily ignitible material and gives clothes closets as the example. Bathrooms are also off limits, but that comes from a separate subsection, 240.24(E), and for a different reason.2026 NEC §240.24(D)

Electrical Control Devices and Disconnecting Means

A feeder supplies a detached building, and the building disconnecting means is installed outside the building. As a general rule, where must it be located?

  • a.At a readily accessible location on or within sight of the building✓
  • b.At the panelboard where the feeder originates
  • c.At any point on the premises that can be locked
  • d.At the first pole or pull box along the feeder

Section 225.31(B) says that a building disconnecting means located outside must be at a readily accessible location on the building or within sight of it as defined in 110.29. The breaker back at the supply panelboard does not satisfy this by itself.2026 NEC §225.31(B)

Electrical Control Devices and Disconnecting Means

The emergency disconnect for a one-family dwelling must be marked on the outside front of its enclosure. What colors and minimum letter height apply to that marking?

  • a.White background, red text, letters at least 1/2 in. high
  • b.Red background, white text, letters at least 1/4 in. high
  • c.Red background, white text, letters at least 1/2 in. high✓
  • d.Yellow background, black text, letters at least 1 in. high

Section 225.41(C) requires the emergency disconnect marking to be on the outside front of the enclosure with a red background and white text, in letters at least 1/2 in. (13 mm) high. Reversing the colors or shrinking the letters is the trap.2026 NEC §225.41(C)

Electrical Control Devices and Disconnecting Means

A motor disconnecting means has a current rating of 100 A. Applying the general current-rating rule for motor circuits rated 1000 volts or less, which of these is the highest motor full-load current it can serve?

  • a.71 A
  • b.77 A
  • c.83 A✓
  • d.88 A

Section 430.110(A) requires the disconnect rating to be at least 115 percent of the motor full-load current. Working backward, 100 A / 1.15 = 86.96 A, so the motor current cannot exceed about 87 A. Check: 83 A x 1.15 = 95.45 A, which fits, while 88 A x 1.15 = 101.2 A, which is over 100 A.2026 NEC §430.110(A)

Electrical Control Devices and Disconnecting Means

A stationary 1/2 hp, 115-volt motor has a full-load current of 9.8 A. If a general-use switch is used as its disconnecting means, what is the minimum ampere rating of the switch?

  • a.11.27 A
  • b.19.6 A✓
  • c.24.5 A
  • d.29.4 A

For stationary motors of 2 hp or less and 300 volts or less, 430.109(C)(1) permits a general-use switch with an ampere rating of at least twice the motor full-load current. 9.8 A x 2 = 19.6 A. Using 115 percent (11.27 A) applies the general disconnect rating rule, not the general-use switch rule.2026 NEC §430.109(C)(1)

Electrical Control Devices and Disconnecting Means

On an ac circuit, a 20 A general-use snap switch suitable only for ac is used as the disconnecting means for a stationary 240-volt motor rated under 2 hp. What is the highest motor full-load current this switch is permitted to serve?

  • a.16 A✓
  • b.17.4 A
  • c.20 A
  • d.25 A

Section 430.109(C)(2) allows an ac-only general-use snap switch for these small motors when the motor full-load current is no more than 80 percent of the switch ampere rating. 20 A x 0.80 = 16 A. Dividing by 1.15 (17.4 A) uses the wrong rule, and loading the switch to its full 20 A is not allowed.2026 NEC §430.109(C)(2)

Electrical Control Devices and Disconnecting Means

A small motor that is not covered by the Code motor current tables has a full-load current of 2.4 A. When rating a disconnecting means for a combination load, what locked-rotor current is assumed for this motor?

  • a.2.4 A
  • b.3 A
  • c.7.2 A
  • d.14.4 A✓

Section 430.110(C)(3) says that for small motors not covered by the motor current tables, the locked-rotor current is assumed to be six times the full-load current. 2.4 A x 6 = 14.4 A. Using three times (7.2 A) or adding only 25 percent (3 A) understates the starting current.2026 NEC §430.110(C)(3)

Electrical Control Devices and Disconnecting Means

A hermetic refrigerant motor-compressor has a nameplate rated-load current of 22 A and a branch-circuit selection current of 27 A. What is the minimum ampere rating of its disconnecting means?

  • a.25.3 A
  • b.27 A
  • c.31.05 A✓
  • d.40.5 A

Section 440.12(A)(1) requires an ampere rating of at least 115 percent of the rated-load current or the branch-circuit selection current, whichever is greater. The larger value is 27 A, so 27 x 1.15 = 31.05 A. Using the 22 A rated-load current (25.3 A) ignores the larger branch-circuit selection current.2026 NEC §440.12(A)(1)

Electrical Control Devices and Disconnecting Means

A torque motor has a nameplate current of 12 A. What is the minimum ampere rating of its disconnecting means?

  • a.12 A
  • b.13.8 A✓
  • c.15 A
  • d.24 A

Section 430.110(B) requires the disconnecting means for a torque motor to be rated at least 115 percent of the motor nameplate current. 12 A x 1.15 = 13.8 A. The 15 A answer uses 125 percent, which is a conductor sizing figure, not the disconnect figure.2026 NEC §430.110(B)

Electrical Control Devices and Disconnecting Means

A feeder supplies a detached workshop that is not a dwelling and contains five branch circuits. The calculated load is 48 A. What is the minimum rating of the building disconnecting means?

  • a.48 A
  • b.60 A✓
  • c.75 A
  • d.100 A

Section 225.39 requires the disconnect rating to be at least the calculated load and also at least the floor value for the type of installation. A building with five circuits that is not a one-family dwelling falls under all others in 225.39(D), which is 60 A. Since 48 A is below 60 A, the minimum is 60 A. The 100 A value applies to a one-family dwelling feeder.2026 NEC §225.39(D)