A 208-volt, single-phase branch circuit supplies a continuous load of 24 amperes. What is the minimum standard overcurrent device rating permitted?
- a.30 amperes✓
- b.25 amperes
- c.24 amperes
- d.40 amperes
An overcurrent device supplying a continuous load must be rated at not less than 125 percent of that load: 24 A x 1.25 = 30 A, which is a standard rating in 240.6(A). The 24 A and 25 A choices ignore or under-apply the 125 percent factor, and 40 A jumps past the next standard size above the calculated value.2026 NEC §210.20(A)
A branch circuit supplies a continuous load of 24 amperes. What is the minimum size copper branch-circuit conductor, assuming 75 degrees C terminations and THWN insulation?
- a.12 AWG
- b.10 AWG✓
- c.8 AWG
- d.14 AWG
The conductor must carry at least 125 percent of the continuous load, or 30 A (210.19(A)). In the 75 degrees C column of Table 310.16, 12 AWG copper is only 25 A, so it fails; 10 AWG copper is 35 A and is adequate, and 240.4(D) allows a 30 A device on 10 AWG. Choosing 8 AWG is oversized for the minimum asked, and 14 AWG is 20 A in that column and limited to a 15 A device.2026 NEC §210.19(A)
Six current-carrying 12 AWG THHN copper conductors are installed in a single EMT run at a 30 degrees C ambient. What is the adjusted ampacity of each conductor before termination limits are applied?
- a.25 amperes
- b.20 amperes
- c.22.5 amperes
- d.24 amperes✓
Start in the 90 degrees C column of Table 310.16, where 12 AWG copper is 30 A, then apply the adjustment factor for 4 through 6 current-carrying conductors, which is 80 percent (Table 310.15(C)(1)): 30 A x 0.80 = 24 A. The 25 A answer is the unadjusted 75 degrees C value, 20 A is the 60 degrees C table value (or 80 percent of the 75 degrees C value), and 22.5 A does not result from any correct combination of table value and factor.2026 NEC §310.15(C)(1)
Four current-carrying 8 AWG THWN-2 copper conductors run in a raceway through a 48 degrees C ambient. What is the adjusted ampacity of each conductor?
- a.36 amperes✓
- b.44 amperes
- c.40 amperes
- d.33 amperes
Begin with the 90 degrees C ampacity of 8 AWG copper, 55 A, then correct for the 46 to 50 degrees C ambient range at 0.82 and adjust for four current-carrying conductors at 0.80: 55 x 0.82 x 0.80 = 36 A. The 44 A answer applies only the 80 percent adjustment to 55 A, 40 A applies it to the 75 degrees C value of 50 A, and 33 A applies both factors to the 75 degrees C value, which is not required when a 90 degrees C conductor is used as the derating base.2026 NEC §310.15
A 120-volt circuit carries 20 amperes through 12 AWG copper (6,530 circular mils) to a load 100 feet away. Using K = 12.9, what is the approximate voltage drop?
- a.10.5 volts
- b.3.9 volts
- c.5.2 volts
- d.7.9 volts✓
For a single-phase circuit, VD = (2 x K x I x L) / CM = (2 x 12.9 x 20 x 100) / 6,530 = 51,600 / 6,530, or about 7.9 volts. The 3.9-volt answer forgets that current travels out and back, so it omits the factor of 2; 5.2 volts and 10.5 volts do not correspond to any correct combination of the formula terms.2026 NEC Chapter 9, Table 8
A 120-volt branch circuit must carry 12 amperes 120 feet with voltage drop held to 3 percent. Using K = 12.9 for copper, what is the smallest conductor that meets the target?
- a.8 AWG
- b.14 AWG
- c.12 AWG
- d.10 AWG✓
Three percent of 120 volts is 3.6 volts, so the required area is CM = (2 x 12.9 x 12 x 120) / 3.6 = 37,152 / 3.6 = 10,320 circular mils. From Chapter 9, Table 8, 12 AWG has only 6,530 circular mils and fails, while 10 AWG has 10,380 circular mils and just satisfies the requirement. 8 AWG works electrically but is larger than the minimum asked for, and 14 AWG is far too small.2026 NEC Chapter 9, Table 8
What is the minimum number of 20-ampere small-appliance branch circuits required for the kitchen, pantry, breakfast room and dining room receptacles of a dwelling unit?
- a.One
- b.Two✓
- c.Three
- d.Four
At least two 20-ampere small-appliance branch circuits must serve the receptacle outlets in those rooms, and those circuits may not supply other outlets. One circuit is below the minimum, while three or four exceed the code minimum and are design choices rather than requirements.2026 NEC §210.11(C)(1)
What is the minimum branch-circuit rating for the receptacle outlets serving a dwelling unit bathroom?
- a.15 amperes
- b.20 amperes✓
- c.25 amperes
- d.30 amperes
A dedicated 20-ampere branch circuit is required for bathroom receptacle outlets, and it may serve only bathroom receptacles unless it supplies a single bathroom entirely. A 15-ampere circuit is not permitted for this purpose, and 25 or 30 amperes are not used for 125-volt, 15- and 20-ampere receptacle circuits.2026 NEC §210.11(C)(3)
Nine current-carrying 10 AWG THHN copper conductors share one raceway at a 30 degrees C ambient. What is the adjusted ampacity of each?
- a.35 amperes
- b.24.5 amperes
- c.26.3 amperes
- d.28 amperes✓
The 90 degrees C ampacity of 10 AWG copper is 40 A, and the adjustment factor for 7 through 9 current-carrying conductors is 70 percent (Table 310.15(C)(1)): 40 x 0.70 = 28 A. The 24.5 A answer applies 70 percent to the 75 degrees C value of 35 A, 35 A ignores adjustment entirely, and 26.3 A does not result from any correct combination of table value and factor.2026 NEC §310.15(C)(1)
A four-wire, three-phase, 208Y/120-volt feeder supplies electric-discharge lighting, and the major portion of the load is nonlinear. How many current-carrying conductors are counted for adjustment purposes?
- a.Two
- b.Four✓
- c.Three
- d.Five
When the major portion of the load is nonlinear, harmonic currents keep the neutral loaded even under balanced conditions, so the neutral counts as a current-carrying conductor along with the three phase conductors, giving four. If the load were linear the neutral would not be counted, giving three, and the equipment grounding conductor is never counted.2026 NEC §310.15(E)
Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
Where must a multiwire branch circuit have a means to simultaneously disconnect all ungrounded conductors?
- a.Only where the circuit supplies more than one device on a single yoke
- b.At the first outlet box on the circuit
- c.At each utilization equipment location
- d.At the point where the branch circuit originates✓
Simultaneous disconnection of all ungrounded conductors is required at the point of origin, normally by handle ties or a multipole breaker in the panelboard, so no part of the shared neutral stays energized during service work. Disconnecting at the first outlet or at the equipment does not remove the hazard back at the panel, and the single-yoke rule is a separate requirement in 210.7.2026 NEC §210.4(B)
In a dwelling unit living room, no point measured horizontally along the floor line of any wall space may be more than what distance from a receptacle outlet?
- a.12 feet
- b.6 feet✓
- c.4 feet
- d.8 feet
The 6-foot rule means a 6-foot appliance cord can reach a receptacle from any point along the wall line, which works out to a maximum spacing of 12 feet between receptacles. The 12-foot answer confuses spacing between outlets with distance from any point, and 4 or 8 feet are not code values for general wall space.2026 NEC §210.52(A)(1)
In a dwelling unit, 125-volt receptacles installed within what distance of the top inside edge of a sink bowl require GFCI protection?
- a.5 feet
- b.3 feet
- c.6 feet✓
- d.10 feet
The measurement is 6 feet from the top inside edge of the sink bowl, taken along the shortest path a supply cord would follow without passing through a floor, wall, ceiling or fixed barrier (210.8(A)). The 3-, 5- and 10-foot values are not used for the sink measurement.2026 NEC §210.8(A)
Arc-fault circuit-interrupter protection is required for 120-volt, single-phase, 10-, 15- and 20-ampere branch circuits supplying outlets in which dwelling unit areas?
- a.Kitchens, laundry areas, bedrooms and most other habitable rooms✓
- b.Bedrooms only, since they are the sleeping areas
- c.Unfinished basements, garages and crawl spaces only
- d.Bathrooms, outdoor areas and boathouses only
The AFCI requirement in 210.12(B) reaches nearly every habitable area of a dwelling, including kitchens and laundry areas, not just bedrooms. Bathrooms, garages and outdoor areas are not on the AFCI list and are addressed by GFCI rules instead, so limiting AFCI to those areas reverses the two protection schemes.2026 NEC §210.12(B)
What is the allowable ampacity of 4/0 AWG copper THWN in the 75 degrees C column?
- a.195 amperes
- b.205 amperes
- c.260 amperes
- d.230 amperes✓
Table 310.16 lists 4/0 copper at 230 amperes in the 75 degrees C column. The 260-ampere figure is the 90 degrees C value and may be used only as a derating base, 195 amperes is the 60 degrees C value, and 205 amperes is not a 4/0 copper value in any column of the table.2026 NEC Table 310.16
Twelve current-carrying 12 AWG THHN copper conductors run in one raceway through a 38 degrees C ambient. What is the adjusted ampacity of each conductor?
- a.15 amperes
- b.13.65 amperes✓
- c.12 amperes
- d.10.9 amperes
Start at the 90 degrees C ampacity of 30 A, apply the 36 to 40 degrees C correction factor of 0.91, then the 50 percent adjustment for 10 through 20 conductors: 30 x 0.91 x 0.50 = 13.65 A. The 15 A answer applies only the 50 percent adjustment and skips the temperature correction, while 12 A and 10.9 A do not result from the correct factors for this ambient and conductor count.2026 NEC §310.15
A 5,000-watt, 240-volt single-phase electric heater operates continuously. What is the minimum standard branch-circuit overcurrent device rating?
- a.30 amperes✓
- b.20 amperes
- c.25 amperes
- d.35 amperes
The load current is 5,000 / 240 = 20.8 A, and because the load is continuous the device must be rated at least 20.8 x 1.25 = 26 A, so the next standard rating is 30 A. The 20 A and 25 A answers either ignore the continuous factor or land below the calculated minimum, and 35 A is not the next standard size above 26 A.2026 NEC §210.20(A)
On a 20-ampere branch circuit that supplies both lighting outlets and cord-and-plug-connected equipment not fastened in place, what is the maximum rating of any one piece of that cord-and-plug-connected equipment?
- a.12 amperes
- b.20 amperes
- c.16 amperes✓
- d.15 amperes
Any one piece of cord-and-plug-connected equipment that is not fastened in place is limited to 80 percent of the branch-circuit rating on a 15- or 20-ampere circuit (210.23(B)(1)): 20 x 0.80 = 16 A. The 20-ampere answer would let the equipment consume the entire circuit, and 12 or 15 amperes are not derived from the 80 percent rule.2026 NEC §210.23(B)(1)
Using the standard calculation method, what is the general lighting and general-use load for a dwelling unit with 2,000 square feet of habitable floor area, before any demand factors?
- a.4,500 volt-amperes
- b.3,000 volt-amperes
- c.4,000 volt-amperes✓
- d.6,000 volt-amperes
Section 120.41 sets the minimum unit load for dwelling units at 2 volt-amperes per square foot, so 2,000 x 2 = 4,000 volt-amperes. The 6,000 answer uses 3 volt-amperes per square foot, the figure from earlier Code editions, and 3,000 and 4,500 use 1.5 and 2.25 volt-amperes, none of which is the current dwelling value.2026 NEC §120.41
How much load must be included for the two required small-appliance branch circuits plus the one required laundry branch circuit of a dwelling, before demand factors are applied?
- a.3,000 volt-amperes
- b.4,500 volt-amperes✓
- c.1,500 volt-amperes
- d.6,000 volt-amperes
Each small-appliance and laundry branch circuit is calculated at 1,500 volt-amperes: two small-appliance circuits plus one laundry circuit is 3 x 1,500 = 4,500 volt-amperes. The 3,000 answer counts only the two small-appliance circuits and omits the laundry circuit.2026 NEC §120.52
Which of the following dwelling-unit locations requires GFCI protection for 125-volt, 15- and 20-ampere receptacles?
- a.A wall receptacle in a second-floor bedroom
- b.A receptacle in an unfinished basement✓
- c.A receptacle in a first-floor hallway
- d.A receptacle in a bedroom clothes closet
Section 210.8(A) lists basements, finished or not, among the dwelling areas requiring GFCI protection, along with bathrooms, garages, outdoors, crawl spaces, kitchens and laundry areas. Bedrooms, hallways and closets are addressed by AFCI rather than GFCI requirements, so they are not on the GFCI list.2026 NEC §210.8(A)
A continuous load draws 16 amperes. What is the minimum standard overcurrent device rating permitted?
- a.15 amperes
- b.16 amperes
- c.25 amperes
- d.20 amperes✓
An overcurrent device supplying a continuous load must be rated at not less than 125 percent of the load: 16 A x 1.25 = 20 A, a standard rating in Table 240.6(A). See NEC 210.20(A).2026 NEC §210.20(A)
For a 16-ampere continuous load, what is the minimum copper branch-circuit conductor at 75 degrees C terminations using THWN?
- a.14 AWG
- b.10 AWG
- c.8 AWG
- d.12 AWG✓
The conductor must carry 125 percent of the continuous load = 20 A. In Table 310.16 (75 degrees C) 14 AWG copper is 20 A but the small-conductor rule NEC 240.4(D) limits 14 AWG to a 15 A device, so 12 AWG (25 A) is the minimum. See NEC 210.19(A).2026 NEC §210.19(A)(1)
Seven current-carrying 8 AWG THWN-2 copper conductors are installed in one raceway at a 30 degrees C ambient. What is the adjusted ampacity of each?
- a.44 amperes
- b.38.5 amperes✓
- c.33 amperes
- d.27.5 amperes
Begin at the 90 degrees C ampacity of 8 AWG copper, 55 A (Table 310.16), then apply the 70 percent adjustment for 7 through 9 current-carrying conductors: 55 x 0.70 = 38.5 A. See NEC 310.15(C)(1).2026 NEC Table 310.15(C)(1)
Five current-carrying 6 AWG THHN copper conductors run in a raceway through a 40 degrees C ambient. What is the adjusted ampacity of each?
- a.65 amperes
- b.48 amperes
- c.60 amperes
- d.54.6 amperes✓
The 90 degrees C ampacity of 6 AWG copper is 75 A. Apply the 36 to 40 degrees C correction of 0.91 and the 4 to 6 conductor adjustment of 0.80: 75 x 0.91 x 0.80 = 54.6 A. See NEC 310.15 and Table 310.16.2026 NEC Table 310.16
Along a dwelling kitchen countertop, no point measured horizontally along the wall line may be more than what distance from a receptacle outlet?
- a.36 inches
- b.24 inches✓
- c.48 inches
- d.12 inches
No point along the kitchen counter wall line may be more than 24 inches from a receptacle, which places outlets no more than 48 inches apart. See NEC 210.52(C)(1).2026 NEC §210.52(C)(1)
A kitchen countertop or work surface must have a receptacle outlet if it is at least what width?
- a.12 inches✓
- b.18 inches
- c.6 inches
- d.24 inches
A countertop or work surface that is 12 inches or wider must be provided with receptacle outlets under the countertop rules. See NEC 210.52(C).2026 NEC §210.52(C)
At least one receptacle outlet must be installed within what distance of the outside edge of each dwelling bathroom basin?
- a.6 feet
- b.3 feet✓
- c.2 feet
- d.1 foot
A receptacle must be located within 3 feet of the outside edge of each bathroom sink, on a wall or partition adjacent to the sink, on the countertop, or on the side or face of the sink cabinet. See NEC 210.52(D)(1) and (D)(2).2026 NEC §210.52(D)(1)
What is the minimum branch-circuit rating required for the dwelling laundry receptacle outlet(s)?
- a.15 amperes
- b.30 amperes
- c.20 amperes✓
- d.25 amperes
At least one 20-ampere branch circuit must supply the laundry receptacle outlet(s), and it may not serve other outlets. See NEC 210.11(C)(2) and 210.52(F).2026 NEC §210.11(C)(2)
Using the standard method, what is the general lighting load for a 2,500-square-foot dwelling before demand factors?
- a.3,750 volt-amperes
- b.7,500 volt-amperes
- c.5,000 volt-amperes✓
- d.6,250 volt-amperes
Under the standard method, dwelling general lighting is calculated at 2 volt-amperes per square foot: 2,500 x 2 = 5,000 VA. The 7,500 VA answer uses 3 volt-amperes per square foot, which is not the current value. See NEC 120.41.2026 NEC §120.41
Using the standard demand table, what is the demand load for a single 16-kilowatt household electric range?
- a.8 kilowatts
- b.16 kilowatts
- c.9.6 kilowatts✓
- d.12 kilowatts
Column C for one range is 8 kilowatts. Note 1 increases that value 5 percent for each kilowatt over 12: 16 kW is 4 over, so 8 x 1.20 = 9.6 kilowatts. See NEC Table 120.55, Note 1.2026 NEC Table 120.55
A store lighting load of 20 amperes operates continuously. What is the minimum standard branch-circuit overcurrent device rating?
- a.20 amperes
- b.30 amperes
- c.35 amperes
- d.25 amperes✓
The device must be at least 125 percent of the continuous load: 20 x 1.25 = 25 A, which is a standard rating. See NEC 210.20(A).2026 NEC §210.20(A)
Four current-carrying 10 AWG THHN copper conductors share one raceway at a 30 degrees C ambient. What is the adjusted ampacity of each before termination limits?
- a.28 amperes
- b.30 amperes
- c.32 amperes✓
- d.35 amperes
The 90 degrees C ampacity of 10 AWG copper is 40 A, and the 4 to 6 conductor adjustment is 80 percent: 40 x 0.80 = 32 A. The final overcurrent device is still limited to 30 A by NEC 240.4(D). See NEC 310.15(C)(1).2026 NEC Table 310.15(C)(1)
A branch circuit supplies a 44-ampere continuous load. What is the minimum standard overcurrent device rating?
- a.50 amperes
- b.55 amperes
- c.70 amperes
- d.60 amperes✓
44 x 1.25 = 55 A, which is not a standard rating, so the next standard size of 60 A must be used. See NEC 210.20(A) and Table 240.6(A).2026 NEC §210.20(A)
What is the maximum continuous load permitted on a 15-ampere branch circuit?
- a.18 amperes
- b.12 amperes✓
- c.15 amperes
- d.10 amperes
A continuous load may not exceed 80 percent of the overcurrent device rating: 15 x 0.80 = 12 A. See NEC 210.20(A).2026 NEC §210.20(A)
In a dwelling-unit load calculation, how are the general-use 15- and 20-ampere receptacle outlets handled?
- a.They are calculated at 180 volt-amperes each in addition to the lighting load
- b.They are omitted from the load calculation entirely
- c.They are calculated at 1.5 amperes each
- d.They are included in the general lighting volt-amperes and are not calculated separately✓
In dwelling units, general-use receptacle outlets rated 20 amperes or less are covered by the general lighting unit load of 2 VA per square foot, and no additional load is calculated for them. See NEC 120.41.2026 NEC §120.41
A branch circuit supplies a 32-ampere continuous load. Using 75 degrees C copper terminations, what is the minimum conductor size?
- a.6 AWG
- b.10 AWG
- c.12 AWG
- d.8 AWG✓
The conductor must carry at least 125 percent of the continuous load: 32 x 1.25 = 40 A. In the 75 degrees C column 10 AWG (35 A) fails and 8 AWG (50 A) qualifies. See NEC 210.19(A) and Table 310.16.2026 NEC §210.19(A)(1)
Which dwelling-unit location requires arc-fault circuit-interrupter protection for 120-volt, 15- and 20-ampere branch circuits?
- a.A bathroom
- b.A bedroom✓
- c.An unfinished basement
- d.An outdoor receptacle
AFCI protection covers most habitable dwelling areas, including bedrooms, kitchens, living rooms and laundry areas. Bathrooms, unfinished basements and outdoor receptacles are addressed by GFCI rather than AFCI requirements. See NEC 210.12(B).2026 NEC §210.12(B)
Which dwelling-unit location requires GFCI protection for 125-volt, 15- and 20-ampere receptacles?
- a.A living-room wall receptacle
- b.A bedroom receptacle
- c.A hallway receptacle
- d.A garage✓
NEC 210.8(A) lists garages among the GFCI areas along with bathrooms, kitchens, laundry areas, basements, crawl spaces and outdoors. Living rooms, bedrooms and hallways are AFCI areas instead.2026 NEC §210.8(A)
What is the minimum size copper equipment grounding conductor for a circuit protected at 60 amperes?
- a.10 AWG✓
- b.12 AWG
- c.8 AWG
- d.6 AWG
Table 250.122 is entered by the rating of the overcurrent device ahead of the circuit, and the 60-ampere row calls for 10 AWG copper. 12 AWG is listed for 20 amperes, 8 AWG for 100 amperes, and 6 AWG for 200 amperes, so all three are the wrong rows.2026 NEC Table 250.122
What is the minimum size copper equipment grounding conductor for a circuit protected at 100 amperes?
- a.8 AWG✓
- b.10 AWG
- c.6 AWG
- d.4 AWG
Table 250.122 is entered by the overcurrent device rating, and the 100-ampere row calls for 8 AWG copper. The 10 AWG row is 60 amperes and 6 AWG is 200 amperes. See NEC Table 250.122.2026 NEC Table 250.122
What is the minimum size copper equipment grounding conductor for a 20-ampere branch circuit?
- a.14 AWG
- b.10 AWG
- c.8 AWG
- d.12 AWG✓
Table 250.122 lists 12 AWG copper at 20 amperes. 14 AWG is the 15-ampere value and 10 AWG is the 60-ampere value. See NEC Table 250.122.2026 NEC Table 250.122
When ungrounded conductors are increased in size for voltage drop, how must the equipment grounding conductor be adjusted?
- a.Doubled in every case, regardless of how much the ungrounded conductors grew
- b.Increased proportionally to the ungrounded conductors' increase in circular-mil area✓
- c.Sized only from Table 250.122 by the overcurrent device rating
- d.Left unchanged, because the overcurrent device rating did not change
Where ungrounded conductors are increased in size, a wire-type equipment grounding conductor must be increased in proportion to the increase in circular-mil area of the ungrounded conductors. See NEC 250.122(D).2026 NEC §250.122(D)
An equipment grounding conductor of the wire type is never required to be larger than what?
- a.The circuit conductors supplying the equipment✓
- b.Twice the value shown in Table 250.122
- c.6 AWG copper in all cases
- d.The ungrounded service conductor size in every case
An equipment grounding conductor need not be larger than the circuit conductors supplying the equipment. See NEC 250.122(A).2026 NEC §250.122(A)
Under the general rule for conductors rated up to 2000 volts, what is the smallest copper conductor size permitted?
- a.18 AWG copper
- b.16 AWG copper✓
- c.14 AWG copper
- d.12 AWG copper
The general minimum conductor size is 16 AWG for copper, 14 AWG for copper-clad aluminum and 12 AWG for aluminum, unless another part of the Code permits something else. Table 210.24(1) shows the same thing for branch circuits: 16 AWG copper on a 10-ampere circuit and 14 AWG on a 15-ampere circuit. See 2026 NEC 310.5(A).2026 NEC §310.5(A)
A 40-ampere branch circuit supplies two receptacles. According to Table 210.21(B)(3), what ampere rating may those receptacles have?
- a.30 or 40 amperes
- b.40 amperes only
- c.40 or 50 amperes✓
- d.50 amperes only
On a circuit that supplies two or more receptacles, the receptacle rating must match the table for the circuit rating. For a 40-ampere circuit the table permits 40- or 50-ampere receptacles. A 30-ampere receptacle is below the table value, and the two single-rating answers each leave out a permitted choice. See Table 210.21(B)(3).2026 NEC Table 210.21(B)(3)
A branch circuit that supplies two or more outlets is rated larger than 50 amperes. Which loads may it supply?
- a.Only nonlighting outlet loads✓
- b.Only fixed lighting with heavy-duty lampholders
- c.Any lighting or appliance load up to its rating
- d.Only cooking appliances that are fastened in place
Multiple-outlet branch circuits larger than 50 amperes are limited to nonlighting outlet loads. Fixed lighting with heavy-duty lampholders is a use allowed on 30-, 40- and 50-ampere circuits in other than dwellings, and fastened-in-place cooking appliances describe the 40- and 50-ampere circuit rule. No lighting of any kind may be on a circuit above 50 amperes. See 210.23(E).2026 NEC §210.23(E)
In a dwelling unit, a hallway must have at least one receptacle outlet when its length, measured along the centerline without passing through a doorway, is at least:
- a.6 ft
- b.10 ft✓
- c.12 ft
- d.20 ft
A dwelling hallway 10 feet or more in length needs at least one receptacle outlet. The 6 foot figure is the wall-space spacing rule for rooms, and the other lengths do not appear in this rule. See 210.52(H).2026 NEC §210.52(H)
For an attached garage of a one-family dwelling, which statement gives the required receptacle outlet arrangement?
- a.One on each wall, no more than 18 in. above the floor
- b.One for the whole garage, no more than 5 1/2 ft above the floor
- c.One in each vehicle bay, no more than 6 1/2 ft above the floor
- d.One in each vehicle bay, no more than 5 1/2 ft above the floor✓
Each attached garage, and each detached garage with electric power, needs at least one receptacle outlet in each vehicle bay, mounted not more than 5 1/2 feet above the floor. A single outlet for the whole garage does not satisfy a multi-bay garage. The 6 1/2 foot height belongs to the outdoor receptacle rule, and there is no per-wall requirement. See 210.52(G)(1).2026 NEC §210.52(G)(1)
In a dwelling unit, lighting outlets for an interior stairway must be controlled by a wall switch or listed wall-mounted control device at each floor level and each landing with a stairway entry when the stairway has at least how many risers between floor levels?
- a.Three or more
- b.Four or more
- c.Five or more
- d.Six or more✓
Control at each floor level and at each landing level that includes a stairway entry is required where the interior stairway has six or more risers between floor levels. Stairways with fewer risers still need a lighting outlet but not the multi-location control. See 210.70(A)(2).2026 NEC §210.70(A)(2)