Motors and Generators

A feeder supplies a 25-horsepower motor (34 amperes) and a 10-horsepower motor (14 amperes), both 460 volts three phase. What minimum conductor ampacity is required?

  • a.67.5 amperes
  • b.60 amperes
  • c.48 amperes
  • d.56.5 amperes✓

Feeder conductors for several motors must carry 125 percent of the largest motor full-load current plus the sum of the other full-load currents: (34 x 1.25) + 14 = 42.5 + 14 = 56.5 A. The 48-ampere answer simply adds the two currents, and 67.5 amperes wrongly applies 125 percent to the total of both motors.2026 NEC §430.24

Motors and Generators

A feeder supplies two three-phase motors with table full-load currents of 34 amperes and 14 amperes. The largest branch-circuit short-circuit and ground-fault protective device is 90 amperes. What is the maximum feeder overcurrent device rating?

  • a.90 amperes
  • b.104 amperes
  • c.110 amperes
  • d.100 amperes✓

The feeder device may not exceed the largest branch-circuit short-circuit and ground-fault protective device plus the sum of the full-load currents of the other motors: 90 + 14 = 104 A. Since 104 is not a standard rating and this is a maximum rather than a minimum, the next lower standard size of 100 amperes must be selected. Choosing 110 amperes would exceed the calculated ceiling.2026 NEC §430.62(A)

Motors and Generators

When sizing motor branch-circuit conductors and short-circuit protection, which current value must be used?

  • a.The locked-rotor current from the nameplate code letter
  • b.The motor nameplate full-load amperes
  • c.The full-load current from Table 430.248 or 430.250✓
  • d.The larger of nameplate current or table current

Conductor sizing, branch-circuit protection and disconnect rating are all based on the table values, which are conservative and independent of a particular manufacturer's nameplate. Nameplate current is used only for overload protection under 430.32, and locked-rotor current is used for withstand and disconnect horsepower comparisons, not for conductor sizing.2026 NEC §430.6(A)(1)

Motors and Generators

A continuous-duty motor over 1 horsepower is marked with a temperature rise of 40 degrees C but no service factor. What percentage of nameplate full-load current sets the maximum overload device?

  • a.140 percent
  • b.115 percent
  • c.125 percent✓
  • d.250 percent

Motors with a marked temperature rise not over 40 degrees C, like those with a service factor of 1.15 or greater, are permitted overload protection at 125 percent of nameplate current. The 115 percent figure applies to all other motors, 140 percent is the allowance when the initial setting will not carry the load, and 250 percent is a short-circuit protection value.2026 NEC §430.32(A)(1)

Motors and Generators

A continuous-duty motor over 1 horsepower has no marked service factor and no marked temperature rise. What is the maximum overload device rating as a percentage of nameplate full-load current?

  • a.140 percent
  • b.125 percent
  • c.115 percent✓
  • d.175 percent

Motors that carry neither a service factor of 1.15 or greater nor a marked temperature rise of 40 degrees C or less are limited to 115 percent of nameplate current, because there is less thermal margin available. The 125 percent value applies to the better-rated motors, 140 percent is the most those better-rated motors may be raised to when the motor will not start (this motor would be limited to 130 percent), and 175 percent is a fuse sizing percentage.2026 NEC §430.32(A)(1)

Motors and Generators

A generator has a nameplate current rating of 200 amperes and no overcurrent protection of its own. What minimum conductor ampacity is required from the generator terminals to the first distribution device containing overcurrent protection?

  • a.230 amperes✓
  • b.200 amperes
  • c.250 amperes
  • d.160 amperes

Conductors from generator terminals to the first distribution device containing overcurrent protection must have an ampacity of at least 115 percent of the nameplate current rating: 200 x 1.15 = 230 A, which corresponds to 4/0 copper at 75 degrees C. The 200-ampere answer omits the factor, 250 amperes uses 125 percent, and 160 amperes derates rather than uprates.2026 NEC §445.13(A)

Motors and Generators

A motor with a service factor of 1.16 will not start because the overload device trips, even though it is sized at 125 percent of nameplate current. To what maximum percentage may the overload device be increased?

  • a.140 percent✓
  • b.130 percent
  • c.150 percent
  • d.175 percent

Where the overload device selected at the basic percentage is not sufficient to start the motor or carry the load, motors with a service factor of 1.15 or greater or a marked temperature rise of 40 degrees C or less may be increased to 140 percent of nameplate current. The 130 percent ceiling applies to all other motors, and 175 percent is a fuse percentage for short-circuit protection.2026 NEC §430.32(C)

Motors and Generators

What is the maximum non-time-delay fuse permitted for branch-circuit short-circuit and ground-fault protection of a 34-ampere three-phase squirrel-cage motor, using the next standard size allowance?

  • a.110 amperes✓
  • b.100 amperes
  • c.90 amperes
  • d.125 amperes

Non-time-delay fuses are permitted at 300 percent of full-load current: 34 x 3.00 = 102 A, which is not a standard rating, so the next standard size of 110 amperes may be used. The 90-ampere answer belongs to the inverse-time breaker at 250 percent, and 125 amperes skips a standard size.2026 NEC Table 430.52(C)(1)

Motors and Generators

A 20-horsepower, 208-volt three-phase motor has a table full-load current of 59.4 amperes. What is the minimum copper branch-circuit conductor at 75 degrees C terminations?

  • a.6 AWG
  • b.4 AWG✓
  • c.3 AWG
  • d.8 AWG

The conductor must carry 59.4 x 1.25 = 74.25 A. In the 75 degrees C column, 6 AWG copper is 65 A and falls short, while 4 AWG copper at 85 A is adequate. Choosing 3 AWG is oversized for the minimum, and 8 AWG at 50 A is well below the requirement.2026 NEC §430.22

Motors and Generators

How many running overload protective devices are required for a three-phase alternating-current motor?

  • a.One, in any phase
  • b.Two, in any two phases
  • c.Three, one in each phase✓
  • d.Four, one in each conductor

Table 430.37 requires a three-phase motor to have an individual overload device in each of the three ungrounded conductors, so that a single-phasing condition, which overloads the remaining windings, is detected. One or two devices could miss an overload on an unprotected phase.2026 NEC Table 430.37

Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Motors and Generators

On a feeder supplying several motors, 125 percent is applied to which motor's full-load current?

  • a.The highest-rated motor, meaning the one with the largest full-load current✓
  • b.The smallest motor, meaning the one with the lowest full-load current
  • c.Every motor on the feeder, each at 125 percent of its full-load current
  • d.The motor with the highest horsepower nameplate regardless of current

Feeder conductors are sized at 125 percent of the largest motor full-load current plus the sum of the full-load currents of the other motors, and the largest motor is the one with the highest rated full-load current per 430.17. Applying 125 percent to every motor over-sizes the feeder.2026 NEC §430.24

Motors and Generators

A 20-horsepower, 460-volt, three-phase squirrel-cage motor has a table full-load current of 27 amperes. Using 75 degrees C copper terminations, what is the minimum branch-circuit conductor size?

  • a.8 AWG
  • b.12 AWG
  • c.6 AWG
  • d.10 AWG✓

Single-motor branch-circuit conductors must carry at least 125 percent of the table full-load current: 27 x 1.25 = 33.75 A. In the 75 degrees C column 12 AWG (25 A) fails and 10 AWG (35 A) qualifies. See NEC 430.22, Table 430.250 and Table 310.16.2026 NEC §430.22

Motors and Generators

A 20-horsepower motor has a nameplate full-load current of 26 amperes and a marked service factor of 1.15. What is the maximum separate overload device rating?

  • a.33.75 amperes
  • b.29.9 amperes
  • c.32.5 amperes✓
  • d.26 amperes

Overload protection is based on nameplate current, and a service factor of 1.15 or greater permits 125 percent: 26 x 1.25 = 32.5 A. The 115 percent factor (29.9 A) applies only to lower-rated motors. See NEC 430.32(A)(1).2026 NEC §430.32(A)(1)

Motors and Generators

A three-phase squirrel-cage motor has a table full-load current of 27 amperes. What is the maximum inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection, using the next standard size allowance?

  • a.90 amperes
  • b.70 amperes✓
  • c.60 amperes
  • d.80 amperes

An inverse-time breaker is permitted at 250 percent of full-load current: 27 x 2.50 = 67.5 A, which is not standard, so the next higher standard size of 70 A may be used. See Table 430.52(C)(1) and 430.52(C)(1)(a).2026 NEC Table 430.52(C)(1)

Motors and Generators

A three-phase squirrel-cage motor has a table full-load current of 27 amperes. What is the maximum dual-element time-delay fuse at the standard 175 percent, using the next standard size allowance?

  • a.40 amperes
  • b.50 amperes✓
  • c.60 amperes
  • d.45 amperes

Dual-element time-delay fuses are permitted at 175 percent: 27 x 1.75 = 47.25 A, and the next standard size is 50 A. See Table 430.52(C)(1).2026 NEC Table 430.52(C)(1)

Motors and Generators

A three-phase squirrel-cage motor has a table full-load current of 27 amperes. What is the maximum non-time-delay fuse at the standard 300 percent, using the next standard size allowance?

  • a.110 amperes
  • b.80 amperes
  • c.90 amperes✓
  • d.100 amperes

Non-time-delay fuses are permitted at 300 percent: 27 x 3.00 = 81 A, and the next standard size is 90 A. See Table 430.52(C)(1).2026 NEC Table 430.52(C)(1)

Motors and Generators

A 25-horsepower, 208-volt, three-phase squirrel-cage motor has a table full-load current of 74.8 amperes. Using 75 degrees C copper terminations, what is the minimum branch-circuit conductor size?

  • a.6 AWG
  • b.4 AWG
  • c.2 AWG
  • d.3 AWG✓

The conductor must carry 74.8 x 1.25 = 93.5 A. In the 75 degrees C column 4 AWG (85 A) fails and 3 AWG (100 A) qualifies. See NEC 430.22, Table 430.250 and Table 310.16.2026 NEC §430.22

Motors and Generators

A three-phase squirrel-cage motor has a table full-load current of 74.8 amperes. What is the maximum inverse-time circuit breaker at 250 percent, using the next standard size allowance?

  • a.150 amperes
  • b.200 amperes✓
  • c.225 amperes
  • d.175 amperes

74.8 x 2.50 = 187 A, which is not standard, so the next standard size of 200 A may be used. See Table 430.52(C)(1).2026 NEC Table 430.52(C)(1)

Motors and Generators

A feeder supplies a 25-horsepower motor (34 amperes) and a 15-horsepower motor (21 amperes), both 460 volts three-phase. What minimum conductor ampacity is required?

  • a.68.75 amperes
  • b.48.75 amperes
  • c.63.5 amperes✓
  • d.55 amperes

Feeder conductors carry 125 percent of the largest motor plus the other full-load currents: (34 x 1.25) + 21 = 42.5 + 21 = 63.5 A. See NEC 430.24.2026 NEC §430.24

Motors and Generators

A feeder supplies two three-phase motors with table full-load currents of 34 amperes and 21 amperes. The largest branch-circuit short-circuit and ground-fault protective device is 90 amperes. What is the maximum feeder overcurrent device rating?

  • a.100 amperes
  • b.111 amperes
  • c.125 amperes
  • d.110 amperes✓

The feeder device may not exceed the largest branch device plus the other motors' full-load currents: 90 + 21 = 111 A. Since 111 is not standard and this is a maximum, the next lower standard size of 110 A is used. See NEC 430.62(A).2026 NEC §430.62(A)

Motors and Generators

A generator has a nameplate current rating of 150 amperes and no overcurrent protection of its own. What minimum conductor size is required from the generator terminals to the first distribution device containing overcurrent protection, using 75 degrees C copper?

  • a.3/0 AWG
  • b.2/0 AWG✓
  • c.1 AWG
  • d.1/0 AWG

Conductors from the generator terminals to the first device must be at least 115 percent of the nameplate current: 150 x 1.15 = 172.5 A. In the 75 degrees C column 1/0 (150 A) fails and 2/0 (175 A) qualifies. See NEC 445.13(A).2026 NEC §445.13(A)

Motors and Generators

A continuous-duty motor with no marked service factor and no marked temperature rise will not start because the overload device selected at the basic percentage keeps tripping. To what maximum percentage of nameplate current may the overload device be increased?

  • a.125 percent
  • b.150 percent
  • c.130 percent✓
  • d.140 percent

Motors that do not have a service factor of 1.15 or greater or a marked temperature rise of 40 degrees C or less may be increased only to 130 percent, while better-rated motors may go to 140 percent. See NEC 430.32(C).2026 NEC §430.32(C)

Motors and Generators

How many running overload protective devices are required for a single-phase, two-wire alternating-current motor?

  • a.One✓
  • b.Three
  • c.Four
  • d.Two

Table 430.37 requires one overload device in one ungrounded conductor for a single-phase, two-wire motor, whereas a three-phase motor requires one in each of the three phases. See NEC Table 430.37.2026 NEC Table 430.37

Motors and Generators

A 5-horsepower, 460-volt, three-phase motor has a table full-load current of 7.6 amperes. Using 75 degrees C copper, what is the minimum branch-circuit conductor size?

  • a.16 AWG
  • b.14 AWG✓
  • c.12 AWG
  • d.10 AWG

The conductor must carry 7.6 x 1.25 = 9.5 A, and 14 AWG copper (20 A at 75 degrees C) is adequate. Although 16 AWG has enough ampacity, 430.22(G) makes 14 AWG the smallest size for motor conductors unless the special conditions for 18 or 16 AWG are met, and the question gives none. See NEC 430.22 and Table 310.16.2026 NEC §430.22

Motors and Generators

A continuous-duty motor over 1 horsepower is marked with a temperature rise of 40 degrees C. What percentage of nameplate full-load current sets the maximum overload device?

  • a.140 percent
  • b.115 percent
  • c.125 percent✓
  • d.130 percent

A motor with a marked temperature rise not over 40 degrees C, like one with a service factor of 1.15 or greater, is permitted overload protection at 125 percent of nameplate current. See NEC 430.32(A)(1).2026 NEC §430.32(A)(1)

Motors and Generators

A feeder supplies a 30-horsepower motor (40 amperes), a 20-horsepower motor (27 amperes) and a 10-horsepower motor (14 amperes), all 460 volts three-phase. What minimum conductor ampacity is required?

  • a.91 amperes✓
  • b.101.25 amperes
  • c.81 amperes
  • d.95 amperes

Feeder ampacity = 125 percent of the largest motor plus the sum of the others: (40 x 1.25) + 27 + 14 = 50 + 41 = 91 A. See NEC 430.24.2026 NEC §430.24

Motors and Generators

Other than at one- and two-family dwelling units, a generator must be provided with a remote emergency shutdown device when its rating is greater than:

  • a.10 kW
  • b.15 kW✓
  • c.25 kW
  • d.50 kW

The remote emergency shutdown requirement applies to generators rated greater than 15 kW that are not at one- and two-family dwellings. The other ratings are not the threshold given in the section. See 445.19(B).2026 NEC §445.19(B)

Motors and Generators

A continuous-duty motor has an integral thermal protector and a table full-load current of 8 amperes. The ultimate trip current of the protector may not exceed what percentage of that full-load current?

  • a.125%
  • b.140%
  • c.156%
  • d.170%✓

For a thermal protector that is integral with the motor, the limit depends on the table full-load current: 170 percent where it does not exceed 9 amperes. The 156 percent value applies from 9.1 through 20 amperes and 140 percent applies above 20 amperes. The 125 percent figure is for separate overload devices and is based on nameplate current. See 430.32(A)(2).2026 NEC §430.32(A)(2)

Motors and Generators

According to Table 430.52(C)(1), an inverse-time circuit breaker used as the branch-circuit short-circuit and ground-fault protective device for a wound-rotor motor may be rated at no more than what percentage of the motor full-load current?

  • a.150%✓
  • b.175%
  • c.250%
  • d.300%

The wound-rotor row of the table limits an inverse-time breaker to 150 percent of full-load current. The 250 percent figure is the inverse-time breaker value for squirrel-cage and synchronous motors, 175 percent is the dual-element fuse value for those motors, and 300 percent is their nontime-delay fuse value. See Table 430.52(C)(1).2026 NEC Table 430.52(C)(1)

Motors and Generators

One feeder supplies only three continuous-duty, three-phase, 460-volt motors: 15 hp, 10 hp and 7 1/2 hp. Table 430.250 lists their full-load currents as 21, 14 and 11 amperes. What is the minimum ampacity of the feeder conductors?

  • a.46 A
  • b.48.75 A
  • c.49.5 A
  • d.51.25 A✓

A feeder for several motors needs 125 percent of the full-load current of the highest rated motor plus the full-load currents of the others. Working: 21 x 1.25 = 26.25, then 26.25 + 14 + 11 = 51.25 amperes. The 46 ampere value is the plain sum with no increase, and the two middle values put the 25 percent on the wrong motor. See 430.24.2026 NEC §430.24

Motors and Generators

A 15 hp, 230-volt, three-phase squirrel-cage motor has a table full-load current of 42 amperes. Using Table 430.52(C)(1) and the standard ratings in Table 240.6(A), what is the maximum standard dual-element time-delay fuse for the branch-circuit short-circuit protection, assuming the motor starts normally?

  • a.70 A
  • b.80 A✓
  • c.90 A
  • d.110 A

The table allows a dual-element time-delay fuse at 175 percent of full-load current: 42 x 1.75 = 73.5 amperes. That is not a standard rating, so the next higher standard size, 80 amperes, is permitted. The 70 ampere answer rounds down when rounding up is allowed, 90 amperes uses the higher limit reserved for a motor that will not start, and 110 amperes uses the breaker percentage. See 430.52(C)(1) and Table 240.6(A).2026 NEC §430.52(C)(1)

Motors and Generators

A 7 1/2 hp, 230-volt, three-phase squirrel-cage motor has a table full-load current of 22 amperes. What is the maximum standard inverse-time circuit breaker permitted for its branch-circuit short-circuit and ground-fault protection, assuming the motor starts normally?

  • a.30 A
  • b.40 A
  • c.50 A
  • d.60 A✓

An inverse-time breaker may be rated at 250 percent of the table full-load current: 22 x 2.5 = 55 amperes. Since 55 is not a standard rating, the next higher standard size of 60 amperes is permitted. The 50 ampere answer rounds down, 40 amperes comes from the 175 percent fuse column, and 30 amperes comes from the 125 percent conductor rule. See 430.52(C)(1) and Table 240.6(A).2026 NEC §430.52(C)(1)

Motors and Generators

A continuous-duty motor has a nameplate full-load current of 18 amperes, a marked service factor of 1.0 and a marked temperature rise of 50°C. What is the maximum setting of its separate overload device?

  • a.20.7 A✓
  • b.22.5 A
  • c.23.4 A
  • d.25.2 A

A separate overload device is set from the nameplate current. The 125 percent allowance needs a service factor of 1.15 or more or a temperature rise of 40°C or less, and this motor has neither, so 115 percent applies: 18 x 1.15 = 20.7 amperes. The 22.5 ampere answer uses 125 percent, and the two highest values use the larger percentages that apply only when the motor cannot start. See 430.32(A)(1).2026 NEC §430.32(A)(1)

Motors and Generators

A motor in an intermittent-duty application has a 15-minute time rating and a nameplate current of 40 amperes. Using Table 430.22(E), what is the minimum ampacity of its branch-circuit conductors?

  • a.34 A✓
  • b.36 A
  • c.48 A
  • d.56 A

For duty-cycle service the conductor size is a percentage of the nameplate current that depends on the type of duty and the time rating of the motor. Intermittent duty with a 15-minute rated motor is 85 percent: 40 x 0.85 = 34 amperes. The other values come from the periodic duty row, the short-time or varying duty rows, and the continuous-rated motor column. See Table 430.22(E).2026 NEC Table 430.22(E)

Motors and Generators

A 3 hp, 115-volt, single-phase, continuous-duty motor has a table full-load current of 34 amperes. What is the minimum ampacity of its branch-circuit conductors?

  • a.34 A
  • b.42.5 A✓
  • c.51 A
  • d.59.5 A

Conductors for a single continuous-duty motor need an ampacity of at least 125 percent of the table full-load current: 34 x 1.25 = 42.5 amperes. The 34 ampere answer applies no increase, and the higher values use 150 and 175 percent, which are not conductor rules for this motor. See 430.22 and Table 430.248.2026 NEC §430.22

Electrical Control Devices and Disconnecting Means

A 30-horsepower, 460-volt three-phase motor has a table full-load current of 40 amperes. What is the minimum ampere rating of the disconnecting means?

  • a.50 amperes
  • b.40 amperes
  • c.46 amperes✓
  • d.60 amperes

The disconnecting means must have an ampere rating of at least 115 percent of the full-load current: 40 x 1.15 = 46 A, so a 60-ampere switch would be the practical selection. The 40-ampere answer omits the 115 percent factor entirely, and 50 or 60 amperes are available equipment ratings rather than the calculated minimum the question asks for.2026 NEC §430.110(A)

Electrical Control Devices and Disconnecting Means

Where must a motor disconnecting means be located relative to the motor?

  • a.Within 25 feet of the motor in all cases
  • b.In sight from the motor location and from the driven machinery location✓
  • c.Anywhere on the same floor level as the motor
  • d.In sight from the motor controller only, on the theory that the controller disconnect is always sufficient and that no separate in-sight rule applies to the motor itself

Under 430.102(B) a disconnecting means must be in sight from the motor location and the driven machinery location. The controller disconnect required by 430.102(A) can do this job when it is in sight from both. An exception lets the motor disconnect be omitted only when the controller disconnect is lockable and, in addition, either an in-sight location is impracticable or adds hazards, or the site is an industrial installation with written safety procedures and qualified persons. Lockability alone is not enough. Under 110.29, in sight means visible and not more than 50 feet away.2026 NEC §430.102(B)

Electrical Control Devices and Disconnecting Means

Under NEC 110.29, what does 'in sight from' mean in terms of distance?

  • a.Anywhere on the same floor level
  • b.Visible and not more than 50 feet away✓
  • c.Within 75 feet whether visible or not
  • d.Visible and not more than 25 feet away

'In sight from' means the equipment is visible and not more than 50 feet distant from the other equipment. See NEC 110.29.2026 NEC §110.29

Electrical Control Devices and Disconnecting Means

A 40-horsepower, 460-volt, three-phase motor has a table full-load current of 52 amperes. What minimum ampere rating must the disconnecting means have?

  • a.46 amperes
  • b.65 amperes
  • c.52 amperes
  • d.59.8 amperes✓

The disconnecting means must be at least 115 percent of the full-load current: 52 x 1.15 = 59.8 A, so a 60-ampere or larger switch would be selected. See NEC 430.110(A).2026 NEC §430.110(A)

Electrical Control Devices and Disconnecting Means

An individual disconnecting means is provided for a 480-volt motor controller. Where must that disconnecting means be located?

  • a.Within 25 ft of the panelboard that supplies the motor
  • b.In sight from the controller location✓
  • c.In the same room as the driven machinery
  • d.Anywhere on the premises if it can be locked open

Section 430.102(A) calls for a disconnecting means for each motor controller, placed in sight from the controller location. The trap is tying the location to the supply panelboard or the driven machine. The machinery matters for the motor disconnect in 430.102(B), not for the controller disconnect.2026 NEC §430.102(A)

Electrical Control Devices and Disconnecting Means

The disconnecting means for a motor controller is also permitted to serve as the disconnecting means for the motor when it is:

  • a.Rated at 200 percent of the motor full-load current
  • b.Located in the same building as the motor
  • c.Marked with the horsepower of the motor
  • d.In sight from the motor location and the driven machinery location✓

Under 430.102(B)(2), the controller disconnect can double as the motor disconnect only if it is in sight from both the motor location and the driven machinery location. A larger rating or a marking does not replace the in-sight condition. Being somewhere in the same building is not enough.2026 NEC §430.102(B)(2)

Electrical Control Devices and Disconnecting Means

When a motor disconnecting means is opened, which conductors must it disconnect?

  • a.All ungrounded supply conductors together✓
  • b.Only one ungrounded conductor, as long as the motor stops
  • c.All ungrounded conductors, each one on its own separate handle
  • d.Only the conductors that feed the motor overload relays

Section 430.103 requires the disconnecting means to open all ungrounded supply conductors, built so that no pole can be operated independently. Opening a single phase may stop the motor but leaves the other conductors energized. Separate handles for each pole are exactly what the rule rules out.2026 NEC §430.103

Electrical Control Devices and Disconnecting Means

A motor circuit has two disconnecting means, one at the controller and one at the motor. How many of them must be readily accessible?

  • a.Neither one, if both can be locked open
  • b.Only the one mounted nearest the motor
  • c.At least one of them✓
  • d.Both of them in every installation

Section 430.107 requires at least one of the disconnecting means to be readily accessible. It does not say which one, so it need not be the one nearest the motor. A lock-open provision does not remove the requirement.2026 NEC §430.107

Electrical Control Devices and Disconnecting Means

Which statement is correct for a motor controller that does not also serve as the disconnecting means?

  • a.It must open every ungrounded conductor to the motor
  • b.It must open the grounded conductor before the others
  • c.It must open the equipment grounding conductor as well
  • d.It need not open all conductors to the motor✓

Section 430.84 says a controller is not required to open all conductors to the motor. That is why a separate disconnecting means, which does open all ungrounded supply conductors, is required. The trap is applying the disconnect rule to the controller.2026 NEC §430.84

Electrical Control Devices and Disconnecting Means

Which mounting location is prohibited for the disconnecting means of an air-conditioning condensing unit?

  • a.On the building wall within sight of the unit
  • b.Within the air-conditioning equipment itself
  • c.On a panel designed to allow access to the equipment✓
  • d.On the unit where the nameplate stays visible

Section 440.14 allows the disconnect to be on or within the equipment, but not on panels that are designed to allow access to the equipment and not where it hides the equipment nameplate. A wall location within sight of and readily accessible from the unit is the ordinary compliant choice.2026 NEC §440.14

Electrical Control Devices and Disconnecting Means

A single-phase, 240-volt room air conditioner uses its attachment plug and receptacle as the disconnecting means. For this to be permitted without a separate disconnect, the manual controls on the unit must be readily accessible and within what distance of the floor?

  • a.4 ft
  • b.6 ft✓
  • c.6 ft 7 in.
  • d.8 ft

Section 440.63 lets the plug and receptacle serve as the disconnect for a single-phase room air conditioner rated 250 volts or less when its manual controls are readily accessible and within 6 ft of the floor. Otherwise an approved manual disconnect must be installed in a readily accessible location within sight of the unit. The 6 ft 7 in. figure is the handle height limit for switches and breakers, a different rule.2026 NEC §440.63

Electrical Control Devices and Disconnecting Means

The disconnecting means for a rooftop refrigeration unit is readily accessible to unqualified persons. An enclosure door or hinged cover that exposes energized parts when open must be:

  • a.Painted red and marked with the circuit voltage
  • b.Interlocked with the compressor contactor coil
  • c.Removed and replaced with a dead-front cover
  • d.Locked or require a tool to open✓

Section 440.11 says that where the disconnecting means is readily accessible to unqualified persons, any enclosure door or hinged cover that exposes energized parts when open must be locked or need a tool to open. Color, signs, or interlocks are not what this rule asks for.2026 NEC §440.11

Electrical Control Devices and Disconnecting Means

What is the maximum number of service disconnects permitted for each service?

  • a.2
  • b.4
  • c.6✓
  • d.8

Section 230.71 starts from one service disconnect per service, and 230.71(B) permits two to six. Six is therefore the ceiling for each service. Disconnects used only for items such as surge-protective devices or power monitoring equipment are not counted toward the six.2026 NEC §230.71(B)

Electrical Control Devices and Disconnecting Means

As a general rule, where must the service disconnect for a one-family dwelling be installed?

  • a.In a readily accessible indoor location nearest the service conductor entrance
  • b.In a readily accessible outdoor location on or within sight of the dwelling✓
  • c.In any accessible location inside an attached garage
  • d.In the basement within 10 ft of the meter socket

Section 230.70(A)(1) puts the service disconnect for one- and two-family dwellings in a readily accessible outdoor location, either on the dwelling or within sight of it. The indoor location nearest the point of entrance is the choice allowed for other occupancies under 230.70(A)(2), and that is the trap here.2026 NEC §230.70(A)(1)

Electrical Control Devices and Disconnecting Means

A service has four service disconnects. As a general rule, how must they be arranged and identified?

  • a.Spread out, with at least 10 ft between each one
  • b.Grouped, with only the largest one marked
  • c.Placed on separate floors, each marked with voltage
  • d.Grouped, with each one marked to show the load it serves✓

Section 230.72(A) requires the two to six service disconnects to be grouped, and each one must be marked to indicate the load served. Scattering them defeats the purpose, which is to let someone shut off the whole building from one place.2026 NEC §230.72(A)